<s>[INST] MD60 No life. Lost ground while operating Summary: MD60 signal phase lost groundwhile operatingI have an 6MDAN-4P5101, single phase, 240v 1 HP. It has run regularly in my shop for 5 years. I lost the ground line while it was operating. I heard I small pop and now it doesn't do anything. I have cycled power and checked the conections to breaker box. All these are working. I fixed the broken ground connection. The display does not come on. No life, nada, zip. Is there any part inside that might be easily replaced or should I go shopping for a new one? [/INST] Usually if you've already cycled power to it a couple of times, and nothing changes on the display, it is damaged and should be sent in to repair, or more probably, you'll need a new one. - fuzzy logic Please remember to Rate the Comments( ) to enhance the reputation of the User who provided help,or close your Topic using the ( ) button over the answer that solved it. Thanks... \\n </s> |
<s>[INST] View Designer issue. How can I create internal HMI tag in View Deisinger. [/INST] I don't believe it is possible to create an internal HMI tag in View Designer. This software is entirely different than FT View ME/SE, so some of the features you may be accustomed to don't necessarily exist here. Not yet, at least.\n </s> |
<s>[INST] Communications Hey guys: do you kwon any cause why cannot communicate with a Ultra3000i even if I check all communications parameters, port settings and RSLinx Classic and Enterprise are shutdown?? [/INST] Sabre, following some technotes that may help... Aid 47739Aid 49520Aid 34935Aid 46489 Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] Powerflex 525 Summary: Not receiving Drive Ready StatusWhen I reset my e-stop signal going to drive, I'm getting 'network ok' signal from the VFD but not the drive ready status within a particular amount of time, say 6 sec. I'm using CPS command to get the status. The ethernet is working fine. Any lead will help. TIA [/INST] Please review Tech Note 588362 PowerFlex 525 Ready Bit is 0 when Stop Command is issued. \\n </s> |
<s>[INST] 1756-L83ES wipe or unlock safety Processor. I've got an upgrade on an existing CPU System problem is the customer has changed the safety Unlock password and doesn't know what it is, and I need to make edits in the safety software. So, the question I have is there a way to brute force the safety open or wipe the CPU so I can download the unlocked programme I have, I can't even Flash the CPU due to the safety being locked. Second to a new processor I've hit a brick wall. [/INST] Factory Reset. You can clear the program from memory on the 5570 controllers. On 5580 controllers, you can clear the program from memory and reset the controller to factory default settings.\n </s> |
<s>[INST] SEW AS7W with PF755 and CIP Motion Summary: Is the AS7W compatible with PF755 and CIP Motion?I have been supplied several SEW motor gearboxes fitted with AS7W encoders instead of the expected AS7Y, they are to be used with PF755 / UFB-1 and CIP Motion. SEW has told me that the AS7W is a Hyperface encoder. I have had no luck getting it to work when Hyperface-SC is selected. Has anyone got any suggestions? I note KB 106072 is not encouraging. [/INST] nan \\n </s> |
<s>[INST] PowerFlex70 and 20CommE We have PF70 drives that are configured to be controlled via the 20CommE module on Ethernet. Works well.In anticipation of a network or PLC crash, can the drive be configured to also respond to hardwired inputs, (start, stop, run at a preset speed) in order to accomodate the emergency situation?Can you program a digital input to transfer control from the 20CommE to hardwire and then back again? Or do you absolutely have to go in through the HIM andmodify the control parameters? Thanks [/INST] wireguy, you may use the Local control function over a Digital input terminal. Take a look to Aid 49630... Also, Aid 41038 gives a similar functionality... Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Command vs. actual position glitch on virtual axis I was wondering if anyone else had run into an issue where .CommandPosition doesn't equal .ActualPosition on a virtual axis. The Rockwell documentation states that a virtual axis doesn't have an actual position, so .ActualPosition returns the same value as .CommandPosition. In my case, I use the command position in an MAOC, and I found a case where I was getting a double trigger of one of the output bits. A trend showed that .ActualPosition was exactly zero, but .CommandPosition was an extremely small number, 2.479553e-8. I'm on version 33.01.00, running on a 5069-L320ERMS2 [/INST] Run the MAOC Position Reference on Actual Position. When e gearing or camming to a Virtual Axis, I always use Actual. \\n </s> |
<s>[INST] Issue with an A-B PowerFlex 753 Summary: Event DigIn Cfg B, DI Run and DI Fwd Reverse at the same time shouldn't be an issueHi, I installed a PF 753 (20F-11ND052AA0NNNNN) Firmware: v2.007.37 with a 24V DC 22-Series I/O Module (20-750-2262C-2R) on slot 4 Configured: DI Stop on Port 0: Dig In Sts.Digital In 1 DI Fwd Reverse on Port 4: Dig In Sts.Input 1 and DI Run on Port 4: Dig In Sts.Input 0 I usually configure inputs this way: two-wire RUN (and normal STOP, ramp or coast), one DI for FWD/REV (if required) and one STOP which I utilize for fast stop (current injection or some other means) In this case I am getting message DigIn Cfg B which dissapears if I disable the Fwd Reverse input. The thing is that I configured the same on another PF 753 v2.005.33 in a similar machine with no issue. I know I can try DI Run Forward and DI Run Reverse instead but I don't want to. Any idea, please Thank you [/INST] The first thing that comes to mind is, why are you using such old firmware? V14.004 is the most current. There were SIGNIFICANT problems with firmware earlier than V4. If you cannot use V14, go as high as your application will permit. Look at the PM manual: https://literature.rockwellautomation.com/idc/groups/literature/documents/pm/750-pm001_-en-p.pdf Go to page 328 of the PDF. This chart documents DIGIN CFG B. I do not see a problem with your configuration based on this chart. Are you sure you have configured the IO as you've described? If you are absolutely sure about your configuration, then I suggest using ControlFlash+ to upgrade the firmware and try again. \\n </s> |
<s>[INST] 700S JOG 1, JOG 2 I have a 700S which has the add on encoder board. The drive is setup to follow the auxiliary encoder encoder with the application of a run input (2 wire). My customer asked me to install a FWD/REV Jog cct. on this application. I setup JOG 1 and JOG 2 on digital inputs 1 and 2, JOG 1 setpoint 10 RPM, JOG 2 setpoint -10 RPM. JOG 1 works fine, JOG 2 almost works, the HIM shows the drive is running I can hear the power module firing, but the motor will not move and the RPM gauge on the HIM shows 0. What have I forgotten to do?? [/INST] First of all I have to say I'm not an expert of this drive... just I'm trying to give some help...:smileytongue: Check Par. 30 (Min. Spd. Ref. Lim.), default is 0; you need to have this set to a negative value if you want use JOG 2 as indicated in your post.Also, Par 153, bit 0 should be 1 (it is by default) to allow bipolar speed reference... Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Powerflex Drive Support on RSLogix Architect Summary: I am using RSLogix Architect V3.6 but i could not import or export powerflex drives to or from RSLogix 5000.Is this feature available with any of the RSlogix Architect versions. [/INST] Hi, Drive support is also not available in RSLogix Architect V20. Please take a look at this article in the Knowledgebase or this article on the forum. \\n </s> |
<s>[INST] Aux encoder with K5500 I need to add a linear encoder to a Kinetix 5500 axis, controlled by a 1769-L33ERM. The 5500 has no auxiliary feedback input so my plan is to use the 1769-HSC to input the encoder signal. I would like some suggestions on how to program the linear scale. One thought I had was to take the difference between the motor encoder and linear encoder positions and add that difference to a MAM instruction's command position. This seems like the least clever solution. Someone had suggested that I create a virtual axis and use the linear encoder as its feedback device, but I do not see a way to do this. If I could do this then this seems like a more elegant solution--I could use a MAG or MDAC to follow the virtual axis in that case. Any other ideas? Thanks! [/INST] I don't think you have many choices. K5500 drives are intended to be low-cost, so do not have all of the features that a K6500 has. One possibility might be to purchase the lowest-cost K350 drive and hook your encoder to that. You don't need a motor; the drive would act simply as a place to bring the linear encoder in as a CIP axis. Then your MAG or MDAC approach would work. Is too late to change to a K6500 drive? What is the data format of the linear encoder? \\n </s> |
<s>[INST] SMC-50 Underload Fault Reset Summary: Cannot reset Using PLC tag, but can reset using drive tab or keypadHello. I am having an issue with a SMC-50 Soft start. The drive has been added to the IO tree of an rslogix application and I can communicate to the drive and I can see status information and also set up certain parameters from the PLC. One thing I cannot do however is reset an underload fault using the clearfault output bit (which is automatically created when adding an SMC-50 addon profile) in ladder logic, however I can reset the fault if I either go on to the SMC-50 drive tab in the PLC application and “clear faults” or from the in built key pad on the front of the MCC. I don’t have to set anything up within the SMC-50 using components workbench do i? I was able to set fault enable outputs directly from the PLC, I just cannot clear a fault using the logicCommands_Clearfault tag. What is the difference in the soft starter between using the “logicCommands_Clearfault tag” output tag or selecting “clear faults” on the alarm section of the drive tab in the IO tree of the plc application. Any help would be appreciated. Note: using 20-COMM-ER module on the drive to communicate to the PLC, no set up using components work bench on the drive itself [/INST] How long are you setting the P2_046_MCC:O.LogicCommand_ClearFault bit in your PLC code? If you're issuing a 1-shot to do this, that's probably not long enough for the signal to get passed via Ethernet. Can you hold it for 1 second? Share a screen-shot of the OTE that calls this tag. \\n </s> |
<s>[INST] PowerFlex70 EC Drives via Ethernet Anyone know the whereabouts in the documentation to calculate the packets per second (PPS) or CIP/TCP connections for a 20-Comm-E adapter? Trying to get a handle on configuring 40 PFlex70 drives on a ControlLogix system. I know it depends on the RPI but not sure about the 20-comm-E adapter... [/INST] fordtt, why don't you use the free tool for Ethernet/IP calculation ? Here the LINK to download it... Take a look to the following screenshot.. Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] Powerflex 40 smoking, but working... Hi.We have an application with about 20 VFD's (PF40 and 400) up and running OK for 3 years.One day the operator noticed that smoke (a lot) where coming out from one of the PF40's, he tripped the EM stop to cut power to the drive. The drive was stopped (motor NOT running) at the time of the smoke.Maintanence people changed the motor (it turned out that the motor also was broken) they did NOT change the drive.After this everything worked fine.What is most likely to burn when the drive is stopped? (Varistors?)Can the faulty motor (short circuit) on the output of the drive make the drive burn without tripping the overload etc? (When motor not running)The circuit breaker on incoming lines to the drive never tripped. And finaly; Yes, the drive is changed now (even thoug its working fine). Best regardsMartin [/INST] We had a problem some years ago on the PF4/40's where our vendor was putting too much conformal coating on the precharge resistor. The drive would smoke for awhile until the coating burned off. Not sure if this is the same problem, but it sounds like it. \\n </s> |
<s>[INST] Max. Motor cable length with/without AC line Filter for Kinetix 5700 Hi everyone, I am using MPM-B1653F-MJ7AAA ( quantity - 1 ) connected with kinetix 5700 2198-S086-ERS3 single axis inverter (quantity - 1). VPL-B115E-PK14AS ( quantity - 6 ) connected with kinetix 5700 2198-D020-ERS3 dual axis inverter (quantity - 3). Single DC bus supply ( 2198- P141) which is 480V AC input So, this DC bus supply is connected with the above 4 invertes. And I am using Single turn Drive to motor feedback cable (so i found that the max cable length is up to 90 m). I am using AC input power type WYE grounded. In the 2198-UM002 manual, I have read that, The sum of the inverter motor-power cable length for all invertes on the same DC bus-Sharing group must not exceed, -1200m when used with 2198-DBRxx-F line filters. -400m when used with 2198-DBxx-F line filters. Since i am using 7 motors, it would be 7*90 = 630m. My questions are: 1. So, in my case is it mandatory to use AC line Filter ? 2. If it is not mandatory will each of my 7 motors still support 90m each with out using the AC line filter. 3. what would be the max. combined length of motor power cable if I am not using AC line Filter? WIll it be 90m each or something else? 4. And how come the combined cable length is 1200m when used with 2198-DRxx-F line filters ? Is it like ( 13 motors * 90m =1170 [approx 1200]) ? [/INST] Hello Chalagulla Please review this manual Drives in Common Bus Configurations with Kinetix 5700 Bus Supplies but you have found all our recommendation already i guess. Yes , we strongly recommended to use a Filter that match your application. an AC line filter have an important role to protect you installation and guaranty the good working condition do you have a specific application that request a remove of the filters ? details please best regards \\n </s> |
<s>[INST] 1336F-b050 Drive Summary: stop drive after 20 minutesWe would like to stop drive after 20 minutes. But this drive is in a stand alone system connected to the pump itself. It has a HIM display, but no TB3 board. What I was going to do is add a timing relay inside and remove the enable after 20 minutes. So here is my question, can the drive have both an HIM (start command and speed control) and a TB3 board? Use start button on the HIM, it would stop 20 minutes later when I removed the enable. Cat [/INST] I would set up the TB3 as a '3-wire' configuration and hold the STOP input true, then interrupt it when you need to stop. You could do the same with the Enable input too. As long as the TB3 doesn't have any exclusive control features programmed (like 2-wire mode, or Local Control) then you can use it to assert a STOP only. STOP is asserted when it is provided by any interface to the drive and cannot be masked out. The -L6 on the end of the part number indicates that there was (when it was delivered from the factory) a 115V AC version of the TB3 discrete input board installed. \\n </s> |
<s>[INST] Controlling position on Ultra 3000 I want to be able to control the position of the motor by giving the drive a specific count. Presets positions restrict me to having only 8 position however I would like to be able to move the drive to a specific position. The psoition count will be eventually generated by a PLC I am looking at using a logix 1400. Any suggestions? [/INST] The Ultra 3000 drive can be configured in a number of operational modes. This includes the capability to follow the commands of a pulse train output from a micrologix controller. I suggest to review the following technotes: Aid 63335 - How to set up an Ultra 3000 to be a Pulse Follower.Aid 17444 - Quick Start using the Pulse Train Output ( PTO ) instruction for the MicroLogix 1100/1200/1400/1500Aid 27781 - Wiring the Micrologix 1500 to the 2098 Ultra 3000 Digital Servo DriveAid 63378 - What is maximum speed I can get from servo motor when interfacing the Micrologix 1400 to the Ultra 3000? Some of the above are only visible if you have a valid TechConnect contract with RA. See also the MX1400 Reference Manual chapter 6 for PTO. Hope this helps, - fuzzy logic \\n </s> |
<s>[INST] Error 'Catastrophic failure' during installing Ultraware v1.64 I have installed Ultraware 1.63 long time ago. This software warning me that 'Unable to open Ultraware local machine registry key. You may need to reinstall Ultraware' So I download the Ultraware v1.64 from rockwell automation software site. But the installer warning me that What can I do to resolve this issue? [/INST] Try the fix attached to Aid 29168 (it is about version 1.61, but why don't try ?) :smileytongue: Otherwise, call Tech Support, there aren't other infos about this strange error... - fuzzy logic \\n </s> |
<s>[INST] PowerFlex 523 Seria A x Serie B Analog Input An OEM was building air compressors using Powerflex 523 Serie A with a Pressure Transducer 4-20mA (2 wire) as a PID feedback connected to pins 11 (+24VDC) and 15 (4-20mA input). Now with Series B is connecting to 11 (24VDC) and 13 (Analog Input) but it is not working. It seems like Common from 24VDC power supply is not connected to the analog circuit. Any suggestion? Regards, Daniel [/INST] Not sure if you have solved this, but if you ground term 14 to term 4 (digital common) it seems to work. \\n </s> |
<s>[INST] How to setup the config between micrologix 1200 - ENI-Interface module and HMI PANEL VIEW PLUS. My problem is my 3 device are in the network I can ping. but for any reazon the HMI don't see the plc. I setup the topic in the HMI proyect but the problem persisting. I used Micrologix 1200, ENI-interface module, HMI panel view plus 400. [/INST] Make sure your PLC shortcut in FTView is copied to the runtime tab.\n </s> |
<s>[INST] Camming I have a PowerFlex DC Drive that I need a Kinetix 6000 Drive and/or motor to cam off of. PowerFlex DC can't be set up as axis so best approach please. [/INST] Your question implies that your DC motor has an encoder. If so, you're in luck but not the way you think. If it's an incremental encoder, I recommend using an encoder splitter (Motrona makes a very nice one). You MIGHT be able to simply parallel the encoder signals without the splitter - it may or may not work. Splitter guarantees it. Split the DC motor's encoder signal, send one to the PF DC drive as normal and bring the other to the aux feedback port on the Kinetix 6000 axis. You can then configure the aux feedback to be a feedback-only axis and let it be the master axis for your camming. You cannnot issue actual motion commands to this master axis, but you can issue passive MAH, MRP commands, and it CAN be the lead axis for camming. You would issue drive commands to the PF DC drive (Run forward, Run reverse, etc). The DC drive is not a motion axis, but the net result means it is the leader. Does this make sense? I can try to explain a different way if needed. But \\n </s> |
<s>[INST] Disable Hw limit Switches control Hi all, I need a way to enable/disable the hardware limit switches of a CIP axis via software like a MSG or SSV or something like that. Do you know if exist a way? The axis type is Kinetix 5500 Best regards. [/INST] See technote QA28637. (Requires TechConnect) If you don't have TechConnect, the note references the CIP Axis Reference Manual: https://literature.rockwellautomation.com/idc/groups/literature/documents/rm/motion-rm003_-en-p.pdf Basically you send a MSG to the drive to Set Attribute Single to the parameter 960. The technote spells it out very well. Regards, RM \\n </s> |
<s>[INST] SMC Flex Par 50 Are the thermistor inputs used to calculate the %MTU ? , and if so can Par 50 be adjusted to give a trip point ? [/INST] MTU is motor thermal usage and is a mathematical model that simulates the amount of heat generated in a motor due to current draw over time. It is based on an I^2T algorigthm (where I is current and T is time). Some of the factors used to calculation are what the full load current of the motor is set at, what the actual current draw of the motor is, and the amount of current used to start the motor. PTC value isn't used for that... it gives you an option to have an enhanced control of motor temperature. An alarm (pre-fault) indication level can be programmed to indicate the unit is getting close to faulting. The alarm modification information is displayed through the LCD, HIM, Communication (if applicable) and alarm contact closing. Parameter 50 is used to set an alarm status in the SMC-Flex based on the programmed level in it...If you want to be advised before %MTU reach 100% and the overload occurs, then you've to program a value at which you will have an alarm...default is 50%. Hope this helps...- fuzzy logic \\n </s> |
<s>[INST] 1756-M02AS Axis Feedback Problems We have a control logix system, using version 13.04. We have a MTS temposonic linear probe that we have connected to a 1756-M02AS card and using feedback only for a display of the position. This works great until the power is removed from the control logix rack for whatever reason, whether it be power outage or turning the power off. When the power is removed and then turned back on we have to cycle the power that goes to the MTS temposonic probe, after we do this it works great again. The part number on this MTS probe is RPM0420UD701S1B6102. We have other MTS probes in use on other machines and don't have this problem. I have contact AB with this problem and they tell me it is a problem with the MTS probe and I need to contact MTS. So I contacted MTS and they tell me that the problem is with the device that we are using to read the feedback. Has anyone ever had this problem? Is there something we could do in the logic to simulate the same thing, like at the first scan or something? Thanks for any help. [/INST] Do you have any error Status on the Axis when the Fault occurs? Have you tried using the MAFR (Motion Axis Fault Reset) in Direct Mode? Possible Workaround is to use the MDO function and the Enable for that Axis to Power the MTS \\n </s> |
<s>[INST] Kinetix and Mitsubishi compatibility Good morning. I am working on a retro fit of an older machine for my employer. The question I have, and can't seem to find the answer to is this: We have a machine that was previously controlled by all mitsubishi products and it was flooded. So the PLC, Servo drive is toast. I want to replace everything with AB, with the exception of the servo motor itself. Can the Kinetixs 2198-H015-ERS control a Mitsubishi HF354BS Servo motor? [/INST] Hello Newton , The Kinetix 5500 servo drive supports Hyperface DSL feedback and Hyperface feedback with Converter to DLS. So the question is what sort of encoder do you have on the Mitsubishi motor? This said, Integration of a 3rd party motor is always a challenging task if you never have done it. So I strongly recommend you to also change the Motor and Cables, because they are the part that wears out faster, and the integration and future maintenance will be much easier. Regards \\n </s> |
<s>[INST] Powerflex 400 heat sink overtemp What else would be causing this issue besides the description in the book? This is a new drive, it has only been running for less than 24hrs when we started having this issue....I have reviewed all the info in the menues and they seem to match what is on the name plate..... [/INST] Hmmm... please check if you have the condition indicated in Aid 58083 In case, contact your Rockwell Automation representative or Tech Support... Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Kinetix 5100 Hi All, Does anyone know if it is possible to read the digital input status of a Kinetix 5100 servo drive? Regards, Ian [/INST] It looks like you can MSG the drive to get information https://literature.rockwellautomation.com/idc/groups/literature/documents/um/2198-um004_-en-p.pdf tells you how to setup the MSG's https://literature.rockwellautomation.com/idc/groups/literature/documents/rd/2198-rd002_-en-p.xlsx is a list of all of the Drive Parameters available but I did not see a parameter for the status of the digital input. Jesse \\n </s> |
<s>[INST] Powerflex 523 Ready and Digital In Feedback Summary: Ready and Digital In Status not working I have 52 Powerflex 523's on an Ethernet network using 523-E2P modules and DLR for the network. The drives are connected to an EN2TR module on the Control Logix Rack. PLC is L62 V20.12 EN2TR module is V4.4 Powerflex Add On Profile is PF5ClassAOP V1.03 The safety circuit is low level, Enable relays from the E-stop circuit tied to terminals 11 & 1 and set to enable. The problem I am having is the Ready feedback to the PLC is not working correctly. When I lose the enable circuit, I still have the input that the drive is Ready. Also, the feedback for Digital Inputs 1-4 are not working either to the PLC. The drive functions correctly and is seeing the inputs, they are just not sent correctly to the PLC. The drive will not run without the enable relay energized. [/INST] Have been finding a number of status bits oin the 520 series drives not working properly. Was told that some of this should be fixed by the next firmware release, sometime in December. What torques me about this new series is that one of the desirable features is the built in safety-off function in the 525, You would think that this function would also be available in the 523. Why would I want to purchase/use this drive, when it doesn't give me a control/safety advantage. I can get the same functionality with the PF4/PF40's. William \\n </s> |
<s>[INST] Can't add PowerFlex 700 to my project Summary: Module profile not installed. Error 8609-0Hi, I am starting a new RSLogix 5000 (v19) project where I will be using several PowerFlex 700 Vector drives. I have done this before, but I have switched to a new laptop since that time. Now, when I try to add the PowerFlex 700 Vector-400V-E drive to my project, I get an error message saying Failed to create module profile. Module profile not installed. Error 8609-0. When I click on help, I get Failure to launch help., so I'm having a hard time figuring out what to do. If anyone can tell me where I can find instructions on what I need to install and how to install it, I'd really appreciate it. Thanks in advance, Paul [/INST] Try getting the database files from the AB Drives support site: http://www.ab.com/support/abdrives/webupdate/powerflex4class.html# Do you know the firmware of the drive? \\n </s> |
<s>[INST] SMC-3 delta Summary: 230v - 400v hi all, I have a motor: 22 kw - 230v. delta / 400v. star . Can I use a SMC-3 delta soft starter to run the motor with different voltage 230v and 400v, using contactors to make the delta or star configuration? and if I can do it, which is the better switch configuration to have a very soft start? thank you. [/INST] nan \\n </s> |
<s>[INST] coping parameter from a powerflex to be stored on a pc Summary: I need to be able to store drive parameters on my pc networkWe have over 400 differant powerflex drives from 4 to 700s We need to be able to back up the parameters so we can use the copycat function to reinstall the parameters when a drive fails and settings can not be recovered. [/INST] http://ab.rockwellautomation.com/Drives/Software/9303-DriveTools-SP \\n </s> |
<s>[INST] CompactLogix 5380 question. When I type the IP address of the PLC in Chrome a web server appears. Is there a way to see tag values here? [/INST] Unfortunately, no\n </s> |
<s>[INST] How to compare two projects AOI automatically or easy way to understand changes? [/INST] Compare & Merge tool.\n </s> |
<s>[INST] IAB question - multiple drives Is there a way to copy devices in IAB? I configured a PF700 DeviceNet drive in IAB. My application has 25 drives. I really don't want to configure each of them separately. I have not found a way to copy. Does anyone know if this can be done or if there is a work around? Thanks! [/INST] It depends on what you've to copy...:smileytongue: If you want the same catalogue number, then right click on the configured drive and the select Duplicate Device...you will have a copy of the same product on the network; after that you may change the configuration if you need, always right click on it and select Configure, to change for example the Current Rating or other options. The Devicenet properties of the drive( position over the network, address, cables etc.) are insted left to default when copied, so unfortunately you've to select every drive and change as needed. Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] PowerFlex 70 Jog Speed Reference I want to modify the jog speed over HMI via PLC + Ethernet. The system works fine with start, stop, jog … commands, and change speed over HMI, but can’t change jog speed. I went through the manual and this board can't find the answer about this function. Does any one know how to set up jog speed reference to DPI port 5?Thanks. [/INST] If you're not doing so already, you'll be using explicit messaging to accomplish this: 20-COMM-E Manual See Chapter 6 for examples of how to accomplish this for your platform. Your instance number for the Explicit Message write will be 100, the parameter number for the jog speed. \\n </s> |
<s>[INST] Release date (just year) of Allen Bradley 2540AB Hi,It`s very important for me to understand the year of manufacturing of this computer.There is no year on the labels and there is not other labels. Ideas? http://picasaweb.google.bg/116078238941018557966/AlB [/INST] I'm afraid I'm unable to find out anything about this very-old terminal.... :smileysad: The only Portable Terminal very very similar to that one I may remember is the 1784-T47, that is supposed to be subsequent the one you've on your table... For what I can see inside the manual (attached here below this post), it is also manufactured by DataGeneral, around 1990-1991... considering Data General is granted inside FFC rules since 1987 (see HERE) , I guess the item you have, should have been manufactured between 1987 and 1989... Maybe some other old users would be able to be more precise than me.... :smileytongue: - fuzzy logic \\n </s> |
<s>[INST] Load Sharing in DC Powerflex Hello to everyone. I have 3 old DC Drivers running on load sharing (paper machine). These old drivers have Load Sharing function, but these function need to be turned on manualy (relay). The bigger motor are 400 HP for yankee dryer, 300HP for cylinder dryer and 150HP for crescent former. The yankee dryer operates as master to cylinder dryer and load sharing. And cylinder dryer as master to crescent former motor. Cylinder dryer are pressed against yankee dryer and crescent former motor are pressed against the rear roll of cylinder dryer section, and the three motors need to stay ate the same speed (syncronized). Reading the Powerflex DC manual, did not see any mention of Load Sharing function. Searching for any documentation about this funciont, found a Rockwell PDF called Load Sharing Applications for AC Drives. In this paper, they describe three forms of Load Sharing, but one im particular seems to be more similar to what i have here. Called Speed Trim Follower, describe 3 drivers where one are driven from torq referece from master and the other one driven from torque reference from the second one. My doubt is: This principle is applyed to DC Powerflex? Because of no single mention of this function in the manual, i need to ask if someone here have already work with this purpose with DC Powerflex. Best regrards, Rafael Mendonça. [/INST] Hello, one of the most common load sharing techniques is the speed leader/torque follower described previously. That principle is also applicable to the PowerFlex DC drives. There is further detailed information available from Load Sharing between PowerFlex DC Drives where key parameter settings are described. \\n </s> |
<s>[INST] Kinetix 5100, disconnect encoder without fault Hello, I would like to know if it is possible, by ethernet ip, to disable the kinetix 5100 drive, it is to be able to disconnect the encoder (through an ATI tool changer), so that, while it is energized, to be able to make the change, and it does not cause an non-recoverable fault, since the way I know to reset the non-recoverable fault is to power cycle or reset the module, and it takes a long time. Another question, if the tool changer is used constantly, while the drive is energized, can it cause damage? Thanks a lot. [/INST] Alejandro I cannot find any documentation to suggest the encoder is RIUP (Removeable or Insertion while Under Power). This can be interpreted as the encoder connection was not designed/tested nor supported for RIUP. If the Kinetix is power but the CIP axis is disabled (open loop), I believe it is still reading the encoder position and it would register an encoder fault. https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1090640 data-linkindex=0>Kinetix 5100 Servo Drive E011 Encoder Error Troubleshooting \\n </s> |
<s>[INST] Rslogix5000 V17 - Additional Axis Servo faults Axis00.Guard..... What do they mean? In Rslogix5000 V17 there are a whole bunch of additional servo axis faults added. Nobody within Rockwell Europe knows what they mean (I asked esupport and they still owe me an answer).I need to explain to my client what they mean but have no clue where to begin.I think it has something to do with Guardlogix Safety PLC but I'm not sure. Is there any additional info available (manual, link,...) RegardsFV [/INST] These new attributes of the Axis structure are related to a new version of Kinetix Drives... here what I've found in the V17 release notes.... Kinetix6000 Advanced Safety Drive (S1) Support Version 17 of RSLogix 5000 software provides support for the Kinetix6000 SERCOS S1 Advanced Safety based family of drives. The safety status can be directly accessed by the user’s application via two new SERCOS Axis attributes (GuardStatus and GuardFaults) in the Axis_Servo_Drive data type. The configuration of the S1 Drive’s safety parameters is done via an Ethernet WEB based interface and downloaded to the Kinetix6000 drive via this Ethernet connection. I'm sure deekster will add some interesting notes on that.... :smileytongue::smileywink: - fuzzy logic \\n </s> |
<s>[INST] Motor Encoder Connector on U3000 Since my motor encoder do not have pinout of overtravel limit, I leave +LIMIT/-LIMIT pins open on CN2. After I startup the driver, there is an Error Code L flashing which means the drive is in overtravel condition. The manaual indicates that the motion will be halt if +LIMIT/-LIMIT circuit is open. I wonder if I can just jump +LIMIT/-LIMIT with EMPWR_5V (or ECOM?) to skip the detection of overtravel. YC [/INST] If you're using a standard Rotary motor, those pins are not active. If you're using a standard Linear Motor, those pins could be active, but only in case where the encoder has this feature. If you're using a custom Rotary or Linear motor, then the parameter could be enabled in the Motor database configuration. Open the Motor window inside Ultraware and look for Integral Limits in General group, if there is yes then the HW overtravel are enabled. If not, then the overtravel error could come from other ways, like configured Inputs of the drive, or from Programmable Software Overtravel limits. Please check first if the Integral Limits parameter is active, then post again, with possibly more details about your configuration and motor. - fuzzy logic Please remember to Rate the Comments( ) to enhance the reputation of the User who provided help,or close your Topic using the ( ) button over the answer that solved it. Thanks... \\n </s> |
<s>[INST] 1305 how do I program a 1305 to run on power up? I have set this parameter to enable - what else needs to be changed? [/INST] This applies only when there is a maintained input to the start and stop inputs. Refer to User Manual, Chapter 2, Figure 2.7 through Figure 2.10. Hope this helps, - fuzzy logic \\n </s> |
<s>[INST] Kinetix 350 Active Homing Summary: MAH ends in ERR 84 - Drive Digital Input Not AssignedI am setting up a new application using older components: ControlLogix 1756-L63 CPU rev 20.11, 1756-EN2T Ethernet/IP card, RSLogix 5000 v20.01, Kinetix 350 rev 1.55. This is an upgrade of a system we had with a SLC500 and an Ultra 3000 indexing through an HSRV. The motor is directly coupled to a ball screw to move flat sheets of material to a sequence of positions for forming. I have the homing sequence set to actively home to a switch, forward bi-directional, and the switch is a normally closed switch wired into the IOD connector of the Kinetix 350. From the Status screen of the Axis Properties, I can change the state of the Home I/O by waving something metal in front of the proximity switch. When I execute a MAH instruction, the ER bit comes on, and the Axis_Home.ERR parameter changes to 84. The ERR codes for Motion Instructions chart in Motion-RM002 says that it means this: 84 - The CIP drive device digital input is not assigned. - Drive Digital Input Not Assigned. I cannot find any place to specify that the homing switch should be anything other than the IOD input, and it seems like this should be intuitive. On the Ultra drives, I had to specify one of the digital inputs as the homing switch, but this should be automatic, right? What am I missing? [/INST] It should be automatic. You might try flashing the drive (current or newer version) to clear out any corrupt configuration information. You could also delete and re-create the axis in case there's something corrupt in the axis tag. \\n </s> |
<s>[INST] SMC Flex Help Hello Friends, I am using about 30 number of 150-SMC-Flex devices on DeviceNet with 20-COMM-D Series-B module. I have installed the modules and the LEDs PORT/MOD/NET-A are steady Green. I have programmed the 150-SMC-Flex for Soft Start and Soft Stop Parameters. I am trying to give DeviceNet Out Signal to start the motor connected to 150-SMC-Flex. For this Motor to start I have enabled Logic Command bit 1 to ON State. In my PLC program, controller tags: Comm_Rack_DeviceNet:2:O.Data[0] to Comm_Rack_DeviceNet:2:O.Data[4] are mapped for DNET Node Output and Comm_Rack_DeviceNet:2:I.Data[0]to Comm_Rack_DeviceNet:2:I.Data[4] are mapped for DNET Node Input. By this mapping, my plc logic makes bit Comm_Rack_DeviceNet:2:O.Data[0].1 == ON making sure that Comm_Rack_DeviceNet:2:O.Data[0].0 == OFF, Comm_Rack_DeviceNet:2:O.Data[0].8 == OFF, Comm_Rack_DeviceNet:2:O.Data[0].9 == OFF.For some reason the motor is not getting started and the 150-SMC-Flex LEDs remain Steady Green and LCD displays Stopped. Am I missing anything? Please help me to rectify this issue. I appreciate your any help in advance! Best Regards, Pramod [/INST] Try first to follow indications in Aid 45475 and see if it helps... :smileytongue: Just another info missed in your post... which are the indications over the Devicenet Scanner display ? - fuzzy logic \\n </s> |
<s>[INST] ArmorStart 284D Summary: Wiring Diagram I am working with the 284D armorstart and am wondering where to find a internal wiriing diagram for the unit. I specifically I want to know where the control power wires go inside the ArmorStart. The OEM that did the hardware layout did not follow the pin outs for this cable. In the 284D manual it says + - 24 vdc are on pins 1 & 2. The OEM connected it to 5 and 2. thanks [/INST] The OEM was right. Pins 5 and 2 connect to A1 and A2 inside the drive, you need 24VDC between them in order to run the drive. The attached diagram might clear things up. \\n </s> |
<s>[INST] PowerFlex 40 (or 523) Keypad Control with Start at Powerup Hi All, I have a contractor who's customer builds machines that used TB Woods drives. We are converting them over to PowerFlex, but one feature that they used in the TB Woods was a setting that allowed them to have both keypad control with the ability to start at powerup. I've looked through all the parameters in both the 40 and 523 and cannot find anyway of doing this in the PowerFlex drive. Anyone with any suggestions? Cheers. [/INST] See parameter #543 (Start at Powerup) in the PF 523. Unless I am missing something, I think this is what you are looking for. Regards, RM \\n </s> |
<s>[INST] PF400 comms loss problem client has 4 x 250kW PF400 units with 22commD and 22Him3cs door mounted HMI. As soon as I plug the HIMM in, the drive trips on “Comms Loss”. Reset the drive, fault re-appears within a few seconds. Leave HIMM plugged out – no problem then. have flased the 22commD to latest firmware as we had simiular problem with profibus module. this time it is not the solution. Fuzzy lets sea how quick you are on this one [/INST] The HIM is actually powered from the same 5VDC as the 20-Comm-D module and plugging the HIM in has the initial potential to drop the voltage to the point the 20-Comm module loses communication until the HIM fully powers up. Try powering the drive down, install the HIM, and then power the drive back up to see if you again get an error. If you do, you may have a problem with the power regulator for the 5vdc....or a faulty HIM. The HIM should be able to be removed while the drive is in AUTO and not MANUAL mode while the drive is powered up. \\n </s> |
<s>[INST] Welcome to Engage, A Rockwell Automation Community--Rockwell Automation Staff Thank you for your interest in Engage! As a Rockwell employee, you can participate in this modern, customer-facing platform experience in which Rockwell staff, customers, prospects, partners, and others can share knowledge, best practices, ideas, and innovations. As the community grows, so will your opportunities to participate, contribute and share your voice. Some things you can do to get started with the community experience include: Visit the Home page to see what's happening in the community. Upload a profile image and update your profile. See all the communities offered, and join those you are interested in. Join General Discussions to keep informed of general community Q&A, announcements, etc. View the How To series to get up to speed on the features and functionality that Engage offers. Browse discussion posts. Guidelines for Participation For a majority of Rockwell staff, we ask that you start your experience on the community by observing and learning from the community activities. You can do so by: Completing your profile details, including adding a photo/avatar. Joining communities of interest. Scanning email digests for relevant conversations. Viewing trending conversations as they unfold. Viewing members who share their expertise with others. Liking posts that you find useful or thought-provoking. Reviewing/mining community data to create content (knowledgebase articles, white papers, product features and functionality, documentation updates etc.). For Rockwell staff who already have experience engaging with customers, or if you have approval from your manager, you can participate in the community by: Replying to questions within your area of expertise. Recruiting community participants for research, product pilot programs, or user groups. Contact Eileen Foran if you are interested in pursuing this option. Please make sure you consult the FAQ and Terms and Conditions prior to any engagement with community members. If you are interested in participating/engaging in the community, please reach out to Eileen Foran at [email protected]. Thank you! -The Rockwell Automation Community Team [/INST] nan \\n </s> |
<s>[INST] MPL B320P-R Hook and Tune problem. Hallo. I am building some kind of manipulator with this servo motors. And now it's time when I need help. I try to do Test Marker (ok), test feedback (ok), but Test Command cannot be completed , motor start and does one rev. and then is a information Test Command cannot be completed. Missing feedback signal error . I check every thing (connection, wiring, etc.). With auto tune there is the same problem (Missing feedback signal error). It's realy strange, because ther is no E07. To configure servo drive I used instruction from ( http://www.rockwellautomation.it/applications/gs/emea/gsbenl.nsf/files/IAMW01ENv1.0.pdf/$file/IAMW01ENv1.0.pdf ). But there is a another servo motor an maybe here is a problem. When I try to use Motion direct commands MSO execute ok but MAJ give me a foult E19. I have no more ideas. Please halp me. P.S. Realy sorry for my English. :smileyhappy: Best regards. [/INST] I solved the problem. Power motor cables ware converted :]. What a stupid mistake :-/ \\n </s> |
<s>[INST] Where are the CAM points stored? In a system I've got a virtual axis and a physical axis. Using a MAPC Instruction I control the physical axis depending on the position of the virtual one with the CAM editor, but.... where are those CAM points stored? I've looked inside all the tags created and couldn't find them... any help, please¿ [/INST] The CAM_PROFILE data type is an array of coefficients representing a calculated cam profile that can be used as input to a time cam or position cam instruction. The only element available to you is Status. This is different from the CAM data type... The Cam data type consists of slave and master point pairs as well as an interpolation type. Since there is no association with a specific axis position or time, the point values are unit-less. The interpolation type can be specified for each segment as either linear or cubic. See also Aid 62304 ... - fuzzy logic \\n </s> |
<s>[INST] PowerFlex 40 Control from Terminals or 22-COMM-E Summary: A051[6] , P36 ,P38We need a Powerflex 40 to Remote start/reference from 22-Comm-e . Local start/reference from terminals If AO51 =6 and input hi does 22-comm-e control VFD? If A051=6 and input lo does P36 and p38 control VFD? Thanks [/INST] Yes, it will work as needed. There is a similar example inside Aid 47161. - fuzzy logic In order to enhance Forum's contributors reputation, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] Kinetix 5700 and STO I have a dual inverter that I want to use STO via ethernet/ip. Can I use a selector switch to an input to a safety PLC and turn off the STO and still be considered safe? [/INST] Hello Fleener You can use a safety selector and connect it to a safety input module that is linked to your safety controller. Then in the controller safety task you can manage your STO output for the Kinetix drive. All this is possible. But you have to respect your safety assessment and do the safety check list (available in this manual for each function https://literature.rockwellautomation.com/idc/groups/literature/documents/rm/2198-rm001_-en-p.pdf ) Just to make sure that we are on the same line... when you mean turn Off the STO , you mean put the drive in safe torque off state (no motion possible) Again, all will depend on the safety level you need and your safety assessment regards \\n </s> |
<s>[INST] Could you explain to me what of fuction is about registration swith? Summary: I want to know why we need registration swith? Could you pls expalin to me ? thank you very much [/INST] I mean I don't know what is registration switch for? anybody can help expalain to me? Thanks \\n </s> |
<s>[INST] ControlFLASH Plus V1.00.00 is available for download (free) Summary: The next generation of flashing firmware devices is availableAll, ControlFLASH Plus V1.00.00 has been released for download from PCDC. This new flashing firmware tool is free. It allows better firmware lifecycle management and improved productivity by allowing you to create and execute multiple device firmware operations. It requires FactoryTalk Linx V6.00.00, which is also free. ControlFLASH Plus Quick Start Guide ControlFLASH Plus V1.00.00 free download Regards, Fabio [/INST] nan \\n </s> |
<s>[INST] PowerFlex 750 as CIP drives Summary: Using Powerflex 750 drives as CIP Integrated motion drives Has anyone had any experience using a 755 drive, 20-750-UFB-1 card and a SSI encoder? I cannot get the Logix PLC to configure the drive in a usable way. [/INST] I have! I have! Getting the settings right required several calls to Tech Support. We had some weirdness occur with getting the drive to configure, I think having to do with one person trying to configure the drive on the network while another was upgrading the firmware on a bunch of Armorblock IO modules. Bad combination; the drive could not handle the RS-WHO calls (40,000 per second, or some such nonsense), and would CIP-SYNC fault. Rockwell has since released a firmware upgrade to fix that. There was much confusion too because Rockwell documentation talks about Channel A and B in the Logix5000 IO tree, but X & Y for the UFB card. It DOES work, but you'll have to give more details for me to be of useful help. \\n </s> |
<s>[INST] 1336 plus and 1336 Plus 2 serial fault Hi, I have got a couple of drives (1336 plus and 1336 Plus 2) I want to connect (via scanport - 1203-module) to a logix controller. However, some of them give F10-serial fault when the scanport cable is unplugged. This network is only for reading parameters (logging). I've changed parameter 92 (logic mask) so the scanport adapter (2) shouldn't be able to fault, but still it does. Any thoughts? Thanks [/INST] nan \\n </s> |
<s>[INST] PowerFlex 4(x) Series Remote HIM I'm trying to pick a drive and I want a remote HIM, a process controller sending a 0-10VDC speed reference and an AUTO-MANUAL selctor switch.(Too bad there's no auto-tuning on the PF4 series drives or I would use the internal PID - but that's another story...)The remote HIM need to be the NEMA 4X 22-HIM-C2S. With the selector switch in AUTO, the drive should respond to the speed reference from the process controller.WIth the selector switch In MANUAL the operator uses the remote HIM to set the speed.The remote HIM is always the start and stop source. What powerflex series drive, if any, allows me to do this?Is the remote HIM equivalent to the integral HIM if the drive is in LOCAL mode? MANUAL mode?Or is the remote HIM considered COMMUNICATIONS when setting up the drives digital input functions? Please don't tell me I need to use a PF7x series. My customer isn't getting any TARP funds.Thanks [/INST] In the user manual, page 3-14, you can set up the digital input to be local control for the HIM; parameter A051 set to 5. For AUTO on digital input #2, set parameter A052 to 13 for 0-10V control. Hope this points you in the right direction. \\n </s> |
<s>[INST] Error E64 (Kinetix 6000 2094-xxxx-x) Regarding E64 (Kinetix 6000 2094-xxxx-x), it happened in 5 axis of my production line (about 85 axis) Actually we see this issue every week. What we did: 1,For the 1st action, we used tie wrap to fasten feedback cable connector at motor end. This allowed us to run for 1 hr then stopped due to E64 again.2,For the 2nd action, we replace the feedback cable. This allowed us to run for other 2 hr, then stopped due to E64 again.3.For the 3rd. action, we replace the Kinetix This allowed us to run for other 2 hr, then stopped due to E64 again.4.For the 4th. Action we find the feedback low profile connector (Kinetix feed back cable connector) that we are having across the line The clam was holding the feed back cable isolation rubber not the exposed braided shield in some of the connector. We plan to turn the low profile connector clam over to hold all the servo motor feed back cable secure.5.for the 5th. Action Kinetix 6000 temperature too high.• Check for clogged vents or defective fan• Ensure cooling is not restricted by insufficient spare around the unit • Verify ambient temperature is not too high We try to cool down the servo motor 6.for The 6th. action, we replaced motor. This issue does not happen again until now.Type of defected motor :MPL-B540K-MJ24AAMPL-B540K-MJ22AA 1326AB-B720E-M2K7L According to Trouble shooting GuideE64 MotorFeedbackNoise (Mtr Fdbk Noise) is Noise on motor feedback cablePotential Cause is: Recommended grounding, per installation instructions, has not been followed. Possible Resolution is: Verify grounding. Route feedback cable away from noise Sources. Refer to System Design for Control of Electrical Noise Reference Manual(publication GMC-RM001).This issue stop my production line:544 min / 85 stop for MPL-B540K-MJ24AA 527 min / 24 stop for MPL-B540K-MJ24AA The input of Rockwell Esupport is: There are no known issues about these motors causing E64, feedback noise. Usually this type of fault is caused by the feedback cable or poor bonding for noise prevention. I am sure that these replacement motors are good, but if the problem comes back please inspect and clean the connector on the motor end of the feedback cable. I would also like to send to you a document on how to assemble the low profile feedback connector to verify that the shield is properly bonded to the cable clamp. Please advise. [/INST] According to your point #4, you show that you do not have the shielding properly bonded to the feedback connector. This is the path to ground for any noise that may be on the signal. Also make sure your motor power cable has the exposed shield under the clamp as well. Making sure that all components are grounded properly can help resolve this issue. Have tech support send you the feedback wiring recommendation that they mentioned. Are there AC line filters installed on the incoming line?Are there MOV's installed on your AC contactors?Are there MOV's/diodes installed on your DC contactors? All of these items can effect the noise on a signal line. \\n </s> |
<s>[INST] 8720MC F1 fuse blown Summary: 8720MC Regen Power supply keeps blowing F1 fuseWhat do I need to look at for possible causes for the F1 fuse blowing? Is it something inside the Power Supply, or wiring on the outside? We have a master unit and a slave unit and it blows both of them. [/INST] nan \\n </s> |
<s>[INST] Ultra 5000 Drive C Programs Failing? We had an issue last night with the Ultra5000 drive failing on one of our Hem presses. The hempress was stuck in the lower position (Manual and Auto). Cycled power to the drive several times but couldn't get devicenet communication. So we eventually swapped the drive. As part of the swapping procedure we reloaded the C program for the Ultra 5000. After swapping the drive, the press was raising extremely slow and stalling after hem. We had to reload the C program a second time in order to get it working properly. This is the second time we have had issues with the Ultra 5000 C program. We think it might be getting stuck in a subroutine. My question is, does anyone else have issues with the C program, and are there any patches available to address this? Thanks Eric [/INST] If you have experience programming in C, you should check to see if the program has appropriate check statements. Typically people will use a while loop to perform some of their code. Like this: while (!StopRequested()) This type of statement can help break out of a routine that is stuck. You can also use some of the available variable tables to write diagnostic info. For example, when the program tries to run a certain piece of code, write a number to the variable table that will indicate it is running that code. This might help you troubleshoot the code. I've written many programs for the 5k and it's a really good drive, but it can be difficult to troubleshoot. \\n </s> |
<s>[INST] Variable frequency drive energy saving calculator Summary: Variable frequency drive energy saving calculatorcan anyone please provide me the excel sheet in which I can calculate the energy saved by adopting the variable frequency drive for the Blower in sewage treatment plant for 120HP motor. [/INST] Contact your Rockwell distributor - this is something that sales group should be jumping all over in order to sell you VFDs. \\n </s> |
<s>[INST] command fault on 1746-hstp1 module Keep getting this fault when tring to jog the axis. slc503, 2 1746-hstp1 moduleconnected to md808-128 controller. When through the module book and set it all up, but get a command fault when tring to move axis. Let me know what other info you need to try to help meplease. Thanks, Wayne [/INST] Wayne, I guess you have the ERR led on and bit 12 on in the Input Word 0.That means something in the output command words is not correct.Double check what is indicate in attached screenshot. Take also a look to the suggestion in Aid 43983. Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] Looking for a name of a part Summary: Trying to figure a name and a function of a part in clients el.cabinetHello! I am trying to figure out what does this component do (in the picture - on the left, gray, named N30.1) and what is its actual name? Sorry for the picture quality, it is the best one I got. [/INST] nan \\n </s> |
<s>[INST] Allen Bradley Power Flex 7000 Password Protection Problem Dear All, I'm using Allen Bradley Power Flex 7000 45KW Inverter in my Industry and facing an issue of Password. My AC Drive is not allow to enter in any parameters list due to password. We did not know the password. Kindly help me how can I access to my parameters and how can I reset the drive's Password. Thank you. Regards, Jalil [/INST] Hi, PF7000 MV Drive with 45KW motor?? Typo?? It would be better to upload the parameter set for RA team to resove for you. \\n </s> |
<s>[INST] 2711P-T15C4D9 Windows CE 6.0 with extended features Hi, I try to understand the difference of the PV 2711P-T15C4D8 and 2711P-T15C4D9. In the discription the ending 9 is marked as Windows CE 6.0 with extended features. Does anyone knows what these extended features are? There is nothing described in the technical manual. Does maybe someone has the knowledge of these old PV and knows what those extendef features are? Thank you! [/INST] Hi Lutz. Thanks for your question. The Engage community is not an internal Q&A or support portal, however. You will need to ask your question in one of the internal support areas that already exist. Thank you. I am closing this thread. Eileen \\n </s> |
<s>[INST] 200hp 1336 Plus - Why am I getting an F12 Overcurrent fault at power up? I am getting an F12 overcurrent fault as soon as I power my drive up. The motor has megged good and I have even taken the motor leads off of the drive. Ohm value between each VFD output phase is around 2.0 meg.Things I have checked:- checked all IGBT's according to manual and they checked good.- checked input voltage scrs and good- checked pre-charge board fuses and good- replaced gate driver board- replaced main control board- replaced HIM- Loaded a different program into drive and still get same fault. We have just replaced this drive about a month before and it ran fine after we replaced it. I sat for about a month and when we tried to start it up the f12 fault is displayed. [/INST] You have been very thorough in your diagnostics, but there is one thing I dont see in that list. An overcurrent in a drive that size would tell me that one or both of the LEM modules on the drive have malfunctioned, or have been wiring incorrectly. They are on the output of the drive, and sense the output current. Can you check them for a shorted or open condition, and make sure that they are wired in correctly. They would be the only thing that would tell the drive it is outputting too much current. \\n </s> |
<s>[INST] Problem with touch screen calibration 2711P-T15C22D9P. First step: Terminal Settings, then choose Input Devices>touch screen>Calibration. Second Step: Carefully press and briefly hold stylus on the center of the target. Repeat as the target moves around the screen. The problem is that i don't have a message that calibration is complete. All the time the target moves around the screen. When the calibration is complete, a message appears to indicate the measurement of new calibration settings. Right now we use USB mouse to navigate through the interface. [/INST] It might be a hardware issue or a firmware issue. To be sure, you can try to flash the panel with the desired version of firmware. If problem reproduces after that, there might be several touch cells damaged. If not, the new firmware image has corrected a corrupted dll library.\n </s> |
<s>[INST] 843ES CIP-Safety configuration issue Hi All, I'm new to Rockwell products, hope this is the right forum to post the issue. With one of my customers, we're struggling to configure an 843ES encoder, here are the details. IP/DHCP configuration Our network configuration does not allow the default 192.168.1.xxx subnet of the 843ES encoder, therefore we have to revert to DHCP configuration. We tried the BOOTP/DHCP EtherNet/IP Commissioning Tool and the EtherNet/IP™ Address Commissioning Tool but it was not possible to use neither of those since they conflict with Windows svchost process on port 67. So, the only way we could enforce DHCP addressing was to set the rotary switches to 999. In this case, the encoder correctly acquired the IP address from our router. Is this the correct way to enable DHCP? Encoder configuration With DHCP enabled, the Module Status Indicator LED on the encoder flashes green/red, that is Device not configured. Chapter 5 Configure the Encoder with Studio 5000 Environment of 843-um001_-en-p.pdf states that The encoder does not work until it has been configured with at least the default configuration.. This chapter describes the encoder configuration using Studio 5000 suite. Two questions: Studio 5000 has many possible variants and configuration, what is the minimal required for configuring the 843ES? In our project we're not using a Rocwkell controller; Is it possible to configure and run the 843ES without Studio 5000? Thank you in advance for your attention, Ezio [/INST] Hello Ezio to answer your 1st question, yes ! setting BOOTP/DHCP you must Set the rotary dials to 999, and use RSlinx Classic. Refere to the Capter 4 of the 843ES User Manual. Now regarding the point that you are not using a Rockwell controller and environment, that is a problem. This device use Add On Profile in Studio 5000 to be configured and to sync with the CIP Safety protocol and Controller. So I'm almost (99%) sure that what you are trying to achieve is not possible in the actual situation (But I will double check) What is your application needs and objectives regarding this encoder? Does your environment support CIP Safety protocol? regards \\n </s> |
<s>[INST] Re: Cut to length Flying Shear Hi,A couple of years ago,I made a very similar application, only using Ultra 5000 and ANSI C programming, and also instead of CAM , I used gearAfter comparing the number of pulses provided by the Aux encoder with the LenghtCount variable, it geared the motor to the encoder, after the motor position was greater or equal than the Distance variable, it disabled the gear and returned the motor to its start positioncheck the attached file, for the calculation I used to set the the variables Hope it helps Gilberto Aranha [/INST] Note for Moderators: this is a reply supposed to be posted to the following topic: http://forums.rockwellautomation.com/t5/forums/forumtopicpage/board-id/Motion/thread-id/818 - fuzzy logic \\n </s> |
<s>[INST] FTview10.0 SE. On a button I can Run command with the parameter Language en-US (or some other language) - and then the language is activated. How do I run this command from VBA? [/INST] ou may use the following VBA script: ExecuteCommand Language en-US\n </s> |
<s>[INST] Active homing on torque level How does the active homing on torque level work?The typically set for the torque level in the homing tab of the axis properties does not match the torque level the axis is using to do the homing sequence. [/INST] Did you see the Application Manual at this LINK ? It could be useful to understand how it works.... also, it may be useful if you can give some more details about your sequence and your doubts... :smileywink: - fuzzy logic \\n </s> |
<s>[INST] 20 COMM D FW VERSION Summary: ERRORS WHEN CHANGING 20 COMM D MODULE WITH DIFFERENT FIRMWARE [/INST] I'm getting some faults related to PORT 5 adapter on a PF70 with device net adapter 20 COMM D, so after troubleshooting it I decided to change 20 COMM D comms adapter, the one that is installed is a 20 COMM D FW VER 1.007 Ser B and I have a new one FW VER 2.001 Ser B, after installing the new one and downloading the config to it a new fault rise and I wasn't able to clear it, the fault was related to config parameters. When I downloaded the config to this new adapter the HIM asked me for confirmation telling that this was a different version to that I hited the enter button accepting the warning. Then after a cuple os seconds of resetting everything the fault appeared. I put again the old module with no faults. Do I need to have the same FW version to replace the 20 COMM D module? Any help will be must welcome. \\n </s> |
<s>[INST] 825-PD protection Relay I need some explation on the function of the terminals Y-(common),and Y12 (IN1) in the 825-PD protection relay. Do i need to use this terminal for a DOL connection?. [/INST] lukman, the function you may assign to that input, and to the other inputs also, are shown in the 825-PD User Manual, starting at page 5-34. Attached a screenshot of the table... Hope that helps... - fuzzy logic \\n </s> |
<s>[INST] Axis Properties - Backlash Reversal Offset Enter the value of the reversal offset for the load in terms of user defined position units. Compensation Window Enter the value for the compensation window in terms of user position units. What Does 'Compensation Window' mean? [/INST] See the Motion System Tuning document https://literature.rockwellautomation.com/idc/groups/literature/documents/at/motion-at005_-en-p.pdf \\n </s> |
<s>[INST] PowerFlex400 not starting from Logic(Studio 5000 V24.0) Hello Everyone, Hope your good. This is Waseem, and facing problem with PowerFlex400. I'm controlling it over Ethernet(22-Comm-E) and Studio 5000 V24.0, I have created logic to control the VFD, Mapping also done with it in logic. The main problem is coming when im giving a start command from logic, the VFD is not starting(Drive Active Feedback not coming). I thought Communication is happening, so i pinged the IP(Working Fine), Checked in IO tree (Status Ok), In VFD property(Left Bottom Corner Showing Running). I faulted the VFD and did clear fault from logic, its working(Fault has been cleared from Logic Command). If i start it Manually Active Feedback getting in logic. Only the problem is its not taking start command from logic. My speed ref option is Com port. Please help me to come out from problem.. Thanks in advance. Regards, Waseem Akhtar [/INST] What is Parameter 36 (start source) set to? If you want to run from the 22-COMM-E, then I believe you must set P36 to 5 - COMM PORT. \\n </s> |
<s>[INST] Configuring 527 for fan motor application I am currently adding a 527 drive to a L71S PLC via ethernet. I am trying to configure the motion group and I need to know what settings I will need in setting up the axis. [/INST] If you already have the drive configured in the IO tree, you should also have an axis associated with it. In the motion group folder, create the motion group using right click / create. Name is unimportant. Move the axis from the ungrouped folder to your new motion group. Doubleclick it to open its property page. You've given us little information to go on, so I'm going to make wild assumptions on what you have - like, no feedback. General tab: Axis configuration - pick frequency control Motor tab: Data source - nameplate data sheet motor type - rotary induction Fill out the motor parameters. Do make sure you get pole count correct - Poles = 120 x base frequency / synchronous speed Analyser tab: Run this after you have wired, powered, and communicating. Dynamic test by preference, but static test will work. Hookup test tab: Use that to verify correct rotation Frequency control tab: Go with defaults until you know what you want to adjust. Drive parameters tab: Pick what parameters you want to have access to read and write. You cannot have them all. Pick the monitoring ones that make sense for your application to display on an HMI. \\n </s> |
<s>[INST] Ultra 3000 Indexing Drive I am using an Ultra 3000 in a simple positioning application. The drive is set up for Indexing and being commanded to move from a PLC using the Index control inputs. The axis is also being 'homed' using the Homing control inputs. The problem I am having is making the drive fault out during current overload. The homing target in this application is a removable piece (not a good idea IMO) but this allows for the homing routine to hunt for the sensor and never find it. The axis is moving slowly during homing and eventually runs into a hard stop. But the axis keeps trying and doesn't fault out. I have set the current limits to a safe low limit but the drive just rolls the current back but doesn't fault out in any reasonable time. I have currently set a timeout in my PLC to turn off the Drive Enable line after so much time. I was hoping that the drive would stop on its own instead. Any ideas? [/INST] Under faults there is a User Current Fault that will cause the drive to Fault with an E17 when it is exceeded. \\n </s> |
<s>[INST] Error code 22 in CAT 160 inverter Hi every body. I have CAT 160 BA01NSF1P1 inverter from AB. I have error code 07 22 . I downloaded manual,but there isn't this error code information.what should I do? [/INST] Fault Code 22 Indication: Drive Reset Description: Stop input not present. Corrective Action: Check stop input at TB3 terminal 8. Check manual: 160-um003_-en-p.pdf Bye \\n </s> |
<s>[INST] COMMUNICATION PROBLEM WITH A 1394-SJT05-T-RL GMC SERVO DRIVE I HAVE A COMMUNICATION PROBLEM WITH A 1394-SJT05-T-RL GMC SERVO DRIVE. I CAN´T GO ONLINE WITH GML COMMANDER. I CHECK RS-232 INTERFACE CONNECTIONS, PORT CONFIGURATION IN MY PC AND THE SERIAL PORT CONFIGURATION SWITCH BUT I CAN´T GO ONLINE. SERIAL PORT CONFIGURATION SWITCH (PORT J4) 1-RIGHT 2-LEFT 3-RIGHT 4-LEFT 5-LEFT 6-RIGHT PORT CONFIGURATION PC BITS PER SECOND-115200 DATA BITS- 8 PARITY- SPACE STOP BITS- 1 FLOW CONTROL-XON XOFF [/INST] The unit has 2 comm ports as I remember, Have you tried both ports, and have tried with a straight and a cross cable? Has your PC a real serial port, or are you using a USB to serial converter? Not all serial converters work on these communication. Jack \\n </s> |
<s>[INST] Kinetix 300 Vertical Brake Summary: Need information on wiring of control and timing for vertical application with holding brake We have a vertical application. The servo motor has a holding brake. An emergency turn off requires the following sequence (this is easy to achieve in other servos) 1. Press emergency stop 2. Signal (which one ?) to the Kinetix 300 is dropped (logic power and 3 phase is kept) 3. Kinetix brings any motion to a halt but holding torque is still on. 4. The Kinetix brake release output turns off to set the holding brake, holding power is maintained 5. A set time later (to allow the holding brake to fully engage) the holding power is released and the drive is disabled. External safety relay timed contacts will - after this action - remove power from the holding brake circuit and turn off the safety inputs to the Kinetix. (This wiring is already in place) We are confused as to the wiring/settings to achieve the numbered steps. This has been fairly easy and actually spelled out in manuals on other servo systems. [/INST] The place to start is here: http://literature.rockwellautomation.com/idc/groups/literature/documents/um/2097-um001_-en-p.pdf Page 93 shows the two parameters you would need to set (651 and 652) for time delays regarding the brake output of the K300 drive. You will need to coordinate the two parameters with your external safety relay timed contacts to make this work. It's not a control scheme I would be very happy with - the K300 is a very simplistic servo. I would take complete control of the brake via external logic (sounds like you already have it), and not do any brake control within the K300 at all. \\n </s> |
<s>[INST] Loadcell feedback to a Kinetix 5700 drive Hello all, Keeping it simple, I am running a servo to a force. I have a loadcell to an Analog input card that feeds MCD instruction to control a MAJ velocity. This works, but I am thinking that a could wire the loadcell directly to the secondary feedback of the K5700 and just use a MAM with the loadcell target? Dose anyone do this. This there any information to help me. My (current) loadcell provides -10/+10 3 wire. [/INST] Morley, Here is a discussion about force and torque. https://engage.rockwellautomation.com/discussion/constant-force-torque-application \\n </s> |
<s>[INST] FTview SE 10.0: How to display (and edit) a different language than the default? I have two languages in my installation. I design in English - but as I sometimes just copy a text box and change the text - then I also need to change the second language. How do I switch the display language in my display editor? [/INST] If you are using FTView v10.0, there is a feature enabling you to change the application language to modify/edit the text strings on the graphic display. Click the 'Change Application Language' icon on the toolbar, without having to close the application and then re-open it with another language.\n </s> |
<s>[INST] powerFlex4 f005 error I am using a powerflex4 inverter with 0.75 kw rating 1-phase input and there is an error f005 (over voltage error) is appearing at power up and it is disappear after many tries of clearing the fault and restart it . and when I shut the power off for a time and want to run it again this fault appear again .note that : I am using it's appropriate EMC filter and input line voltage not exceeds it's recommended value (265 v) and when I measured the voltage at dc terminal it is around 308 v (normal value ) so I am kindly asking about guide to know what is the problem and what is solution ..... thanks [/INST] If this is happening at power-on, your line-in voltage is too high. It may be below the 265V max, but it needs to be closer to the nominal 240V recommended. Also, if you're cycling power, you need to give the drive bus capacitors time to discharge before applying power again. If you're cycling off-on more frequently than one minute, the bus voltage doesn't decay low enough and you end up with an F5 fault on power-up. \\n </s> |
<s>[INST] Servo motor control Whether the servo motor can be directly controlled by 5069-ob8f / 5069-ob8 DC IO module output. If not, what method should be used to control the servo motor? [/INST] Hello Gary. We have a Servo Control solution in our Kinetix portfolio that can be controlled directly with I/O interface Look at our Kinetix 5100 . All depend of course on the application requirements, function, Speed, Power, Positionement...etc . But like any sizing for a motion control application, if you have no experience (or limited) I strongly recommend you to contact your local Rockwell Automation representative or distributor to assist you in this process, we have specialists that can help you to do the selection and we can also assist you in the implementation. I hope this help you :) Best regards Vincent \\n </s> |
<s>[INST] 1747-UIC driver Summary: 1747-UIC dont work in my PC Hi My PC crashed last week, now I'm installing everything again, I tryed the 1747-UIC and had a FTDI FT8U2XX device driver under Universal serial bus controllers but nothing shows up on Com & LTP ports, first I installed from RDS500 cd and then I tryed the RA downloaded file, does anybody know how to fix this I have RFSLinx lite 2.57 RS500 RS500 8.40 CPR9 [/INST] Have you changed your operating system? Which operating system is it? 32 or 64 bit? Try installing the drivers and following the directions from the following technote: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/115561 Thanks! \\n </s> |
<s>[INST] Email Address / Subject of Engage outbound Mails Hi, it would be great to have a more descriptive Email Address for Engage Outbound Mails (e.g. the Daily Consolidated Digest), so that it is easier to define a automatic filter for moving the Mail to a folder. The current address is [email protected] and the Subject Line does not refer at all to Engage, so it is hard to define a reliable filter. Viele Grüße, Daniel [/INST] Hi Daniel. Good suggestion! I'm looking into whether we can get Engage in the subject line. Thank you! Eileen \\n </s> |
<s>[INST] Rockwell Drives Firmware now secure Summary: Rockwell now uses SecureFlash for drive firmwareIf you purchase a drive new now, it will come with firmware that is digitally signed and thus secure. If you wish to replace an existing drive with a new one, you cannot simply downgrade the firmware by flashing with the appropriate firmware for your application. You need digitally signed firmware. In fact, you may have to upgrade before downgrading, according to the release notes of Firmware 10 and 11 for PF755s. I feel very strongly that Rockwell should have announced this to their drives customers several months before rolling out this new feature or behavior. Rockwell has their reasons (according to tech support, it is because of new federal export laws prohibiting drives from having output frequencies above 600 hz). Fine - there's a reason and a need to do this. Don't you agree Rockwell still needs to tell us in advance? [/INST] Hi TJ, I'm a drives distributor specialist selling Rockwell VFDs and this is the first I'm hearing of this. Thank you for posting. \\n </s> |
<s>[INST] When drive is told to decel it stops Summary: when we tell the drive to decel it coast to a stop.I have a power flex 753 drive on a 250hp motor. The machine has been in service for 10 years, but we had a drive go bad a few weeks ago. We installed the new drive loaded the original parameter's back in, and it went back into production. We have a problem now that when you tell the drive to decel it goes to stopped. This started yesterday in the middle of production. The drive has a 110v adapter card that we send an analog input to for a speed reference. The drive shows that it is still enabled, and it is still being told to run. I am also trending the command speed with drive observer, and it is not dropping out either. I even put latch bits in the PLC to make sure that the drive commands are not blinking. The other thing I noticed is that the last stop source, and the last start source bot say pwr removed. I have looked all over for more clarification on what this means, but cant seem to find any. We are going to change the adapter card this morning, and see if that makes a difference. I am also going to hook a process meter up to the drive, and send it an analog signal just to verify the wiring. I am able to start the drive and ramp it up I can start and 30hz and ramp it up incrementally no problem. The problem only occurs when trying to slow it down. I have a breaking resistor installed as well, but the dc buss doesn't even go up. If we want to start the drive back up, then we have to cut off the start signal and turn it back on again. There is no faults or warnings on the drive, and it still shows enabled. I have included a screen shots for reference as well. I guess my question is has anyone ever had a drive do this? I have looked in knowledge base, and forums but cant seem to find anything. [/INST] Can you upload the drive DNO file for us to look at? \\n </s> |
<s>[INST] Rotary to Linear Motion any Ideas? [/INST] Try a virtual Axis as the position on the linear axis (Axis 1) Axis 2 is the Angular Position of the CAM Create a MAPC to copy the effect of the physical CAM (Look up COS rule to calculate values) Tie Axis 2 to Axis 1 via the MAPC Control the motion via Axis 1 Problems that you need to think aboutHoming When to engage the MAPC Overrotation of the Angular Position End of travel limits \\n </s> |
<s>[INST] Ultra 3000 Won't communicate I have a set of Ultra3000i drives that will no longer communicate with ultraware. I have tried with my other drives to verify that the problem is not with ultraware settings. Any help would be greatly apprecieated. [/INST] Do you mean you are able to connect to other Ultra drives with same PC and same cable ? Did you get a comm error? Which ? Anyway, try to take a look to the following technotes.... Aid 47739 - Aid 49520 - Aid 42830 Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] Kinetix 5300 Communication I have two Kinetix 5300 drives in a new machine. Connecting to a 1769-L36ERM compactlogix processor version 33. I set the software up as we have in the past for the 350 drives. Both drives have configured IP addresses in the in the range of the processor. On startup the drives show up in my controller organizer as having no problems. They never come off the 00 state on the drives. If I unplug the Ethernet cable to the drives and re-insert. The drives go through their startup sequence and reach 04 state. I can start and run the drives without errors. I have replaced the 100 foot Ethernet cable out to the drives. I have replaced that cable also with a Cat 5e cable that checks out with our blackbox cable tester. I have moved the connection from the system Ethernet switch directly to a port on the processor. I have pulled the 24V supply to the drives until the system starts up, and applied power. The only thing that makes the drives come online is pulling the Ethernet cable and re-inserting. I have two powerflex 523's on the line that have no problem attaching at startup. What am I missing? [/INST] Don't have a good answer as to why you're seeing this phenomenon, but you could try programatically disabling the drives in the IO tree and then re-enabling them. It would do the same thing as unplugging the cable. It sounds like there is some sort of boot process foot race and the 5300s consistently fail the race. Programatically disabling / reenabling fixes the problem (though it doesn't solve it). The snippet below shows how to do this: You use value 4 to disable, value 0 to enable. I made constant tags to help others read the logic. Instance name is the name of the drive in the IO tree (not the axis name in the motion group). We use this sort of logic to allow the motion group to initialize on boot when a drive is missing / failed. All drives must be in place and communicating with the processor at time of PLC boot; if one is missing the motion group never initializes. The logic above allows an a drive to be programatically disabled which then permits the motion group to initialize and run. \\n </s> |
<s>[INST] Safety Instruction Safety L6XS for SafeOff (dual channel Output - single channel feedback input) Hello, I'm looking for a safety instruction in my L62S that can handle the safe-off functionality as follows:- Safe-Off switching done by 2 safety outputs (dual channel) to 2 relays on same SafeOff-board of K6000-drive- Feedback of Safe-Off status: 2 feedback contacts on SafeOff-board of K6000 drive are wired in series and put finally to 1 safety input. I thing about using the ROUT-instruction (redundant output instruction), that requires 2 feedback contacts together with 2 outputs.The 2 outputs are no problem. But for the 2 feedback contacts (inputs) in the ROUT-instruction, I thought about using for Feedback1- and Feedback2-field the same safety Input. So far so good.Then I read the help function of the Rout instruction again and saw that it will do Pulse-checking on both inputsignals (feedback1 and feedback2-inputs).If it makes pulse checking according SIL3/CAT4 on both inputs what will the instruction do when there are 2times the same input configured? Will it go in error?Can I have a similar safety instruction with no Pulse testing on the 2 feedback input signals, or a similar safety instruction for dual channel safety output with single channel feedback input? Regards,Frank V. [/INST] Hi Frank, Pulse checking is done by configuring the safety in- and outputs, it has nothing to do with the ROUT function.If the input is configured for testpulse and that input does not get the correct testpulse signal, it will fail. So your solution is to configure only one feedback signal for testpulse. Only one testpuls output goes to your feedback input. In your ROUT block, use the input for both feedbacks and you are ready. p.s.Testpuls is mainly used for more diagnosis. Your application will also work without testpuls. Success,Cya \\n </s> |
<s>[INST] power cable high flex for the MPL-B880D-MJ22AA I have found the standard flex power cable for the MPL-B880D-MJ22AA servo motor. What is the part number to order high flex instaed of non-flex power cable? Standard power cable part number 2090-XXNPMP8S03. THANK-YOU [/INST] The part number you need is : 2090-XXTPMP-8S03 You may find this information on the Motion Selection Guide, page 396. Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] STEP Files Does RA provide .stp files of their components. I would like to use 4983-DC120-03.If I had the solid model, it would be very easy to incorporate the part into my (PRO-E) design. The dwg, dxf, & pdf options under the drawings tab don't help me. [/INST] As far as I know, the .stp files are only available for Motors... anyway, you may want to try to ask RAISE support team and see if they may help... Technote 40706 contains phone and e-mail address. Hope this helps, - fuzzy logic \\n </s> |
<s>[INST] Problem with SERCOS interface on Ultra3000 Drive. We have a control system that consists of 4 Ultra3000's communicating with an Allen Bradley PLC via a SERCOS fiber optic link. Ever since the initial startup of this unit we have had intermittent communication errors. Well, today they became much less intermittent and more permanent, we could only keep communication established for about 10 minutes in every hour. Each one of these drives are connected to the SERCOS in series to each other. It was obvious therefore to find out where the communication ended. I have no way to test the quality of or the data integrity of a fiber optic link, I can only use my eyesight to verify that there is light emitting from the SERCOS link at whatever point that I remove a cable. It was obvious using this method that the signal was entering a certain drive in the string, and in fact was being acted upon since the communication light was green, but it was not exiting this drive and entering the next one in the string. The red light was not emitting from the output of this card, so that eliminates the next fiber optic cable as being the problem. Also, if I remove the cable from the input of the bad drive and install it in the input of the next drive in the string, the rest of the drives from that point on establish communication again. So, obviously, the SERCOS interface card is defective in that drive. The question is, What has been the resolution of this problem? If you ran into this, was it just as simple as maybe the card is not fully seated into the connector in the drive? Remember, this problem is intermittent, it comes then it goes. I actually observed the output starting to work, then not work visually several times while the output cable was removed. Or does anyone know what specific component on the board may be defective? I have not disassembled the drive yet to see what components are there, but assume there must be an optocoupler I.C. of some sort that may be getting spotty? Or possibly something as simple as a poor solder joint? The simple answer is obviously to replace the card, but the customer is coming in Monday afternoon to observe the unit we are using this control system on run, so it might be quicker to source the individual component locally. Thank you for your help. [/INST] Is the drive with the problem still under warranty? I have never messed with the internal hardware of the SERCOS interface on the Ultra 3K but I have had this problem before. I just had the drive replaced. By the time you mess around with troubleshooting at the component level, you could just get a new drive and be done with it. I don't know what the urgency for this application is, but the drives aren't that expensive. \\n </s> |
<s>[INST] PowerFlex 755 and IPM motor with an encoder Summary: Can’t control the speed of a permanent magnet motorHi, I am trying to control Internal Permanent Magnet Motor (not experienced at all) with Powerflex755 drive and I am lost. Today last thing I was successfully able to do was direction test and auto tune for rotational test. But after that once I started commanding the speed, drive couldn’t hold the speed at desired speed. The status would show constantly changing into accelerating, at reference and decelerating (what is the reason for this?)And it would fault as input phase loss. I received other faults too while trying lots of things and it turned into a mess. We are commanding the speed using a 0-10V analog card. The permanent magnet Baldor motor has a continuous rated speed as 1800RPM. And it’s maximum safe speed is rated as 5000RPM on the data plate. I was using CCW wizard to tune and start the drive. My question is: I set the speed reference as: Speed reference: Port5,Param Anlg In0 Value Speed ref A high: 1800rpm Speed ref A low: 0rpm Analog in Hi: 10V Analog in Low: 0V Analog Out 0 as: Select: Port 0, Param Mtr Vel Fdbk Scaling: Value High: 5000, Value low: 0 Range High: 10v, range low: 0v Attached are the screen pictures from ccw. I can add more pictures if needed. Should the scaling be 1800 since it’s the rated rpm? But I will need to run it at maximum safe speed... I tried changing speed reference from 1800 to 5000rpm but it doesn’t accept any value more than 1800rpm. Any thoughts would be highly appreciated. I’m lost... Thanks in advance [/INST] What is the value of parameter 35 (motor control mode)? What are the values of parameters 25 through 31 (motor data)? What is the value of parameter 125 (primary velocity feedback select)? \\n </s> |
<s>[INST] Kinetix drivers Summary: Load the parameters setting automatically from PLC programHello, 1-Is it possible to load the parameters setting automatically for Kinetix 300 using RS Logix 5000 ? If this possible,explain how to do it? 2-For the Kintix drivers which the parameters loaded automatically from PLC program,when replace the driver with another,it should use another one with the same type or it possible to use any equivalent one? Best regards......... [/INST] Mr. PLC, the K300 isn't really intended to function that way. The K350 WILL do what you want, automatically. The K2000, K6000, K6300, K6500 will as well. The K300 drive is intended to be a stand-alone indexing drive. It IS possible to send move commands (position, speed, accel, etc.). There are add-on instructions available in the Motion Accelerator Toolkit to run a K300 from Logix5000. I've never tried to change any configuration parameters of a K300 drive from Logix, however. If you have not already purchased the K300 drive, I strongly suggest you switch over to the K350. The K350 is intended to be controlled from a Logix environment. All of the drive parameters are set and adjusted from Logix, are stored with the Logix application. To answer your second question, if you replace a Kinetix drive with an equivalent one, you should not have to do anything at all. If you put in a drive from the same family but larger power, you may have to adjust some parameters in the I/O tree and the axis properties. If you replace one Kinetix drive with another of a completely different family (say, replace a K350 with a K6000), you will likely have a number of parameters to adjust, but it wouldn't take long. \\n </s> |
<s>[INST] How to send an ASCII/telnet command to a IP device by RSLogix 500 Hello, I have a ML1400 and I need to access the data of a Omega device through a Ethernet Network. This Omega device is a coordinator that handles wireless data transmission from a 0-20mA device. You can use a Telnet programs to access the data using ASCII commands. (example; send command ERDG00A and the device response with 0 120 24 3,45 mA 4 V. Indicating nº of device, sequence, channel 1, unit, channel 2, unit.) The Omega device, a PC and the ML 1400 are connected to a network, and have an IP address that is in the same range. I want to know if the MSG commands works for this, and How can I configure this instruction? or What command can I use to request data from the PLC to the Omega device? Thanks and Regards. [/INST] Never done something like this, but I'm quite sure the only way is through Open Socket features. See Chapter 23 Socket Interface Using CIP Generic Messaging in MicroLogix 1400 Reference Manual. Unfortunately I've not found examples about that, just something about the -EWEB module of CLX, which uses similar manner to communicate through Open Sockets over Ethernet....In case, take a look to the following technotes for reference: Aid 33240 - Aid 32962 - fuzzy logic \\n </s> |
<s>[INST] Heartbeat for Powerflex 70 EC w/ ethernet with Logix Profile Hello, I came acrossed a slight issue today. I have a Powerflex 70EC VFD with ethernet connect to my CLX v16 PLC. The drive was running and I use the DriveStatus_Active bit as my running feedback. In the middle of the drive running, an electrician unplugged the ethernet cable from the drive which stopped the drive however the DriveStatus_Active bit stayed high and the drive displayed as running on my HMI. I was wondering if the Powerflex has heartbeat I can configure in the datalink so I can fault the drive on the HMI if I lose comms in the above scenario. [/INST] I would like to suggest a way to check the connection with your drive, that I've used in many plants...You may program a GSV instruction, checking the drive status using Module object... you may find some examples in the following technote: Aid 24162 In the RSLogix5000 online help, search for GSV/SSV objects - MODULE, to see what is available to check... see also attached screenshot with an example.... Hope this helps…- fuzzy logic \\n </s> |
<s>[INST] PF 400 output current fluctuations Summary: pf400 output current is fluctuation too muchhoping all you are doing great. here is new the problem, PF 400 3-phase 25Hp drive is having issue. in telephonic discussion with site person he told me that there are total 7 drives out of which 2 drives is having issues. these drives are connected with motor and motor is coupled with load via Belt system. Load is FAN and application is blower. drives are working fine when load is uncoupled with motor. Issue is that during operation current fluctuations can be observed from 15 amps to 45 amps and motor is producing too much noise. I already told them to set basic motor parameters and to increase PWM frequency from 4khz to 6khz but it wasn't making much difference. also compensation mode to set at both(electrical and mechanical) sometimes drive is also faulting at F7. accl dcl time is above 50sec. boost select is at 0.0 no IR, what else can be done to overcome this issue. regards. [/INST] Is this a new installation, or have they been running normally for some time and the problem suddenly cropped up? What is the nameplate data for the motor? What is the exact part number for the PF400 drive? All 7 systems are identical, but 2 do not function correctly. What is different about those 2? Are the belts tensioned in the same manner as the other 5, and tensioned to the same amount? Do the fans spin freely by hand (is there something wrong with the bearings)? Many questions, but they all need to be answered to diagnose this problem. \\n </s> |