<s>[INST] PowerFlex DC line voltage operation ranges Summary: Can the PFDC bridge operate with line voltages other than given in specs We have many situations in the elevator industry where the armature voltage of a given machine is above 240, and below 500 vdc. An example is one I am working on now where the armature voltage is 315 vdc. The existing machine is operating with an AB1395 drive, and it is fed by power from an isolation transformer with a secondary of 315 vac. This is a common practice, to help optimize form factor, and to help in sizing the transformer. So my question is, can I now use a PFDC drive with the same line voltage feeding the SCR bridge? There is no information in the literature. [/INST] Technical document for the PF-DC http://literature.rockwellautomation.com/idc/groups/literature/documents/td/20p-td001_-en-p.pdf What I see in this document is that your 315VDC motors fall in a hole for the Rockwell PF-DC products. This is DEFINITELY a time you should call Rockwell Tech Support and talk with the drives group: Dial 440-646-3434 Option 3 for Tech Support Option 1 for Direct Dial Option 1 to enter code Code 511 for DC Drives \\n </s> |
<s>[INST] PF700S - Fault 41 RideThru Timeout I have a 2Hp PF700S powered off of an NRU/RGU (so it is not rectifying AC to DC, it is supplied off of a DC bus). The motor is running about 127RPM, and is overhauled slightly so it runs ~ -12%FLT. There is some variability in the overhauling load. I have recently started seeing a fault 41, RideThru Timeout. This fault indicates that the drive has been in a bus loss ridethrough for more than 2 sec. Since I don't have AC supply to the drive and none of the other drives on the NRU/RGU are having faults, I assume that this is not truly the cause. Could I experience this fault if the drive runs at zero torque for some period of time? The motor does not have an encoder, and Par 485 = 0 (FOC). [/INST] Which firmware revision do You have on Your drive ? \\n </s> |
<s>[INST] PF 700H Does anyone understand why pf 700H experiences F10. User manual diagnostics suggests to replace drive, since failur has occurred within the PF 700H's powerstructure. [/INST] bayew, try to download from this LINK the troubleshooting guide for your drive frame (see the screenshot)... it could be useful to check the fibers... Anyway, as you can see from the manual, it could be an hardware failure that is not solvable in the field... :smileysad: the why... could be a defective part ?! :smileysurprised: - fuzzy logic \\n </s> |
<s>[INST] Meaning of Displayed current value on VFD Hi, I'm using PowerFlex40 VFD to drive a 3 phase induction motor. I have a basic doubt. In VFD display parameter d003 output current is shown. Now My question is which is this current. I can connect motor in STAR or DELTA configuration and current will be different in both the cases (I mean Phase and Line current values). Also there are three windings U,V and W in motor. So is it the case that VFD is delivering same current to all 3 Motor windings (just 120 degree apart ) and it is that current ? Also is this the RMS or PEAK or AVERAGE current ? [/INST] Hello, d003[Output Current] is the total output current present at terminals T1, T2 and T3 of the drive, as measured and calculated by the internal drive circuitry. The total output current can be defined as: where Torque Current is the amount of current in phase with the fundamental voltage component and Flux Current is the amount of current that is out of phase with the fundamental voltage component. Torque Current and Flux current are not available from the PowerFlex 40 drive (there are other drives from the Rockwell portfolio that provide feedback on Torque Current and Flux Current via read only parameters). It is expected the value of parameter d003 [Output Current] to be different depending on the internal arrangement of the motor windings (STAR or DELTA). Those values should be in accordance with the relevant formulae for voltage and current in typical Start and Delta motor connections. Please note that the drive will not be aware of how the motor windings are internally connected. The drive will be able to provide an output voltage up to the same level as the supply voltage (the drive will not be able to provide more voltage out than the voltage coming in). It is important to check the specifications of the motor to make sure that the motor windings in the desired connection (STAR or DELTA) are rated and capable of withstanding the output voltage provided by the drive. The inverter section of a variable speed drive does not produce sinusoidal voltage waveform, but rather a series of voltage pulses created from the DC bus, also known as PWM (Pulse Width Modulation). More information on this can be checked via this document Induction Motor Winding Voltage and Inverter Drive Output Voltage Relationship Those voltage pulses will be applied to the motor windings and there will be a flow of current from the drive output terminals T1, T2 and T3 through the inductance of the motor windings. The value of parameter d003 [Output Current] is provided in Amps with two decimal places. This value is filtered by the internal electronics of the drive and is an averaged value of the real time PWM current waveform. \\n </s> |
<s>[INST] Missing suggested tags # Hello In the Drives, Motions Control and Low Voltage Products community missing some [/INST] Thanks, Vincent. Tags are now updated: \\n </s> |
<s>[INST] PLC programming mode status to SCADA. I want to sent a high signal to SCADA when PLC is in programming mode.Somebody else made programs and I am commissioning now. There is a tag for CPU1 and CPU2 programmming mode in tag table. I did crpss reference and I cannot find where from it came. Also I have a redudent L75 PLC. When I turn the key on CPU and made program mode, I did not get program mode tag high to HMI. Its value is 0 and not getting high.why? [/INST] In Program mode the program does not run, so no values will change. Here, I have used a GSV to get the Status of the controller. When the controller is in Program Mode, as shown, the instructions don't run, so the values are as they were when it was last in Run mode. You haven't said what SCADA system you are using. If you are using FactoryTalk View SE then there are some tags you can read to get the status. They begin with @ and you can find a list in the documentation. You could look at the @Mode tag. If you are using a different SCADA package, check its documentation. You could use GSV instructions an ladder to get information about the Controller status. You are using a redundant processor, so you ought to be able to get information about each controller from the Redundancy object. So if if the Secondary is in Program mode you should be able to find out.\n </s> |
<s>[INST] POWERFLEX 525 DRIVE STARTING ISSUE Hi, I'm using powerflex 525, I'm giving speed command drive and it is reflecting in drive Hz, but if I give start command it's still in ideal, Before it was running perfectly [/INST] Hello Suresh, There are three start sources P046, P048, P050 (start source 1, 2, 3) There are also there speed references P047, P049, P051 (Speed ref 1, 2, 3) If using ethernet IP (for example) as start source and speed reference the use P046 and P047 change these parameters to the correct value. It is important to make sure any of the other start source and speed ref cannot be set to the same value. Start source 3 and speed ref 3 are set to Ethernet IP by default and will need to be changed in this case. Hope this helps. \\n </s> |
<s>[INST] Power Flex 40 - Device Net Adapter Problem The MOD LED is blinking red. The drive is not used in Multi Drive mode.The drive was working before around 100 hours then not used just staying in the cabinet as spare. HMI was sending speed and Run/Stop parameters, but no motor was connected to it. Wiring of the Device Net is ok.There was no error on the drive. I cycled power and nothing changed. I also reset to default values and nothing happened. I also got some warnings when resolving device mismatch. I never saw this message before. I attached a screen cut width the warning.The module was moved to another Power flex and still having the problem width the module. If I browse the network width RsNetWorks, then the module is shoved active, but on the device net scanner I have Error 83 for that node address. Flashing the adapter with the latest firmware release, I saw is not possible on field.- My question is what I could do to recover that drive- And second what could happened, in order that I prevent it in the future. [/INST] Hi enguson, and welcome to the Forum ! :smileyhappy: First, the MOD led... as you may already have seen in the User Manual, this is the meaning:The adapter has failed the firmware test, connected drive is faulted, or a drive is missing in Multi-Drive mode. Excluding second and third possibilities, as per your indication, only a firmware problem remains.Here some tests, also from troubleshooting chapter:If cycling power does not correct the problem, the parameter settings may have been corrupted. Reset defaults and reconfigure the module. If resetting defaults does not correct the problem, flash the adapter with the latest firmware release. The firmware of the communication adapter *can* be upgraded in the field, HERE the website with the firmware and instructions. About the scanner error 83...Slave device is returning error responses when module attempts to communicate with it (node number alternately flashes).Check accuracy of scan list table entry. Check slave device configuration. Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Is it possible to create a function block in RSLogix 500 Pro? [/INST] RSLogix 500 only uses Ladder language, in routines. Only LAD2 is launched by the controller, and you should use the instruction JSR to launch the other ladder routines. There isn't a feature like Add-On Instructions in RSLogix 500. Additionally, the JSR doesn't accept parameters, like Studio 5000. The feature that you are searching for, is available in Micro800 and CCW.\n </s> |
<s>[INST] Question about motor driver information Summary: location for storing motor driver info Hi all, I have questions on motion control. Q1. what are the motor driver information? And what it means when people say 'putting all motor driver info on the PLC and have an auto download of driver info once an new driver is installed'? Please help me in details because I don't know much about motion control and PLC ( I am fresh in auto) Q2. what it means when people say 'put recipe system and info on the PLC and not on the HMI'? Thanks! [/INST] The PLCs that support CIP motion and control Powerflex 755 VFDs download all data to the drive on power-up and successful network connection. When a drive is used outside of CIP motion, basic motor data is not usually sent to the drive from the PLC. In fact, the minimum control one could do over Ethernet for a drive not used for CIP motion is a start/stop command and a speed reference. All other parameters (tuning gains, motor data, etc.) would have to be set at the drive. Additionally, Rockwell's recent versions of PLCs can store the firmware of a drive (regardless of CIP motion or not). With the proper configuration in the PLC, this firmware can be downloaded to a drive automatically to a new drive replacing a failed one. \\n </s> |
<s>[INST] ControlLogix 1756-M02AE/A Servo Module I have a new 1756-M02AE/A servo module installed in my rack. When I attempt to configure the card the catalog number is present but grayed out. Please advise. [/INST] Are you trying to add it in online mode ?Try the same offline, only some modules can be added during online... - fuzzy logic \\n </s> |
<s>[INST] powerflex 70 Summary: sts light blinking yellowneed help with a powerflex 70 wont start the motor sts light is blinking yellow [/INST] i think i just need to change a parameter but not sure which one \\n </s> |
<s>[INST] MV Softstarter EDIT: moved to Drives and Motion community -FL Hi, wondering what the difference is between 1562E and 1562F. Thanks Terence [/INST] The 1562E was based on the SMC-Flex soft start controller, adapted to Medium Voltage. When we redesigned the MV soft starters to use the new SMC-50 based controller, the series number was changed to 1562F. There are numerous improvements and additions to the controller with the SMC-50, too many to list here. But suffice to say it does everything the SMC-Flex did, plus more. The power structure remains the same. \\n </s> |
<s>[INST] How to setting Axis scaling of ball screw vertical load ? Summary: How to setting Axis scaling of ball screw vertical load ?Dear Experts, I have the question about axis scaling setting my load is ball screw the pitch distance is 5 mm. height 1450 mm. How should I setting the values in these subject title ? Transmission ? Actuator ? Scaling ? Travel ? Soft Travel Limits ? My load move on ball screw in vertical and use 2 axis left and right it will synchronize position and speed moving in order to press the fabric roller by tension sensor control. Which command suitable for my application to motion control between MAG and MAPC ? If use MAPC How should I setting Cam profile ? How can I jog axis master and slave move only one pith of ball screw ? Best Regards, Vorapob Take_up_Machine.jpg× 1 / 1Show captionsShowing image 1 of 1 [/INST] more picture Axis_Scaling.jpg× 1 / 1Show captionsShowing image 1 of 1 \\n </s> |
<s>[INST] New surplus 1305- Not Enabled Message I acquired a 1305 drive AA08A (2HP) that I hooked up with a Programming Interface 1201-HA1.I tried two interfaces and keep getting a Not Enabled message.Reset defaults on HIM.I run a 1336 on another motor and the Interface runs fine.Have entire manual and they talk about enable signal but not in much specifics.I have 5V on TB2 pin 11 , nothing on 12.Any suggestions if I missed a jumper or setting or is drive bad?Thanks,Rich [/INST] As I can remember, you have to close either a contact or a wire between terminals 11 and 12 of TB2 to enable your drive; you can't use an external 5 volts source, it is supplied internally. - fuzzy logic \\n </s> |
<s>[INST] Leave VFDs unpowered or powered during curtailment? Occasionally we curtail parts of the plant or pieces of equipment. I personally think we should leave them running but stopped. Other people think we should shut everything down to save energy and potentially machine wear. We use 520 series and 720 series drives. Is there an official advice from Rockwell on this? I'm looking at periods from 1-6 months. Thanks [/INST] nan \\n </s> |
<s>[INST] Camming 4 Real Axis & 2 Virtual Axis? I am using an L45 processor with two sercos cards and 7 axis total. 4 of these axis need to be cammed together, but not at the start of the process. I have put these 4 on the same sercos card. I am presently camming virtual 1 to axis 1 & axis 2. I then cam virtual 2 to axis 3 & axis 4. I then jog both virtuals separately. Later in the process, I cam virtual 1 to virtual 2 and then only jog virtual 1. All 6 move at that point. This seems to work ok, but I haven't run the machine much at this point. Is this the best way to do this?Does anyone know any problems that may crop up? [/INST] your only alternative is to cam axis 3 and axis 4 to virtual 1 vs. cam virtual 2 to virtual 1 in your second mode. Based on my experience (even though I haven't done what you are doing) it seems like what you have already done should work fine. I think the only thing...if you read some AB literature (it seems to be in the back of my mind I read somewhere) that you have a slight delay (probably un-noticable, except in extremely critical applications) where you are cascading these camming functions. I think this delay is equal to one trajectory calculation cycle.... maybe in mSec??? You'll have to do a little reading if you think it will matter in your application. Sorry I can't help more than that. \\n </s> |
<s>[INST] Powerflex 70 Digital Output At Torque? Powerflex 70 has DigOut1 or 2 parameter setting At Torque/12. Does a powerflex525 have equivalent parameter for relay output or digital output? [/INST] Options for Digital Outputs starts on page 93 of the user manual: https://literature.rockwellautomation.com/idc/groups/literature/documents/um/520-um001_-en-e.pdf I suppose you could use option 7, Above Cur and set the level in the related parameter. Regards, RM \\n </s> |
<s>[INST] Rockwell Powerflex 700 faults auto reset EDIT: Removed links to external community probably added by the user via copy/paste of the thread -FL Have 700's and 753 VFD, in the 753 parameter P348 [Auto Rstrt Tries] can't find the parameter for the 700 to activate this feature. TIA.. [/INST] Welcome to Engage, Frank! See the following manual, page 41: https://literature.rockwellautomation.com/idc/groups/literature/documents/um/20b-um002_-en-p.pdf Param. 174 in PF700 drives is Auto Rstrt Tries: Hope this helps, fuzzy logic Please don't forget to LIKE and highlight the decisive answer: REPLY > Make Best Answer \\n </s> |
<s>[INST] Changing ACV Motor speed Tach feedback to DCV or 4-20ma HI , We would like to use our existing GE AC tach generator 90vac/1000rpm 180vac/2000rpm on a motor as a feedback to a DC drive. The drive will be similar to this 20hp 20P41AB073RA0NNN . This is for a conv belt, The drive excepts a DCv Tach feedback as well as 4-20 ma , 0-10v but not ACv. What converter is available to convert an AC Tach to DCv ? Or a converter to 4-20ma would also work. Note:The wave form of the AC Tach is not a square wave nor is it a nice sinusoidal shape.Frq is 265hz @400rpm. We have a few drives to upgrade and are comparing cost of an AC drive to a DC drive set up. I think a company called Mighty Modual may have what I need but if someone has been down this path before I would like to here their suggestions. Thank you! [/INST] Hi, Charles. Unless a fellow member of the community can answer your question, I suggest you reach out to Rockwell Automation Support for help with your particular situation: https://www.rockwellautomation.com/en-us/capabilities/industrial-maintenance-support/product-application-support/remote-support.html Thank you, Eileen \\n </s> |
<s>[INST] PowerFlex 70 Simulation Can I simulate a PowerFlex 70 Drive using RSEmulator or SoftLogix and download my program and do the necessary PowerFlex 70 configurations etc. [/INST] roomi, unfortunately this kind of emulation isn't available. :smileysad: You need to be connected to a real Drive in order to test its configuration... Anyway, either you may use Premier Drive Integration in RS5000 to create an offline configuration of a Powerflex, to download later (if your drive is connected via Ethernet/IP or Cnet), or you may use Drive Executive Software (also for offline settings of PF). More informations on those solutions above, in the following link:http://www.ab.com/drives/software.html Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] Powerflex Drives Specifications When reading the Specifications for a Powerflex 750 Series Drive it states that in Flux Vector Torque Control Mode the specification is +/- 2% 2500 rads/s bandwidth with an encoder and +/- 5% 600 rads/s bandwidth without an encoder I understand the percent is percent of total base torque. So if using a 60 n-m motor the 2% is 1.2 n-m or 5% is 3.0 n-m. I just don't understand what radians per second bandwidth has to modify the situation. [/INST] Hello, think of bandwidth in this context as how quick the internal Torque Loop inside the drive can work. The higher the bandwidth, the faster the torque loop can react to torque variations. The faster the torque loop is, the more accurate the torque regulation will be as well. The speed and torque closed loops inside the drive are implemented via the firmware. Typically the input of the torque loop comes from the output of the speed loop and the regulation of the torque signal occurs much faster than the speed signal. This is normal. Bandwidth can also be measured in Hz. 1 Hz = 6.28 rad/s. Think of the bandwidth in terms of frequency domain rather than time domain. So for example if signal to control (in this case Torque over time) is likely to change very quickly in the time domain, then the higher the bandwidth of the system the better chances the control loop of the system will have to control more accurately the output torque within tighter tolerances. Jose Garcia \\n </s> |
<s>[INST] How Did You Hear About Engage? Hi, Rockwell Automation staff! The Rockwell Automation Engage community has officially launched! Thanks to all who helped to get it set up as a digital collaboration space for customers and Rockwell experts to engage and optimize product usage. Some questions for you: How did you hear about Engage? What do you hope do learn or do as a member of the community? How can the community team help you with your goals and expectations? Do you have any questions or comments about your experience in this community? Thank you! -Eileen [/INST] hello Eileen, answers: 1. Blair Wilson told me about this a few months ago 2. I think/hope that this site will help engage in widely varying discussions; help people with questions to get answers. 3. My expectation is that if I (or anyone) posts a query here, that some expert will be able to chime in to help us out. 4. nothing at this point. \\n </s> |
<s>[INST] POWERFLEX DC 3000 - Field Volatge Summary: Field Voltage VariationI am using the Motor with Field Voltage of 195 VDC. But my drive is giving 207 VDC. I am supplying 220 VAC to field supply. Can anyone suggest how to reduce or amend the field voltage as per the motor requirement. Thanks for your support and co-operation. Best Regards [/INST] Take a look at this article: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/605924 If I understand it, the field voltage is not as important as matching the field current. Parameter 374 must match the dip switch setting for S14 (see page 60 of the PF DC User's manual for this critical dip switch configuration). Set the dip switch to match the motor field current from the motor nameplate, set parameter 374 to match, and supplying 220 to the field supply terminals should be fine. \\n </s> |
<s>[INST] powerflex 40 what is the difference between these settings on the dip switch??? Sink/SourceDIP Switch [/INST] You may choose if PF40 Inputs can be wired as Sink (SNK) or Source (SRC) via that DIP Switch setting. Leaving it as default (SRC) means you will use the positive wire to connect your inputs, to have them Active HIGH; on the contrary, setting it at SNK will allow you to connect your digital inputs to the negative wire (common) having them Active LOW - fuzzy logic \\n </s> |
<s>[INST] Kinetix 5500 Servo Driver H015 FLT S25…PRECHARGE FAILURE Hi, I had two kinetix 5500 servo driver H015 will show FLT S25…PRECHARGE FAILURE error on the drive whenever it being power up with DC 24V & single phase AC 240V simultaneously. I read across the user manual for the power up sequence. It required to provide DC 24V first then wait until it turn to PRECHARGE state only provide the single phase AC 240V. I follow with this method and the error didn't not show & motor show RUNNING state. But I feel quite weird for the machine & driver that need to turn on DC & AC voltage at different time. Anyone meet this issue & any solutions I can deal with this condition so that my panel able to power on the DC & AC at the same time & the servo driver able to run? [/INST] Hello, the power up sequence of the Kinetix 5500 servo drive, as mentioned early on this thread, is clearly documented on Publication Kinetix 5500 Servo Drives User Manual. By design specifications, the Kinetix 5500 servo drive needs to be powered up following that order. After applying the 24V DC control power, the LCD display begins the startup sequence, which includes a self test that requires a few seconds, before the axis state can reach the PRECHARGE state. Is that time when three phase AC power should be applied. If the AC voltage and DC voltage are applied at the same time, the shunt resistor circuitry may not enable at the right time, which could generate these type of nuisance faults. More information about this via this technical note Kinetix 5500 No display or lights, not powering up . \\n </s> |
<s>[INST] Compact L18ERM With Kinetix 350 Over IP Summary: Drives not recognised in Linx; Download from Studio puts drives in error Oh heck, this is proving to be a trial. System set-up is an L18ERM, f/w 21.11, lined to two Kinetix350 amplifiers, f/w 1.55, driving two linear drives. Comms is via Ethernet/IP. Amplifiers are set up as 192.168.1.xx, gateway 0.0.0.0. PLC is set to 192.168.1.xx. Once the kit is connected together, I can ping everything successfully on the network. If I now look in RSLinx (Classic), under the ethernet driver, I see the PLC. If I enter the IP address of the amplifiers manually, then they appear eventually, but are unknown devices and red-crossed. At this point, they still respond to a ping. All three LEDs on the front of the drive are flashing green. OK, I set up Studio5000 with the PLC and amplifiers, use the motor catalogue number to set up the amplifiers. I create a motion group and assign the amplifiers to the group and all is well. This configuration is then downloaded to the PLC, and by definition, the Kinetix drives. The PLC is quite happy with the configuration and can be switched between run and stop with no complaints. The drives however are definitely not happy. The network LED is solid green. The other two are flashing red. The drive shows a fault indicating motor over-temperature (the motors haven't been run at this point!) and can't be tuned or tested in any way from Studio because the software reports that the axis are not configured. RSLinx still shows the drives as unknown devices and red-crossed So now what? I've exhausted my meagre knowledge of IP and Rockwell and can't see that I've done anything wrong. My gut feel is that this is a firmware problem, but the latest revision of firmware for the amplifiers available from ab.com is 1.055 - the amplifiers were shipped with 1.55. Any thoughts, comments or laughter would help at the moment. My client has customers coming to see this system running on Monday (ha ha - why not commit to this when the R&D and commissioning is complete????) so feedback would be great. Many thanks, John [/INST] First question would be what version of RSLinx you're using. Next, I'd suggest downloading the K350 EDS files from Rockwell. That MIGHT help. Next, doesn't the K350 have a web page? If you access one of your K350s with a web browser (HTTP://192.168.1.xx) do you get anything? Just because you downloaded the program successfully to the PLC does NOT mean the configurations got to the drives. The fact that Linx can't really see them says it did not get there. How is everything networked? All devices connected to a central switch? What sort of switch (managed, unmanaged, what manufacturer)? If you want faster communications, you're welcome to communicate via email or even phone if you're USA based. I'll send you contact information privately. \\n </s> |
<s>[INST] where is my quesstion? hii can not find my quesstion which i post last 2 days and i wait or a reply?how many days a quesstion is stay in the forum? quesstion about un installation of rs emulator [/INST] javaboy420, there isn't a limit in time for a question to stay in a Board.... problem is that your questions were in the wrong board, so a Moderator has moved them to the right place.You cannot see these other Boards because of the following: There are some boards that require you to have a support contract with Rockwell to see them. If you already have a TechConnect support contract, you can put your authorization number directly into your profile and the boards will become immediately available. See this post in the Welcome section for more information. - fuzzy logic \\n </s> |
<s>[INST] PF700 Size 3 Parts AB: I have to repair a 52A PF700-VC VFD (Size 3 Frame) P/N 20B E 052 A 0 AYNACO1) Can I order parts for this size 3 VFD?2) Can I get a service/repair manual? We have ~20 of these VFDs that are powered directly from pole mounted 600VAC transformers in sanitary lift systems. Sometimes the diode/SCR End and MOVs are blown by the power company. I lost another one last night, during a lightning storm, and I would like to repair it in our shop. I know that AB offers an exchange repair but the price our distributor quoted was 72% of the cost of a new unit so it wouldn't be worth the time to exchange. --SMW [/INST] The following link is to the spare parts listing for the powerflex 70 / 700 drive familyMaybe you need some line chokes to dampen the poor power, and some transtector units ( www.transtector.com )to suppress the lightning. ( have saved many drives with their units) http://www.ab.com/support/abdrives/powerflex70/PF7ReleasedParts.pdf \\n </s> |
<s>[INST] HMI for PowerFlex 700 I have a PF 700 on a winder with some basic hard wired I/O. I am upgrading it to control tension using the PI loop but I need an HMI for the drive so I can change tension setpoint and monitor actual tension. I have done this with a system that has a PLC but I can not find a way to do it without one. Has anyone connected a graphical HIM directly to a PF 700 without a PLC in the mix? [/INST] I'd try a PanelView Component or small PanelView Plus with a DF1->DPI converter (the 1203-SSS). I attempted to use a PV Component over Ethernet to a 22-COMM-E and was unsuccessful. I think that over DF1 it might be easier. A remote HIM module with the process display set to show tension units would be a lot easier, but might present a navigation challenge to an inexperienced operator. \\n </s> |
<s>[INST] I have an application I'll be receiving where we will be using a Kinetix 5700 drive system to control stack crowders for a blank destacking application. My issue is we don't have good control over the stack location. I was wondering if there was a way for the Kinetix drive to find the stack location and perform its location based off its learned location. I'm envisioning that when the stack is loaded, the crowders would advance with low torque toward the stack. When the drive senses a jump in current, it would record the location and base its crowding operation off that location. [/INST] What you try to do should be possible, this will require some code in your Logix controller, and can be challenging. You also could use the VTS to do this (virtual Torque Sensor). There is also a very common way to locate the position of an item that is unknown, it's the registration sensor. You can connect to the drive an accurate sensor that will detect the presence of the item, and take a picture (registration) of the actual position of your axis. since you know the relative position of your sensor (HW location) and the position of your axis when the item trigger the sensor you know now the position of your item relative to the actual axis location. So you can control move your axis to an accurate position relative to your item. this require some code in Logix aswell.\n </s> |
<s>[INST] MPF series Motors Where do I find the Encoder counts/rev. for the MPF series motors (single turn)? [/INST] Depending on which drive you have there are 1024 Sin/Cos cycles per rev.The Kinetix 6000 interpolates to 2048 x 1024 counts per rev.The Ultra3000 SERCOS interpolates to 1024 x 1024 counts per rev.The Ultra3000 Indexer has programmable interpolation from 4-1024 default is 256. \\n </s> |
<s>[INST] SMC Soft Start Fault, Phase C Loss F # 37 I have a SMC Soft Start, cat [/INST] Did you already read Aid 63282 ? - fuzzy logic \\n </s> |
<s>[INST] Kinetix 350 - 2097-V33-PR1-LM Incoming power supply Summary: Can the Incoming power supply support Single phase 230V AC Hi, I am a new user of Kinetix 350 - 2097-V33-PR1-LM. I purchased a new drive. When seen on the Mains connector side its say Single phase 120V or three phase 240V. I use the Motion analyzer software to finalize the part number. The software says we can use it as Single phase 240V incoming power supply. In actual Can I power it on with a Single phase 230V AC? Thanks, Gowri. [/INST] Yes, see the table below. - fuzzy logic In order to enhance Forum's contributors reputation, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] DriveExecutive program Summary: DriveExecutive backup file not openingDear All drive executive installed on my computer but what could be the reason why the imported driver doesnt open backup files blank page open , does not give error I checked on another computer the versions are correct my computer only opens the backup file it received what would be the reason Thanks [/INST] My computer only opens the backup file it received Could you explain this in a different way? Do you mean your computer will only open .DNO files that it creates and will not open .DNO files created on a different computer? \\n </s> |
<s>[INST] PF700 faults Summary: Power flex 700 faultsPower flex 700 always faulted number 10 and display system fault,I don't know how to disappear it and what exactly is the system fault. By the way 250kw. [/INST] I guess you're talking about a PF700H... correct ? Here from the Manual : F10 - A hardware problem exists in the power structure. More specific info about this fault can be obtained by checking the fault subcodes... See the following technote for more infos : 55133 - PowerFlex 700H - what is a Fault 10? Chances are that you will have to repair or replace the drive... - fuzzy logic In order to enhance Forum's contributors reputation, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] After swapping of two Kinetix 5500/5700 Servo Drives and assigning of new IP Addresses, the modules show error code 16#080e Safety network number mismatch in Studio 5000 Logix Designer Software. [/INST] Disconnect EtherNet network cable from drive module to be sure to close Motion and Safety connection. On Kinetix 5700/5500 Servo Drive display\n press the Settings button, \n select Safety, \n then press Enter button three times to Reset Ownership.\n When module boot is completed, the EtherNet connector can be plugged in again.\n This method is described in Kinetix 5700 Servo Drives User Manual, Publication 2198-UM002.\n </s> |
<s>[INST] Temp problem on VSD Unrelated to the false F008 issue is the fact that, if I run the VSD’s with the doors closed the drive temperature (B014) goes up to over 70 deg C. If I open the door it comes down to 61 deg C. This site is in the eastern part of South Africa and the average air temp in the summer is above 40 deg C with a very high humidity factor. We have forced air cooling on the enclosure's that move about 540MC/H through the enclosure. The pumphouse ambient temp is about 25-30 deg C and could go as high as 45-50 deg C in the summer. [/INST] 1. Verify that maximum ambient temperature has not been exceeded. 2. Check fan. 3. Check for excess load. If the drive still fails after checking previous actions, probably it should be replaced... :smileysurprised: See also Aid 59345 Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Axis Event Logging Summary: Capturing events on K6500 amplifiersA while back, I was able to download some sample code from Rockwell that captured events on K6000 (SERCOS) amplifiers. This was handy when debugging events or faults that occurred on back shifts or weekend events. Does anybody know if there is sample code like this for K6500 amplifiers? [/INST] I haven't seen an error logging AOI for the K6500 like the one for the K6000. The built in fault log in the axis properties should provide similar functionality though, just make sure you only execute an MAFR or MASR when a fault or shutdown condition exist. Otherwise your log will get filled up with every time you executed one of those instructions. You can also see all the faults that have occurred on a particular drive through the drive webpage. \\n </s> |
<s>[INST] PowerFlex 753 go to maximum speed Hello, I'm using a PowerFlex 753 (7.5kW, 15A) AC drive. It takes the speed reference from the analog input. It works in closed loop. I'm using 20-750-ENC-1. But, for example, when the commanded frequency shows 12 Hz, it suddenly starts working at maximum speed. The version is 14.005. Any ideas what might be causing this issue? How can I solve it? Regards, [/INST] Hi, Programming Manual, Appendix A: Control Block Diagram: from here, find out the correct block diagram of your specific application Execute CCW to monitor your reference signal, actual feedback signal (shown on the block diagram), torque referece, actual torque, etc. Surely you can allocate where the problem is. Good luck! Terence \\n </s> |
<s>[INST] Connected Components Workbench. Is there a reason that CCW version 21 takes 5 and a half minutes to open? All of the other Rockwell software on the same computer opens normally. [/INST] Does the delay happen at opening the CCW from its icon, or at opening a CCW project? CCW launching delays might be related with big projects and computer resources. I tried in my virtual machine (not lots of resources , but only CCW V21.01 software installed) and it has opened in 30 seconds. If it isn't the case, you can check the possible cause in Windows Events at launching it. Or in Task Manager. May be a dependency of a service that spends to launch.\n </s> |
<s>[INST] ONS automatically reseting bit, It is energized green color. why? [/INST] If you cross-reference the ONS bit, is it used elsewhere? The ONS will highlight green once it has executed and stored the memory bit. Otherwise would could insert some diagnostic latches or counters on each branch to catch a possible nuisance condition.\n </s> |
<s>[INST] kinetix 5500's Summary: MAM will finish after an interrupt instead of executing new MAMI have run into an interesting issue. When i break the light curtain while my machine is in motion, safe torque off activates and the program holds that position until a return to home command or continue cycle is initiated. this is normal operation. On this machine though, i have found MAM's still enabled even if the rung isn't true anymore, and the drive will finish the motion that was in progress instead of executing the return to home MAM. is there a way to clear the memory of the drive in this situation so i can be sure it executes the MAM the logic dictates? as of now, the drive is not following the logic of my program. i have looked at scan times, made sure that my routines were being read in the right order, checked for duplicate MAM's and OTE's, made some logic very unique to ensure it wasn't duplicated in other places. i have worked on this issue for two days and not had any luck. processor is 1769-L27ERM-QBFC1B mated to 2198-H070, H008, H003 - ERS. Studio5000 version 30.11 I have 4 identical machines that were just built and all exhibit same behavior, so i'm certain it is in my program, but i cannot find the bug in the code. i have built 30+ machines like this but have never run into this issue before. [/INST] Gregory, you're far more likely to get a useful answer if you share your ACD file and point us to the location of the MAM that persists. \\n </s> |
<s>[INST] HW overcurrent Summary: PowerFlex 700 HWovercurrenthi everyone Can anybody help me with 20B PowerFlex 700 HW overcurrent fault (F12)? i run Drive without motor there is no fault. But when connect the motor and running( there is no load) F12 immediately applied. [/INST] You have already done the test to see if it's the drive or external. If no fault without load it is shorted motor or leads. Megger both. \\n </s> |
<s>[INST] PowerFlex 700 Drive fault [/INST] Dave, I think a little bit of information is missing. ;) JHutch \\n </s> |
<s>[INST] 2097-R6 Shunt Resistor Summary: Clarification on 2097-R6 Heat Sink SelectionI have a 2097-R6 shunt resistor I need to install on a 2097-V34PR5-LM Kinetix 350. The installation guide says to use a 7.9 x 7.9 x 0.12 heat sink at 77 degrees F, but it doesn't say much more than that. I don't understand what the 77 degrees F is supposed to tell me. What material can/should be used? Can I use a sheet of aluminum? Should I mount it using thermal paste? Is there anything to consider regarding how the heat sink is mounted to the cabinet other than spacing? If this thing truly can get up to 392 degrees F, I want to make sure I do this right. http://literature.rockwellautomation.com/idc/groups/literature/documents/in/2097-in002_-en-p.pdf Thanks. [/INST] I think the 77 degF refers to the ambient temperature. I would mount the resistor to the enclosure and use the metal of the enclosure as the heat sink. If you tighten the screws to the specified torque then you shouldn't need any thermal paste. Monitor the temp of the resistor while the machine is running at max speed (when the resistor is working the hardest) and verify it stays below 392 degF. \\n </s> |
<s>[INST] MATC vs MAPC Summary: What is the main difference?I have an applications where cutting blade has to match speed of a material for certain time, then let material move certain distance and cut again... I tried to use MATC and it works, the complexity is that if I change material cut distance (requirement), speed does not adjust, it just scales up or down. I am trying to figure out how MATC is used, can someone explain in simple words how this instruction works and how do you relate position to the master? Thanks! [/INST] Can we assume the master encoder runs on the material? I would think an MAPC (position cam) is a better choice. You would use MCCP in conjunction with MAPC in order to define the region at which the blade runs at web speed, and then can be faster as needed to recover. I wouldn't touch a time cam at all for the exact reason you've encountered. \\n </s> |
<s>[INST] PF 400 Fan & Pump Ratings Summary: Trying to understand the different drive ratingsGreetings all, I recently sold a 10hp and 2 x 15hp 208V PF400 Fan & Pump drives only to have my customer come back and tell me that I have undersized the drives. The motor FLA's are 32.7A and 47.8A respectively. Their case is that even though the part numbers on the drive indicate that they drives are 33A and 49A output capable, however in the technical data guide, in the F&P section it states the drives have a 30.8A and 46.2A output. My question is, how is this possible? See clips of the two ratings below. Please help. Standard Drive Rating F & P Drive Rating [/INST] I believe the numbers you're looking at are on page 37, which are for configured drives. Did you sell these as configured or just open type stand-alone drives? \\n </s> |
<s>[INST] Coordinating 2 axes, MCLM, MAG, MAM & MAJ I need to be able to move 2 axes simultaneously with a defined relationship between them (the axes are at right angles, and the angle of the trajectory with respect to 1 of the axes is defined). To do a move of a predetermined distance it seems my best bet is to use a MCLM instruction (although I guess I could use MAG and MAM to gear the axes together and then move one of them). To allow the operator to jog the axes I think my only option is to use MAG and MAJ? Having geared the axes together using a MAG do I then just execute a MAJ on one of the axes and the other will automatically follow it? Presumably the .ER bit on the MAJ instruction tag will only be set if there is an error on the master axis? Does a Motion Axis Stop (MAS) 'disconnect' the 2 axes so that they can move independently? If not then what does? A bit later... I guess another option is to create a virtual axis and gear the 2 real axes to that. I wonder what the pros & cons are of the different approaches? Mike [/INST] If you define a coordinate system, axis 2 does not automatically follow axis 1 in a jog. The two axis are only going to be together when you execute the MCLM or MCCM instructions. For operator jogging the two axis together will require the MAG. Having geared the axes together using a MAG do I then just execute a MAJ on one of the axes and the other will automatically follow it? The MAJ is executed for the master and then the slave will follow at the gear ratio. If you MAJ the slave, it moves by itself. Presumably the .ER bit on the MAJ instruction tag will only be set if there is an error on the master axis? The .ER bit simply means that there was an error in the MAJ instruction. It does not indicate that there was a physical error with either of the axis, unless either axis has a particular error and that causes the instruction to fault. Does a Motion Axis Stop (MAS) 'disconnect' the 2 axes so that they can move independently? If not then what does? The MAS can 'disconnect' the gearing if the Stop Type is set to ALL or GEAR. If the Stop Type is just set to Jog for the master then they both stop, but both will move again for the next motion command on the Master. I guess another option is to create a virtual axis and gear the 2 real axes to that. I wonder what the pros & cons are of the different approaches? There is really no big difference in using the virtual to control the other two axis unless your automatic mode is for a coordinate system and the manual operator jog is for just jogging the two axis in a gear mode. That might make your programming more organized, but doesn't effect the timing or accuracy of the moves. \\n </s> |
<s>[INST] downsides of running drive at low frequency for long periods? Summary: What are the disadvantages of running a VFD at a low frequency for an extended amount of time? [/INST] The VFD doesn't care what output frequency, it will run anywhere in it's range all day. The problem is the motor. A normal general purpose motor TEFC motor will not cool itself at low speed and burn up windings. \\n </s> |
<s>[INST] 1756-M02AE wiring for single-ended encoder Summary: 1756-M02AE wiring for single-ended encoderIs it possible to connect a single-ended encoder in to 1756-M02AE? [/INST] Welcome to the Forum ! NO. Single ended encoders will not work with the 1756-M02AE module The 1756-M02AE supports differential encoders only. - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] PowerFlex 400 Fram size H overtemp trip I am having trouble with a VSD. Even if it has only been running for 2 minutes, then it comes up with a HeatSink OverTemp (F008) error. There seems to be an error with the sensing circuit since it tells me that the temperature is 140 deg C (B014) but it is NOT – if I switch the drive completely off and wait for it to discharge before switching on again (approx 3 minutes), then it comes up fine with a temperature of only 41 or so degrees C.All of them are 22C-D460A103 Series A, Manuf 19 August 2008, [/INST] It could be a faulty sensor...anyway, try to see if all the fans start when PF400 starts by run command....if just one of the fans doesn't start, then you have to replace it. Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] PowerFlex 40P scattered read on Ethernet I see the knowledgebase article (63547 - PowerFlex40 Scattered Read/Write on DeviceNet), but was wondering if the same works for on Ethernet (with 22-COMM-E).If so, is everything the same as DeviceNet?Thanks, Kevin [/INST] Kevin, The 22-comm-e supports scattered reads and writes through the DPI Parameter Object. The method is the same as the other scattered R/W MSGs that you have configured already. \\n </s> |
<s>[INST] Add index option Is there a way to control position with a 2098-DSD-010-DN Firmware 1.32? or Is possible to convert a 2098-DSD-010-DN to 2098-DSD-010X-DN? [/INST] You may control your Ultra Servo Drive from an external controller by Analog Command or Pulse Train... as far as I know, there is no way to a have a conversion in the field from servo model to an Indexer or Devicenet model...you have to buy a new drive for that. :smileysad: - fuzzy logic \\n </s> |
<s>[INST] Servo motor Brake engage problem Hi, I am trying to find if there is any solution to my problem. I am using a servo motor with a brake and the mechanical part that this motor is moving, shakes only when there is a transaction from drive going off to brake engage in the motor. I am using these blocks in my program: MSO -->MAM or JOG --> MSF Parameter configuration: Mechanical brake engage delay = 0 Mechanical brake release delay = 0 Mechanical brake control = Automatic stopping action = Current dec & Disable Drive type :2198-H025-ERS2 Motor type : VPL-B1003T-P Ps, I do not think that it is a good solution to hold the drive in ON state for a long time in order not to have this issue, Your thoughts about this will be welcomed. [/INST] Try adding an MAS (Motion Axis Stop) before issuing the MSF (Motion Servo OFF). One would expect some unwanted dynamics if you're allowing the brake to activate while the motor is still turning; servo brakes are generally holding brakes, not stopping brakes. I would suggest issuing the MAS, verify that the axis stopped by checking for zero speed (I think I remember that drive has a zero speed bit in the axis parameters already), then issue the MSF. If the drive definition doesn't have zero speed bit, it's easy enough to use a LIM command with axis velocity. \\n </s> |
<s>[INST] armorstart Hi, i am using armorstart for the first time and when i come to add a 284D drive into the devicenet program i get an error. saying The applet used to configure the device did not initialize properly.i have downloaded the latest EDS from the web.has anyone any ideas? thanks [/INST] Welcome to the Forum ! Be patient, but more infos are needed to try to help.... :smileywink: RSNetworx versionRSLinx versionArmorstart catalog numberEDS file version downloadedOS of your PC Best if you can also add a screenshot of the error you got. - fuzzy logic \\n </s> |
<s>[INST] PF 755 - Rod Torque measurement unestable Grettings We have in the field a PF755 drive connected to an 32 poles permanet magnet motor using the PCP oil well application. The motor runs unstable as if it has a fisical impediment in the bearing. The torque shown in the parameter 1166 vary from 0 to 300 to 0 again in a matter of seconds. Originally the drive was connected to an 60 poles motor. When we change in the drive the number of poles back to 60 the torque stabilize and the motor work fine until it reach 200 RPM when the problem star again. Is it possible the autotunne is not working propertly? We have done it several times an it never gave any alarms. The motor characteristics are: 380VAC, 37Amp, 27HP, 350RPM, 32 poles. The drive characteristics: PowerFlex 755 75 Kw. Thanks in advance for te response. [/INST] Hello, Thanks for sharing this problem. It looks as if the drive is being used within a Pump Jack oil well application. I am hoping this thread could be visible by other Engineers that have used the PowerFlex 755 drive on this particular type of application, very common I believe in countries with significant onshore oilfields. I do not have experience on this type of application. I can see a specific set of many parameters within the Applications File that should be carefully addressed based on the key mechanical elements of the rig. Equally, there is an additional feature called Pump Off, addressed to automatically change the speed of the pump jack based on torque feedback from the motor. The procedure to set up that feature is described in more detail on Appendix C of https://literature.rockwellautomation.com/idc/groups/literature/documents/pm/750-pm001_-en-p.pdf and assume the Motor Ctrl Mode to be InductionFV. Please note that there is no mention to permanent magnets motor when using the Pump Jack feature. There are also some specific relevant technical notes from the Rockwell Knowledgebase that address this type of setup/application as well. Please see below: PowerFlex 750 series drive Pump Jack setup guide PowerFlex 750:Pump Jack Pump-off Function and Setup Any comments from any Engineers with relevant knowledge and experience on this type of application shall be very welcome on this channel. Regards, \\n </s> |
<s>[INST] How to forcibly reset counts in a 20-750-ENC1 encoder option Summary: Is there a programmatic method to reset the current count of the encoder board? This is a motion application using a CIP-Motion PowerFlex 755 drive with a standard incremental encoder.. In general it works quite well. But the trend of position and velocity that I've been watching worries me at times - velocity becoming ragged and unstable at times.. Passive rehoming of the axis doesn't reset the underlying encoder count, but I may have one of the setup options wrong for doing so. My Axis Travel option is set for Unlimited, therefore the Unwind option isn't available for setting. It's configured this way because that was the default - and I didn't mess with anything that didn't appear to need messing with. As the encoder values increment toward very high integer values, the velocity trace (on a trend) becomes increasingly ragged. Restarting the drive causes the encoder to reset to zero, and the raggedness disappears. My theory is that encoder values that correlate into floating point values (positions and velocities) begin to lose numeric precision when derived from very large integer values. There may be a variety of more elegant ways to solve the problem (and I'd be interested to hear them all), but my brute force method would be to just reach in and reset the encoder. Is there a way to programmatically control the encoder board's count? Is it through an SSV? Or a motion instruction? Or explicit message? Or some other clever thing that hasn't occurred to me? My exact application configuration is contained in an earlier post. The sparseness of this post is an attempt not to be redundant with those details (if relevant). Thanks [/INST] I'd try MRP (Motion Redefine Position). \\n </s> |
<s>[INST] kinetix 5100 registration help Has anyone had any experience with setting up a K5100 for registration using a photo eye. I have done this with the k300 with no problem. There is a migration guide for k300 to k5100 but doesn't really cover this. Any ideas, suggestions, or direction would greatly be appreciated. [/INST] Hi Justin. Have you tried the Rockwell knowledge Base ? https://rockwellautomation.custhelp.com/ it all depends on the type of integration, are you going to use the drive with a MicroLogix , a ControlLogix/CompactLogix or standalone? \\n </s> |
<s>[INST] E91 Watchdog Timer Error on Kinetix 300 I have a couple of MPL motors setup (using Modified code from the Rockwell Sample code SMC_ENETIP_ML1400_K300_2AXIS_V1_0.rss) It works great, Micrologix 1400 1766-L32AWAA Kinetix 300 2097-V34PR3 >>>> MPL-B310P-MJ72AA Kinetix 300 2097-V34PR6 >>>> MPL-B4560F-MJ72AA Now I want to setup another machine, but I want to use different IP address. I changed String: ST199:0 From 192.168.1.5 to 192.168.3.229 ST199:1 From 192.168.1.6 to 192.168.3.230 ST199:2 From 192.168.1.7 to 192.168.3.231 Once I do this the RIX201 Tables seem to populate with all of the correct IP addresses. I think that I have changed everything correctly, but I keep getting an Error on the Kinetix drive: The Error that I get is: E91 user watchdog has timed out. I get the error on both drives, and when I log onto the drives using the MotionView software, I can't clear the Error Any suggestions on where to look? [/INST] I think that the problem was in my PLC File. We found out that N197:11 had a value of 408 , and N197:23 also had a 408 value. Those integer files are supposed to toggle on and off from 0 to 1 so that the controller knows that it has communication. I manually entered in a value of 1 and then they started going back and forth from 1 to 0 and the E91 error went away. \\n </s> |
<s>[INST] Control Logix5561 softwares requirement Hi,As a part of my thesis I am using a ControlLogix5561 processor to communicate with powerflex 700 AC drives. The set up will used to do basic operations of speed and torque command and to display the parameters on the HMI. I have downloaded the demo softwares:1) RSLogix50002) RSLinx Lite As it is a thesis project and not a industrial project there is a financial restriction. So I am wondering whether I can use the demo version to program the PLC or I will have to purchase the full version? And if I will have to purchase the full version then can anyone please let me know what all softwares are mandatory. I think:1) RSLogix50002) RSLinx Classic Single Node (I will be having only one workstation)3) RSView32 -- I think so??? Also while going through the tutorials I understood that:Firmware revision=RS logix5000 revision=Project (.acd file) revision How do i take care that Firmware revision=RS logix5000 revision?? Should i take care while ordering?? Thanks in advance... any help will be much appreciated Jai [/INST] also the cotrolLogix processor is without the compact flash card. Why is this card required and can i do away without this card?? Jai \\n </s> |
<s>[INST] DriveExecutive, PowerFlex 753 and 20-750-DENC-1 Summary: Can't configure a PF 753 with a DENC card in DriveExecutive 5.02Hi, I'm trying to create a Powerflex 753 with a Dual Encoder board 20-750-DENC-1 using DriveExecutive 5.02 but DriveExecutive doesn't allows me. I created one using CCW software V 11.00 from a friend's computer My question: Is there any version of DriveExecutive that allows me to create a PF753 with a DENC? it's just that CCW and I don't get along well together Thank you [/INST] I think your problem is the DriveExecutive version. You should upgrade to 5.06.03 (the last supported version of DriveExecutive). In addition, there may be some drives database file upgrades necessary to make this work. Go to Rockwell's PCDC site, pick the downloads section, type in DRIVES in the search box. The first one that comes back is drives database files for CCW. The second one is drives database files for DriveTools (DriveExecutive). \\n </s> |
<s>[INST] Explicit messaging to a 20 Comm module Now that I have the Explicit Messaging working great to the PFlex 7XX drive, I need to know how to set up the Set Attribute Scattered MSG to write Parameters to the actual 20 Comm E module. I can't find (or understand) the Class/Instance/Attributes that I need to specify to write to the module and not the drive. Can anyone point me in the right direction?Thanks,Bill [/INST] Bill, Class Instance and Attribute should be the same as those used to read/write parameters in the drive... Just you need to specify in the Scattered_Write_Request (source element in the example of the 20-COMM-E User Manual) the number of the adapter parameters; they start from 16384, as you can see in the screenshot. So, for example, if you want to write Accel. Time 2 in the drive, you will use 141, if you want to write the adapter parameter 03 to Enable BOOTP, you need to use 16387 (16384 + 3) Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Power Flex 40 Speed transition Hello All, I have a turn Table that is driven by a 1 hp motor controlled from a Powerflex 40. The Turn table is 18 feet in diameter.After all four stations are complete, the VFD is told to Run at the preset frequency of 60 Hz. During the rotation @ approximately 11sec, a prox switch is flagged that changes the preset frequency to 10Hz for a slow down and finally the stop prox switch is flagged and engages stop. During the slowdown process the turn table appears to stop (Jerk) and then continue on at the 10Hz speed. How can I ease the transition between the selectable presets? More info: The selection of the preset is controlled by 3 inputs to 5, 6, 7 on the terminal strip. The purpose was to have 4 selectable speeds and a slowdown speed to ease the stopping of this massive turn table. Suggestions are appreciated. [/INST] You will need to closed vector using a Powerflex40P with encoder feedback from the motor. With the large diameter the gearing would cause alot of back pressure onto the motor shaft when decelerating. \\n </s> |
<s>[INST] PowerFlex 523 - static vs dynamic autotune IR Voltage Drop Hello, We have a few PowerFlex 523 drives, all setup in the same manner and connected to identical motors. Static autotune was done on all of them and as a result the parameter 496 (IR Voltage Drop) was automatically set by the drives to a value in the range 22-24 V, each drive having slightly different value. Then, dynamic autotune was run on two of these drives and the parameter 497 was automatically set on them as expected, but also these drives changed their parameter 496 to a completely different value - 40V. Is this normal for dynamic autotune to override parameter 496? The updated value was not just slightly different. Static autotune sets it to 23.8V, then dynamic autotune overrides it to 40V, the difference is about 16V. Is dynamic autotune able to sense the voltage drop better and hence updates this value or is this erroneous behavior? [/INST] Hi Nickolay, The Static Tune Par 70 =2 can be performed in SVC and FV modes (Par 35) no matter if motor has or not a feedback encoder. It usually gets a reasonable value for the most of applications. The Dynamic Tune Par 70 = 3 only returns valid results with FV with feedback, or SVC with uncoupled load. If your application doesn't have a feedback encoder, the best solution is the Static Tune. It is explained in page 61, speaking about the Par 70: PowerFlex 750-Series AC Drives - Programming Manual. Publication 750-PM001. Paragraph: Important: If using rotate tune for a Sensorless Vector (SV) mode, the motor should be uncoupled from the load or results may not be valid. With a Flux Vector (FV) mode, either a coupled or uncoupled load will produce valid results. \\n </s> |
<s>[INST] Loop Detected Error in EN2TR Module. We have rockwell dcs with L75 controller and EN2TR. In one of the network the EN2TR module went to fault with error code as Loop Detected. Beacon time out and interval went to huge number outside the range. Anyone faced this issue? [/INST] Loop problems in DLR networks might be solved declaring a second Supervisor in the network. With 2 supervisors, one be the active supervisor and the other the backup supervisor (selecting which is the active, can be done with the precedence number, the highest wins).\n </s> |
<s>[INST] Power Flex 755 Fault Code 61 Noticed every time the drive is stopped the HMI display shows a FAULT S 61 0.000 RPM. AUTO. Why does the drive display a Fault code 61 and what does it mean? [/INST] The PM manual says a plain fault 61 (without the S) is Shear Pin 1, that the value set in P436 (Shear Pin 1 level) has been exceeded. I'm willing to bet you're not using the shear pin function. One would expect the S to refer to safe-torque-off or safe-speed-off. Do you have either card installed? That said, I can't find a reference to fault 61 in any of the safe-off module documentation either. What option cards are installed in this drive? Are you running it as a CIP motion axis? \\n </s> |
<s>[INST] Powerflex 525 communication I have a system with compact logix plc and three 525 power flex vfd one vfd is 5hp but i need go dawn to 3hp, did i need modify the program? [/INST] Probably. The IO tree in the logix program expects to see a 5HP drive and will likely complain when it sees a different drive at the 5HP's IP address. \\n </s> |
<s>[INST] PF 70 Hi all, Can we use the PF 70 with 4X enclosure outdoor in a shaded highly corrosive area? [/INST] Are you *talking* about IP66/NEMA 4x version of PF70 ? In that case, at the following links you may find some infos... http://www.ab.com/drives/powerflex/70/http://www.ab.com/drives/powerflex/70/70_nema.html Be aware that only the Flange mount version is suitable for outdoor use. If you're instead asking for a configured drive, this other link... http://www.ab.com/drives/powerflex/70/70_configured.html Last, if you're installing the drive in a custom enclosure, if it is NEMA 4x, for sure it is ok. Hope this helps...- fuzzy logic \\n </s> |
<s>[INST] Powerflex 40 I have a power flex 40 which has power to it but no power on the screen and just 3 flashing amber lights Port, Mod and Com A. please help!!! [/INST] Perhaps those drives have failed due to a problem with the switchmode power supply.Take a look to Aid 34911 .... Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Running a Kinetix5700 drive on 120V AC Hi All, I am new to the community. I teach at The Ohio State University and am using a PLC workstation with an integrated Kinetix 5700 drive. The drive has been wired to 120V AC for power instead of 240V. I have been told that to use the K5700 with 120 AC there is a specific procedure/code that allows the 5700 to use 120V, but I haven't been given the procedure or code. Does anyone know what the procedure is? Thanks in advance for any help. Tony... [/INST] Hello Shoup. You are right for demonstration purpose we have a Demo Mode that can be enable. But we do not provide those details on Social media. If the Kinetix module that you interested in operating in Demo Mode is a part of a Rockwell Demo Box/Unit, the unit comes with all needed software to be able to operate the module in Demo Mode. If the accompanying software that is included with the Demo Box/Unit is lost or misplaced please contact your Rockwell distributor that provided the Demo Unit to you. So please contact your local Rockwell Automation office. regards \\n </s> |
<s>[INST] Modbus TCP for PowerFlex700 drives Summary: Modbus TCP for PowerFlex700 drives Looking for anyone that has successfully deployed the 20-COMM-M Modbus/TCP Adapter for control and monitoring of a PowerFlex700 Drive. It appears that the addressing listed in the 20-COMM-M manual does not conform to standard Modbus protocol. Need to know what is going on with mapping to drive parameters and data. Thanks! [/INST] Hi, try to see if the following old topic could help... together with the comm module User Manual... http://forums.rockwellautomation.com/posts/dde8b7fcb1 http://literature.rockwellautomation.com/idc/groups/literature/documents/um/20comm-um014_-en-p.pdf - fuzzy logic Please remember to Rate the Comments( ) to enhance the reputation of the User who provided help,or close your Topic using the ( ) button over the answer that solved it. Thanks... \\n </s> |
<s>[INST] Reminder to all Rockwell Staff on the Engage Community Hi there. Thank you all for joining the Engage customer-facing community! This is a friendly reminder/notice to make sure that if you have questions or want to discuss product-related subjects with fellow Rockwell Automation staff members, you should follow these rules: If there is already an internal communication mechanism (IT ticket, Yammer, Epoch, etc,) where you can have a conversation with fellow staff members, please use those established mechanisms. Engage is not a substitute for those areas... Engage is primarily a customer-focused hub where customers can ask product-related questions. Also, this RA Staff area on Engage likely has a smaller internal audience than the already established internal areas. If you want to reach out to staff members who are also members of Engage, this Rockwell Automation Staff forum is the right place. Questions asked in this RA Staff forum should be focused on questions that help other staff members in answering actual or anticipated questions on Engage. Please do not ever post a question to the larger Engage community that is intended for staff members. We do not want customers to see questions that are intended for RA staff. I hope this clears up any questions you may have around the larger Engage customer-facing community and the internal RA Staff forum. If you have further questions, please take a look at the Engage Welcome post and the FAQs. You can also email me directly at [email protected] or email [email protected]. Also, I hope your experience in seeing how customers are using RA products is helpful and educational. If you are interested in interacting with members on Engage, please reach out to me, and I will help you with some tips and tricks (and some rules) about how to best participate. Thank you! Eileen [/INST] nan \\n </s> |
<s>[INST] Setting parameter 445 on 753 Summary: Sensitive level in terms of %Good day, I wish to activate the phase loss on the 753 drive and I have a few questions 1. What is the correct setting of output phase loss level ( parameter 445) 2. The default setting is 200, and 200 is equal to what percentage of phase loss? 3. The sensitivity is based on voltage? M. Mahao [/INST] https://rockwellautomation.custhelp.com/app/answers/detail/a_id/719367/page/1 According to this knowledgebase article: F21 is Output Phase Loss, which means that the current in one or more phases has been lost or remains below the threshold set in Parameter 445 [Out PhaseLossLvl] for one second. Decreasing the threshold in Parameter 445 [Out PhaseLossLvl] will make the drive less sensitive to tripping. This is usually necessary when the motor is smaller than the drive rating. Check for an open output contactor or any loss of connection between the drive and motor. However, I'm pretty sure that the value in P445 is NOT in units of current; otherwise, why would the default value be 200? I don't think it's percentage either. However, no where I can I find a good definition or method to set this value properly. To activate output phase loss, you need to set parameter 444 to something that is useful to you (either alarm or fault). Default setting is ignore. You should be able to view the knowledgebase article; it is tagged as being for everyone. \\n </s> |
<s>[INST] Kinetix 5100 to DeltaV (PK Controller) explicit messaging Hi all, We are working with a Kinetix 5100 drive which we want to connect to a DeltaV system using a PK controller through Ethernet IP, the drive will be used to control the speed of a pump for a bag and bottle filler, previously in a past project it was used the Kinetix 300 but since it'll be discontinued, we were told to use Kinetix 5100 instead, Kinetix 5100 manual indicates that we can use same explicit class 3 messaging like Kinetix 300 to communicate with DeltaV but the Input and Output assembly data shown in the manual says that is intended to use only with IO mode (Class 1 Ethernet/IP connection). Does anyone know how or where to find the Input and Output assembly data when using Class 3 explicit messaging? Any help would be appreciated. Thanks in advance Edgar V [/INST] Hello, you can perform Class 3 Messaging to an external device only. The I/O assemblies are only available using a Logix based controller as you mention. You can use the example MicroLogix 1400 or Micro800 Class 3 messaging examples on the SampleCode Library (or available from your local Rockwell Automation Tech Specialist or distributor). These examples show how you can get some meaningful (but not as rich as the I/O assemblies) information passed between the controller and drive. Hope that helps. \\n </s> |
<s>[INST] PF755 - CIP motion and I/O cinfiguration Summary: Problem with adding PF755 drive in ControlLogix controller organizerHi everyone, I can't get rid of fault state of PF755 in I/O configuration. I try to add drive as CIP motion (PowerFlex 755-EENET-CM), I create an axis and connect it to the drive, but there is a fault of drive definition. I receive a message in drive's connection tab: Module Fault: 16 [/INST] Can you show us an image of the GENERAL tab? Also show us an image of the Module Definition when you click the CHANGE button on the General tab. \\n </s> |
<s>[INST] Can I control an MPL-330P servo motor using an old 1394-AM03 drive? I would like to install an MPL-330P motor on a few lines without upgrading the drive, as this would require a major rework. [/INST] JLawler, could be important to know which 1394 Controller you have, not just the axis module.... Anyway, take a look to the following technote: Aid 57030 edit: take also a look to the attached screenshot, taken from an old Motion Selection Guide... Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] can multiple 753 safe torque-off modules be connected and maintain the safety function Has anyone cascaded multiple 753 drives thru the 20-750-s safe torque off module. Can this be done ? I have a customer who would like to use 1 safety output to control 16- 753 drives ,he wants to maintain a cat3 rating. Thanks John [/INST] You should be able to parallel the signal from a safety relay output to the 20-750-S modules. The returns would also then be tied together as well. TJ McDermott \\n </s> |
<s>[INST] 5700 Motor cable plugs Hello, We recently installed some Kinetic 5700 series, D057 servo's. Installation and commissioning went well but after a few days of running we had a fault which turned out to have been caused by a motor plug coming out of the socket. Apparently this is a known issue and amplifiers which are of the B series rather than A series have used a different socket so that the sides of the plug are now meant to be gripped. But we have used the new connection kit and can't see any physical difference between the old and new motor plugs, you would of expected to see a raised dimple on the side of the plug to allow the new socket to grip the plug better. The old connection kit part number is 2198-KITCON-D057 and the new connection kit part number is -L. I have read the only document I can find regarding the difference between the two connection kits (Rockwell Automation Publication KNX-TD003H-EN-P - October 2021) but it only specifies which connection kit should be used for which series of amplifier (page 41). I am starting to think that the wrong plug has been put in the new connection kit (-L) that we have just received. Can anyone confirm if there is any difference between the plugs or not? Thanks, [/INST] Hi Luke did you check the Rockwell knowledge base article QA36257 ? \\n </s> |
<s>[INST] APR fault after download new program Summary: APR fault , waiting for group,i have a project same as did before , all configration is same as first one,but when i downloaded the program , all the axis state are waiting for group power flex 527, some is configing, some kinetix 5700 is APR fault ,it happened before on other porject and i cleared them very easily use clear fault in group, but this time can not. and try many way to solve: 1. recycle power many times 2.clear faults both in group and axis , failured, says the group is not in sync state. 3. checked the encoder wiring. 4.checked firmware and ip address. this is i first time to ask question here , is anyone can help ? [/INST] The fault image is telling you a lot of information. There is something wrong with this servo motor's feedback device. Did you configure the axis with one type of motor but actually connect a different motor? SOMETHING is different from your previous project to this one. Focus on the motor / feedback device and be sure your axis is configured to use what is actually out on the machine. Either correct your axis definition or replace the servo motor because it is defective. \\n </s> |
<s>[INST] PowerFlex DC Fram D 690V Document Hi, I see PF DC power rating has extension,but where can see the fram D document?Please help,thank's. [/INST] Can you post a little more information on what you're asking? \\n </s> |
<s>[INST] PF755 in Torque Mode Unwind App Does anyone have experience with an ac drive running in torque mode? What will drive do when it is used in torque-mode running an unwind application? I have an application that is applying constant tension in forward mode but occasionally the product unwinds and the drive will be forced in reverse. The tension is operator's selectable and the drive is running in Min Speed/Torque SLAT-3. The maximum speed is clamped thru SLAT-3. What do I expect from the drive when I force it in reverse like un-winding applications? Although I am using PF755 Ethernet, the PF700 should behave the same. Any feedback will be appreciated. [/INST] Noor Shah, did you get any support from your local Rockwell distributor on this? \\n </s> |
<s>[INST] RSLogix 5000 with Customized Servo Motor I might be pressing a hot button here, but is it possible to configure a user defined servo motor to use in RSLogix 5000? Thanks. [/INST] lendyck, a user cannot add his own a custom motor inside RS5000... you need to request your local RA representative to have the custom profile created for you, giving them all the datas about the motors. Anyway this procedure should be approved from RA before they start with analysis and profile definition... so I think it isn't quick to get... May also try to ask if there is already a profile created for your motor... take a look to the following thread: LINK Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] FactoryTalk Optix WebPresentationEngine. Currently, I am testing Optix on my laptop and wanted to access my runtime via web client on the same laptop that the runtime is running on. I could not find any example and read through what I did find on the Optix support website. I also looked on Rockwell's YouTube channel. Here is a screenshot of my current configuration. When I type the IP address in, I get This site can't be reached message. What am I missing? Dynamic variables polling time: 0000:00:00.100, Protocol: https, IP Address: 127.0.0.1, Port: 8443. [/INST] If you click on Advance it should take you to the project. Otherwise you should be able to skip the warning for now by switching the protocol to http instead of https.\n </s> |
<s>[INST] PowerFlex drives over ControlNet? I know PowerFlex runs over Ethernet. What about ControlNet? (And if it does, any problems to watch for?) I've got a customer that has a nearly religious conviction against ehternet as a control protocol... ;) [/INST] Yes, the powerflex dives have an adapter 20-comm-c and 22-comm-c depending on what drive you have to operate on controlnet. In my opinion it is just as easy as ethernet to setup. Just have to schedule the network once configured. \\n </s> |
<s>[INST] PF753 - can I use units other than Hz or RPM? Summary: Web handling application - I would like to set units to feet per minute (web speed)Hi, I am considering using a PowerFlex 753 drive for a web handling application. I see that parameter 300 [Speed Units] allows me to select either Hz or RPM for the units to be used for all speed related parameters. The units that I would really prefer would be my web speed in feet per minute (FPM). This equals the surface speed of my driven roll. I can use my gear ratio and roll diameter to calculate the scale factor required to convert motor RPM to web speed in FPM, but I don't see if/how I can enter this into the PF753 so that it would allow me to enter my speed setpoint in FPM and display my actual speed in FPM. If anyone can tell me if/how I can do this, I would greatly appreciate it. Thanks in advance, Paul [/INST] You don't do it to the drive specifically - you change the process screen of the HIM. http://literature.rockwellautomation.com/idc/groups/literature/documents/um/20him-um001_-en-p.pdf See page 37 of the user manual at the link above. \\n </s> |
<s>[INST] Drives AOP v2.01 I received a pdf concerning RSLogix v17 that advertised the ability to create drives while online. I saw it well before v17 was released. I was surprised to learn that creating a drive while online wasn't possible once I upgraded to v17. Going back to look at the pdf I noticed that it did say that Drives AOP v2.01 was required. When will it be released? [/INST] Drives AOP v2.01 is targeted January 2009 and will be downloadable from the following links when available: http://www.ab.com/support/abdrives/webupdate/software.html http://support.rockwellautomation.com/controlflash/LogixProfiler.asp - fuzzy logic \\n </s> |
<s>[INST] Powerflex 755 Electricity Shutdown Parameter Problem Hello Everyone, I have a strange problem on Powerflex 755. We use 15kW 30 A drive and do incremental position control. When we download parameters to the drive, the motor works fine but after we cut off the power and start the drive, the motor vibrates and runs loudly. After we upload backup file again and the motor starts fine again and after we cut off the power and start the drive, the motor vibrates and runs loudly again. There is a loop. Same thing for 20-HIM-A6. We can't see any parameter after cut off power. When we upload backup file again we can see parameters. How can we fix this problem? Can you help me? [/INST] Hello Emre, Do you have a Logix PLC communicating to this VFD via Ethernet? If so, do you have Automatic Device Configuration (ADC) enabled? I ask because if you are connected via Ethernet to a Logix processor and have ADC enabled, the PLC memory card is storing a copy of the VFD programming. So any VFD programming changes that you do AT THE DRIVE with the HIM module must then be uploaded into the PLC program. If not, then whenever control power is cycled to the VFD, the ADC system will see that the programming in the VFD is different from that in its memory and restore the programming from its memory back into the VFD, wiping out any changes you may have made locally using the HIM. \\n </s> |
<s>[INST] DriveTools SP Full Version Summary: DriveTools SP is installing the lite version instead of the full version After two days on the support site and one call to tech support, I am still unable to install a full version of DriveTools SP (DriveExecutive and DriveObserver) on my computer. I am installing version 3.01 and upgrading it using the DriveTools 5.06.03 patch. According to tech support, DriveTools SP is now freeware. EDIT: removed at the request of the drives group. This serial number backdoor is not intended to work as a full version work-around. I'm installing on a Lenovo Thinkpad T530 running Windows 7 Pro SP1. After repairing a problem with the install files (an INI file decompresses to the wrong subdirectory unless installing from a CDROM). DriveTools 3.01 installs successfully as the Lite version. Is there a more recent, full version available for download on the Rockwell website (I haven’t been able to find it)? What do I need to do to install the full version? Is there an alternative to the trending package (DriveObserver) that comes with DriveTools SP? [/INST] According to Rockwell's website, DriveExplorer is discontinued. However, DriveExecutive Full Edition is still available from Rockwell's distributors. http://raise.rockwellautomation.com/RAConfig/config.asp?cmd=edit&CID=2ABAF46255EB400C8839FDAF039287E8 As of a couple minutes ago: 9303-4DTE01ENE 1 Drive Executive full for Win 98/ME/NT/2000/XP $ 465.00 I have yet to try running it on Win7, however, if it is a 32-bit OS you'll probably be fine. Contact you local Allen-Bradley distributor and inquire about the above listed Catalog Number. Sometimes Rockwell's Divisions are really divided... \\n </s> |
<s>[INST] Connect to PF drive through a tunnelling Router Summary: How do I connect to a drive through a tunneling router that changes IP I have an Ethernet IP network with a PLC and Drive on a subnet of 10.179.88.xxx. I have to support this remotely and I'm using a secure router that tunnels traffic through a different IP address. My PLC is on the local network as 10.179.88.20, but when I connect remotely, I set up RSLinx to 10.2.23.20 and the router redirects the traffic to the PLC correctly. I can see my drive in linx at (10.2.23.40) but it's actually at 10.179.88.40. This works great for going online with PLC, but when I connect to the drive, it tells me that it mismatches with the project since the IP in the project is different than the one I'm connecting with. Any ideas on how to connect? [/INST] What software are you trying to connect to the drive with? What type of communication adapter is the drive using for integration? Are you using a licensed copy of RSLinx Classic? What type of RSLinx driver are you using? If using DriveExecutive and trying to connect to a 20-COMM-E adapte with RSLinx Classic Lite (non-licensed)r, I'd try a different EtherNet/IP driver (than the one used to connect to the CPU controller); if this fails try using an Ethernet type (not EtherNet/IP) RSLinx driiver and enter the drive's 20-COMM-E IP address manually. If you are running a licensed copy of RSLinx then you could try using a Remote Devices via RSLinx Gateway RSLinx driver; you will have to enter the drive's communication adapter IP address in Server’s IP Address or Hostname location when configuring this type of driver. \\n </s> |
<s>[INST] Question on PF40 and PF70 Accel2 and Decel2 Hello everyone, I have a question about the PF70's Accel 2 and Decel 2 parameter. From what I've found in the User Manual. The only way to use decel 2 on a PF70 is to have a Digital Input parameter (361 to 366) set to value 20 (for Accel 2 & Decel 2) or 22 ( for Decel 2 only). I could also be using the DPI but in this case that's not an option. We want to use the Digital Inputs. In comparison, when using the PF40 with different preset speeds. Preset speed 0, 1, 4 and 5 will use accel 1 and decel 1. While preset speeds 2, 3, 6 and 7 will use accel 2 and decel 2. Does the PF70 work the same way or is my initial thought of having to use another Dig. In correct? [/INST] Digital input can only be assigned to one function at a time so you need a digital input to select value 20 (for Accel 2 & Decel 2) or 22 ( for Decel 2 only). The Speed selection would be a different digital input \\n </s> |
<s>[INST] K5700 with MPM PLe Safe Speed Application Hi , I'm wondering if somebody has experience or can validate this Safety application : My customer would like to use a MPM motor ( Sin/Cos Hyperface feedback ) with an Kinetix5700-ERS4 drive .The Safety requirements is PLe . Is this possible to wire the Sin/Cos Motor feedback on the MF ( DSL ) port via 2198-H2DCK , and the 842-HR ( Sin/Cos Second channel ) on the UFB port of the K5700 ? Is it categorized safe ? the 2198-RM001 is only mentionning VP motors in PLe ... but MP Motor can achieve PLd using H2DCK converter ... Anybody can help ;-) [/INST] Hello Stephane The MPM does not support a safety encoder. what you are trying to do will require a lot of effort for an uncertain result, because you will have to validate this architecture via SISTEMA software. So to simplify the integration I strongly encourage you to consider the VP series motors solution that supports Safety Encoder, in association with a second encoder you will achieve Ple without much effort for you or your customer. Best regards Vincent \\n </s> |
<s>[INST] Virtual Torque Sensor Hello Good Morning, I was working on predictive maintenance for Kinetix 5700 servo drives using the add on feature virtual torque sensor for jams or mechanical system issues including gear tooth fracture or breakage in gearboxes, bearing damages, damaged coupling, damaged balls crews, and broken blades or wore blades in rotary knifes etc. There was an AOI developed by Rockwell to detect any disturbances in the profile. I am using the Torque estimate for the detection as said by the document. My question is I am doing a test on the Kinetix 5700 on a motion drive using a single axis & I configured for velocity loop. There is not much information about the use of AOI. For example, My test procedure is as follows. At First I wanted to record or save the good profile & then stop it then loosen the couplings so that the AOI will detect the disturbance based on the first profile. But I was not able to detect the disturbance. I am looking for some information on the AOI I am attaching the AOI_LoadConditionMonitoring_v2 pdf for the reference of the AOI. There is not much information on the knowledge base as well regarding the test procedure or about the AOI Thank you [/INST] Sai, Never seen this AOI before but the picture from the pdf graphical tells me what I need to know, During the yellow highlighted period, the monitored value is above min. and below max.. thus normal. At the end of the yellow highlight period, the monitored value dips below the min. value and this starts a timer If the monitor value remains low and the timer completes, it sets a Boolean to indicate a disturbance is detected. The trick is to have a measured value that can reliably indicate there is a problem. I'm guessing a loose connection might show up as a period of no torque, or high positioning error, or maybe non-linear response. but it might be too short to see or otherwise masked by the closed-loop algorithm. \\n </s> |
<s>[INST] Is there any easy way to move all coils one step back and keep NO contact in the same place. Total 547 rugs. Each contsins an NO contact and a coil. I want to move all coils one step back and keep NO contact same place.Is there any easy way to make it fast other that cut paste each rugs coil? Rtu register not have 10th bit address.so all coils move one step back.I mean coil with 10th bit delete and place coil with 11th bit in place of deleted one and so on. [/INST] Many years ago I used to generate PLC5 ladder from a database into text files which I'd then import into RSLogix software for download. If this functionality is still available, you could possibly export your ladder as text, manipulate it as required, then import again. Excel may be the easiest tool for the manipulation if you can break each rung up, adjust the relevant part (the address after the OTE instruction?) and reconstitute it again.\n </s> |
<s>[INST] PowerFlex DC, Upload to PC How can I Upload drive Parameters/Configuration to my PC, I have available (RS Logix 5000, Drive executive lite, RS Linx classic lite). I have no serial port on PC, I'm using USB to Serial adaptor and null modem adaptor to communicate with Controller(LOGIX 5563). There are 2 PowerFlex DC drives connected to Controlnet module(1756-CNB) on controller. Ethernet through ControlNet?DPI directly to drive? Have no cable availableThrough backplane of controller via serial port? already connected [/INST] You may use the RSLogix5000, through the feature named Premier Drive Integration. When you're connected online to the Controller, you may go to the Controlnet PF DC and communicate with the drive. Involved in this are the versions of RSLogix 5000, PF DC AOP, etc... If you still cannot realize it, please post your RSLogix 5000 software, Drive Executive and RSLinx installed software versions and somebody will give other suggestions. - fuzzy logic \\n </s> |
<s>[INST] Motors failing. Does anyone know why motors are failing? I have two motors attached to a flex 4. One motor is attached as T1, T2, T3 (forward motion) and the other motor is attached as T1, T3, T2(reverse). The motors that are running in reverse keep failing. When the motors were attached to a regular contactor, the motors ran fine (no issues). As soon as they were attached to the Flex 4, the motors began to fail. Any ideas? [/INST] If both motors are attached to the same drive... you have so much artifact,ringing,mismatch flying back and forth your lucky the whole room isnt full of smoke. are the motors inverter rated at least? \\n </s> |
<s>[INST] SMC Flex Soft Start control voltage My employer is migrating to 24VDC for control & I/O. Is it possible to change the controller from 120VAC to 24VDC without replacing the entire starter? 201-480A rating. [/INST] Hi Perry, it should be possible, as per the following technote: QA27072 Please note the document indicates to look at Appendix C of the User Manual, but it is Appendix A in the latest publication's release. I'm going to update the technote. fuzzy logic Please don't forget to LIKE and highlight the decisive answer: REPLY > Make Best Answer \\n </s> |
<s>[INST] more curent on PowerFlex 70EC hi all! I've a PowerFlex 70EC for 37 kw motor, with NP 65A, the motor is working in the limit, I wish to try to put 2 amps more, the parameters to change are 42, 47 and 48? thanks [/INST] nan \\n </s> |
<s>[INST] Suggestion for a servo motor required to connect to rockwell servo Summary: Selection of a suitable servo motorHi, I want to connect a suitable Rockwell servo motor to a Rockwell drive system. The PLC used by my customer is AB PLC L36ERM. I want to connect a suitable Rockwell servo motor to this. The torque requirements are very less. The mechanicals comprise of a linear timing belt and carriage. At present we use a stepper motor with a max holding torque of 101 Ncm. Anything more than this would also be suitable. Could anyone suggest which motor would be suitable? thanks arun [/INST] You've given very few facts with which to size a servo system. You've only given us a processor model, so you could use a K350 or a K5500 economically. But you've not said anything about voltage so no one could recommend more than that. You've given only torque, you've said nothing about the necessary speed. You've told us the type of mechanical setup, but nothing at all about reduction ratios, load, inertia, friction, cycle time, etc. You need to give us a LOT more information if you want useful recommendations from us. I suggest you use Rockwell's Motion Analyzer: https://motionanalyzer.rockwellautomation.com/ \\n </s> |
<s>[INST] Powerflex 525 VFD Summary: Powerflex 525: Not showing ADC optionI have 10 powerflex 525 module in my program and all of them have ADC option except for one VFD. I compared all setting with the one which has this option and everything looks same, Anyone can tell me what am I doing wrong here? [/INST] In the image you shared, we can see two different drive tabs. The one labeled VFD80205 shows firmware 5.002. The one labeled VFD80305 shows firmware version 5.001. Since you can't see the ADC branch for that drive, the first thing I'd try is flashing VFD80305 up to firmware 5.002 to see if that fixes the problem. \\n </s> |