text
stringlengths 38
9.81k
|
---|
<s>[INST] Powerflex 755 No converters port 11 please help Summary: HIM module is showing this message can someone elaborate pleasePowerflex 755 drive giving me No converters in port 11 message on HIM someone please elaborate. [/INST] Did the converter section on this large drive get serviced or replaced? That message means there's something wrong with the fiber optic connections. Are you also getting 11142, 11242, 11342 errors? See page 347 of the 750-PM001 manual. Also see the re-rate section in the troubleshooting chapter, page 353. \\n </s> |
<s>[INST] Powerflex 700 memory loss Summary: looses settings when power is lostPowerflex 700 looses all of its settings when power is lost. How is this fixed? [/INST] Either the drive main control board is completely damaged, or you have a DeviceNet system configured to perform Automatic Device Replace. Is there a network connection to the drive ? \\n </s> |
<s>[INST] 755 CIP motion Summary: Using Powerflex 755 drives as CIP Integrated motion drives Has anyone had any experience using a 755 drive, 20-750-UFB-1 card and a SSI encoder? I cannot get the Logix PLC to configure the drive in a usable way. [/INST] See your other post; I answered there. \\n </s> |
<s>[INST] PF525 utilizing a Line Reactor I'm curious if it's possible (and safe) to group multiple PF525 drives on a single line reactor. I am designing a panel that contains fourteen (14) 10hp drives and ideally, I don't want to have a line reactor for each individual drive. Can I group 2-3 drives per line reactor, and if so, how do I go about sizing the correct line reactor? Is it as simple as combining the FLA of the 2-3 drives for the individual line reactor or is there some other calculation to utilize? [/INST] Hello Mark, Please review QA13774 All of the relevant information is available through the technote. Thanks \\n </s> |
<s>[INST] PF 700 Minumum Load Does anyone know what the minimum load is that you can put on a particular drive? For example, where in the documentation does it tell me that I can/can't run a 50A load on a 100A rated drive. [/INST] The best performance will always be when the drive has the same current rating as the motor.Matching drives and motors closely also removes the need to adjust the Current Limit parameter, which is normally related to drive rated amps. As a general rule, the drive rated amps can be up to 200% (2 times) the FLA of the motor. If the mismatch is more than 200%, the drive may not be able to control output current correctly. This is due to the internal CT's only measuring current over a small amount of their overall range. [Reference Aid 51640] Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] MRP - Position Select Hi, I am trying to use MRP instruction. I don't see any differences between Actual or Command. I observe the same behavior in both cases. If you have information about this topic please share with me. Thank you. [/INST] Hello Gulec There is a very good explanation in the Help in Studio 5000. for that you have 2 ways. Select your MRP instruction in your ladder code and hit F1 or got to the Help tab and select Instruction help and search for MRP. What is you need for the MRP ? regards \\n </s> |
<s>[INST] How to Programm kinetix 300 with RSLogix 5000 How do I have du Programm a Kinetix 300 Drive with RSLogix 5000? I use a MPL-A310 Servo and want to use my Kinetix with a Logix5561. How do I have to configure the axis in RSLogix for Ethernet/IP? I am new to Rockwell and Allen-Bradley I only used Siemens SIMATIC device for projects. I only want to get into this software and my first step is only to control thios one axis. [/INST] There are some sample programs for K300 with Logix 5000. Go to this page: http://samplecode.rockwellautomation.com/idc/groups/public/documents/webassets/sc_home_page.hcst And select MOTION CONTROL, INTEGRATED for the product family, and then OTHER for the product. There are a number of K300 and Logix 5000 examples. \\n </s> |
<s>[INST] Powerflex70/700 Current Lmt Gain Par 149 action? Am having problems with an occasional overcurrent situation and playing with settings 148,149. For Par 148.Some manuals talk of this being a percentage of drive rating.Yet user manual states units as amps.So is this to be entered directly as amps to current limit at OR as amps percentage of drive rating. For Par 149.Can find no information in manuals as how to use this.Or exactly what action it has on current limiting. Trying to take care of very occasional overcurrent situation.With default 250 in Par 149 and motor FLC entered in Par 148 I am still getting occasional trips.Normally system is running 10-15% below FLC. [/INST] Very old topic, but I guess it would be interesting for others searching for a similar question to know that another Forum has the SAME thread which got instead some replies. http://www.plctalk.net/qanda/showthread.php?t=55918 - fuzzy logic In order to enhance Forum's contributors reputation, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] Error code on the MCCP instruction Summary: Error code 31 produced on the MCCP instruction Dear all Sometimes as the instruction MCCP is engaged,error code 31 is produced on the MCCP motion structure control word. I check in the user manual says cam profile is still in use. But in my program Pcam instruction is all disabled. Anyone met that situation? [/INST] I am having a similar problem with error code 31... Did you ever find resolution to this issue? thanks, Josh Williams \\n </s> |
<s>[INST] Disconnecting Feedback & Power Cables on Kinetix 6500 Drive Is it okay to disconnect feedback and power cables on the 6500 Drive while the drive is powered on but inhibited or safe torque off state? [/INST] Rockwell does not recommend it, but it is often done while troubleshooting problems. You will cause a number of obvious faults (such as loss of feedback). \\n </s> |
<s>[INST] SmartGuard 600 Summary: SmartGuard 600 Does anyone know how to tell the drive link for communication via USB port, to access the SmartGuad 600? [/INST] nan \\n </s> |
<s>[INST] PF525 with Horner XL4 Modbus/RTU Hi, Has anyone used a Horner XL4 Modbus/RTU to a PF525? I've tried but keep getting errors. Thanks, Thomas [/INST] I figured it out, for the variable's you need to select 32bit access and swap words on 32bit data. \\n </s> |
<s>[INST] 1394 series B amplifiers on Sercos Kinetix 1394C-SJT22-D System module When Configuring the Axis under the Properties Tab Drive/Motor The Amplifier Catalog Number of the module I am using is not available from the Pulldown menu. All Available Module are 1394C-XXXX, I am using older servo amplifiers (Series B) and My part [/INST] Just a question to clarify.... did you try to select as Amplifier the 1394C-xxxx instead of none ? - fuzzy logic \\n </s> |
<s>[INST] FactoryTalk Network Manager Hi Guys, who knows about the new Software FactoryTalk Network Manager? I am trying to get the connection with a stratix 5700 but no success. I think i do not know how to really configure the network Manager so that it sees the switch. Now just for the test i have a LAN cable from switch (any port) to the host PC where Network Manager is installed; the IP of the PC is in the same range like the switch. i can not find where to add a new topic/post, that is why i posted this in here, sorry. Any ideas? thank you [/INST] Yes, the .alarm and .faulted bits come from the PF40. You are correct; from this logic, ANY alarm or ANY fault will turn on bit 31. The PF40 does not offer a lot of diagnostics. The parameter list offers parameters 7, 8, and 9 as Fault Code 1, 2 and 3, the three most recent faults. You could use MSG instructions to get the code stored in those three parameters. You would then need to create a look-up table based on data you can find here: https://literature.rockwellautomation.com/idc/groups/literature/documents/um/22b-um001_-en-e.pdf Refer to section 4-3, page 95 of the PDF above. There's nothing wrong with the code. The drive is a simple drive. If you want a lot of useful diagnostics, a PF750 will give much more (at higher cost). This code tells you the drive faulted. You'd have to go to the drive, look at the fault code displayed on the LED display, and then look it up in the user manual. \\n </s> |
<s>[INST] An attempt to Reset Ownership from the Safety tab of the Kinetix 5700/5500 Module properties was not successful, it ended with error message: Failed to perform required operation.Unable to perform service due to current module mode. [/INST] </s> |
<s>[INST] Drive Executive Lite download disabled There must be a simple solution regarding the Drive Executive Lite software download icon and menu item being disabled. When originally setting up the drives did not see this, now doing startup it is a problem. Using 50 flex 40 drives communicating via Controlnet comm modules. Only indicator displayed is the enabled (not running). We also have hardwire controls when the PLC comm is lost. Thanks in advance Gary [/INST] Hi Gary, Where are you seeing a Drive Executive Lite software download icon and menu item? \\n </s> |
<s>[INST] Optix: how can i call a bit of int at active of led (of base control)? [/INST] Use the Scalar to Bit Array Converter\n </s> |
<s>[INST] Keep Motor Warm with DC Brake Function Summary: How to setup PF70EC DC Brake to keep motor warm Hi All, I have setup a Powerflex 70EC VFD to DC Brake indefinitely when the VFD is not running, and while it appears I have done everything correctly, it does not appear to engage. I'm using Digital Input 6 set to Stop Mode B which is set to DC brake after a 10 second delay. When the drive is on and not running there is 24V on Digital In6 and nothing is suggesting that it's working. The only thing I can think of right now is that maybe I can not engage a stop command after the drive is not running - Please comment. Here are my parameters: 156 Stop Mode B = DC Brake 158 DC Brake Level = 1 Amp 366 Digital In6 = Stop Mode B 384 Digital Out2 = Run 386 Dig Out2 OnTime = 10 Seconds Here is the IO wiring: [/INST] I really don't think permanent DC braking is a solution for keeping the motor warm; excessive DC braking could and most likely will deteriorate your AC motor's windings insulation. Refer to Page 197 of http://literature.rockwellautomation.com/idc/groups/literature/documents/rm/pflex-rm001_-en-e.pdf for the detailed description of the PF 70-700 DC Brake functionality. If you are trying to avoid condensation you might need to deploy space heaters or choose a totally enclosed type of motor (if there are no water vapors within the windings there will be no condensation!). \\n </s> |
<s>[INST] Drive executive and Kinetics 6500 over ethernet Summary: Drive executive and Kinetics 6500 over ethernet communucaitionDoes Drive executive work with Kinetics 6500 servo drives over ethernet with RSLinx? [/INST] I just opened it and tried to create a new file - K6500 is not an option. While you could access a PF755 drive which is controlled via CIP motion from a logix processor, any changes you could make to parameters are wiped out at the next power cycle. Drive Executive is not intended to work well with CIP motion hardware. \\n </s> |
<s>[INST] PROBLEM WITH INVERTER POWERFLEX 40 I HAVE A PROBLEM WITH SIX INVERTERS POWERFLEX 40, THE INVERTERS SWITCHED OFF AND DID NOT SWITCHED ON NEVER AGAIN, AND I NEED TO REPAIR PLEASE SOMEBODY CAN HELP ME TO IDENTIFY DE PROBLEM [/INST] Looks like the switch mode power supply has gone....... see tech note 34911 on the knowledge base \\n </s> |
<s>[INST] Motion Database Hello, I use rslogix 5000 V 18.00 but I discovered that now I can't change any motor or drive in the project as the motion database is no longer available. How can I solve this problem? thank you very much [/INST] Starting in V18 Rockwell changed how the Motion database is handled. You used to be able to goto Tools-Options, select Motion and point the database to another database. Now you have to use a new tool available here: http://rockwellautomation.custhelp.com/app/answers/detail/a_id/116617/kw/motion%20database/r_id/113025 This should only effect you if this is a custom motor.The normal V18 database should be located at C:\Program Files\Rockwell Software\RSLogix 5000\ENU\v18\Bin\Motion.db You could try a couple of things, try the import tool above to see if it can see the database, replace the database using a known good database from another computer, or you may have to reinstall Logix to correct the corrupted database. \\n </s> |
<s>[INST] ControlLogix MSG instructions I need to query a bunch of drive parameters using ControlLogix MSG instructions. Must I issue one message at a time and wait for it's .DN bit before executing the next MSG instruction, or can I fire them all off at once and wait for .DN from all of them? Mike [/INST] Mike, firing many messages together could generate some problems... it is better to manage them... Take a look to the following technotes... Aid 39998Aid 21193 Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Need documents of Maxitron 8500 SCL As the title, Is anyone can provide me the documents(Manuals,Pictures,Spare parts list) of Maxitron 8500 SCL? Appreciate it. [/INST] Was that a Reliance Electric product ? If so, it's old enough that I have never seen one. Can you tell us more about this device ? I don't know if Baldor took over responsibility for obsolete parts and repair when they bought the Reliance Electric motors and drives business a few years ago. \\n </s> |
<s>[INST] Memory module in Kinetix 300 and Kinetix 350 Hello, I read in the manuals the following: [/INST] Hello, I have a doubt about the following issues: 1-The parameters loaded automatically to Kinetix 350 from RS Logix 5000, What is the function of the memory module in Kinetix 350 in this case? 2-Is the function of the memory module in Kinetix 300 is to save the parameters only? 3-Can we Run Kinetix 300 or Kinetix 350 without memory module? 4-If we replace the damaged Kinetix 300 or Kinetix 350 with a new one with the same type and put the old memory modules in them, To run the normal operation need to perform any thing in the new drives? Please explain Thank you in advance. \\n </s> |
<s>[INST] Powerflex 700s VFD Running but Motor is NOT Summary: VFD shows running but motor not turningWhen the VFD is issued a run command it goes into run mode, the HIM module shows increasing DC bus and Output Current, but the RPM is bouncing in the + and - range, the direction is also bouncing from FWD and REV. It seems that it is trying to start the motor, but the motor stays still, and the VFD does not go into fault. Looking to find out what is causing this. The VFD is 600VAC, 208A and was installed in 2006. [/INST] Does this motor have an encoder on it for full flux vector control? Did anyone touch the wiring of this system between the time it did work properly and now? \\n </s> |
<s>[INST] K5700 Drives Inverter Overtemp Fault We have a vertical load application with two axes sharing the load using the same K5700. For some reason when we move the axes up or down, we will intermittently get an Inverter Overtemperature FL Fault. So far, we haven't been able to nail down a root cause. It doesn't seem like the torque is causing this problem because we have tried with varying weights and torques, and it doesn't seem like velocity or acceleration are the main factors either because we have tried playing with the speeds. We trend the inverter temp and notice that this alarm occurs when the inverter temp hits 155.6 degrees C. Does anyone have any good ideas as to why this fault might be occurring in our application? [/INST] EDIT: added proper numbered list to questions -FL Hello Joe. Based on the little information's that you give us it is not easy to identify the issue you have. Some questions: is it a new installation that you are commissioning or something new on an old system? you said that the dynamic generates the over temp fault. what is the torque value before the fault occurs... are you close to 100% or above for how long , does the 2 motors shows approximately the same torque level (how did you manage the load sharing ? ) have you check that the break works correctly? stupid question (but I have seen it) check if the motors are not working against each other did you monitor the drive capacity tag? could you provide the Drive and motors ref , to see if they can match? do you have a current and position error trend ? Regards \\n </s> |
<s>[INST] PowerFlex 40P Downgrade Summary: downgrade from 3.01 to 2.01Hello, we want to downgrade a drive PowerFlex 40P from Firmware 3.01 to 2.01. Our machines are using drives with 2.01. Last Time a 40P was defect we installed a drive with 3.01. After that we had massive problems in cause of the mismatch from firmware. We tried to disable Keying-> didn't work. We are using ControlFlash. Is it possible to downgrade? [/INST] According to this knowledgebase article: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/42454/page/1 Users like us cannot change the firmware of Powerflex 40P drives. You have to send the drive back to Rockwell to have it changed, or hire Rockwell to come on site to do it for you. Sorry, you're out of luck there. You're going to have to figure out ways around the changes caused by the firmware. What processor is choking on the changed firmware? \\n </s> |
<s>[INST] Kinetix 6000 drive fault Summary: Drive faulted not sure on what the bits mean in PLCWe had an MDF-SB1304F-QK82B-S motor fail on us. We replaced it and all is good. What I was wondering is that we had a drive fault and in the PLC software (RSLogix 5000 V.20) it showed a Physical Axis Fault. We found but 14 and 31 on in the AxisServo.DriveFault. Is there a table that shows what all these bits mean. I believe I found one in the help file but it shows 28-31 as reserved. Is there a table which shows which each bit means Thanks in advance [/INST] Rockwell publication MOTION-UM001F-EN-P, pg 212 http://literature.rockwellautomation.com/idc/groups/literature/documents/um/motion-um001_-en-p.pdf Its easier to troubleshoot the K6000 using the 7 segment display on the front of the drive, what was the error code that showed there? \\n </s> |
<s>[INST] PF755 Summary: Drive Parameter Hi, Anyone knows what parameter to change in the drive when using a brake resistor? Any safety precaution about wiring will be much appreciated. Thanks you, [/INST] P372 and P373. Refer to http://literature.rockwellautomation.com/idc/groups/literature/documents/rm/750-rm002_-en-p.pdf Page 36 and http://literature.rockwellautomation.com/idc/groups/literature/documents/pm/750-pm001_-en-p.pdf Page 90. \\n </s> |
<s>[INST] Fault NODE FLT 06…LOST CTRL CONN in Kinetix 6500 Good Morning, This problem happened to me twice, the first time I just thought it was a coincidence, but now it's the second time I confirmed that this error occurs every time I'm connected to the PLC with my laptop, I'm working and at any moment 1 or 2 servo drives fail and this originally caused the production line to stop, with that I began to suspect and stayed connected, the machine started up again and after several minutes the same thing happened again, so I had to disconnect. It should be noted that with that same laptop I connect to other machines and I don't have those problems. The machine has a Rack with 2 1757-L72 V19 processors and both manage 120 Kinetix 6500 servo drives. And failures can happen in any servo drive, both PLC 1 or PLC 2. Thank you very much for your support. [/INST] QA20825 Kinetix CIP Motion Drive: NODE FLT 06 LOST CTRL CONN Faults \\n </s> |
<s>[INST] Logix designer Compare tool, AOI logics not opening. I cannot open AOI logic in compate tool. I clicked several times on it but not open. My both projects AOI protected with a security key file with extention .sk, but I go to tools, security section, select. Sk file and un protect project AOI in rs logix. Why I cannot open and see changes in the AOI logics? [/INST] Protected AOI can be compared, and double-clicking on the Logic icon should open the Ladder Content window at the top. If the SK.dat file is missing, it is indicated near the Routine name in the compared content, and clicking on the Logic icon still opens a window on the top, with some encryption information and timestamp. As you wrote, your logic has been unprotected, so the comparison should basically work like all other routines. I suggest to check the Compare Tool version, and try a Repair or just an update of the tool if a newer version is available (maybe it's an old version). About the other message you got about memory, it usually happens when trying to compare large arrays or very complex file. As you mentioned it happens during .pdf export, it may also be related to corrupt or old Compare Tool version.\n </s> |
<s>[INST] feedback data loss factory limit kinetix 350 Summary: Fault 45Hi everyone, here's the detail : Kinetix 350 (2097-V33PR3-LM) and a servo motor [/INST] http://literature.rockwellautomation.com/idc/groups/literature/documents/rm/motion-rm003_-en-p.pdf Chapter 2, page 253 describes this problem somewhat. It's basically telling you you've got a connection problem or you have noise coming in on the feedback cable. Page 249 says to use a MSG command to get the RA specific exception (to get the fault subcode), page 257 shows how the bits are mapped. Suggestions: Remove the feedback connectors from motor and drive. Inspect each end, inspect the drive pins, motor pins. Look for something wrong with the connector. If there are screw terminations involved, make sure all conductors are properly seated. Make sure you follow Rockwell's grounding practices with regard to drive and motor. If none of that solves the problem, then: Change the cable. Change the motor. \\n </s> |
<s>[INST] FAULT S47 EN KINETIX 6500 Summary: APOYO CON LA FALLA S47 EN SERVODRIVE KINETIX6500 ESTIMADOS TENGO UN PROBLEMA CON LOS SERVODRIVES KINETIX 6500, CADA CIERTO TIEMPO APARECE EL ERROR S47, EL CUAL SOLO SE BORRA QUITANDOLE LA ENERGIA DE CONTROL AL DRIVE. ALGUNA SUGERENCIA? [/INST] Se pone que quando el servo motor esta en operation. El kinetix 6500 esta tratando de reglar el encoder en el servo motor. Quando dese Motor encoder self test. El encoder esta malo. Estos servo motores estan en eithernet. En el axis properties/hook up tab. puedes linar el neuvo encoder con el presente motor. Pero no te lo recomendo, es un batailla. Es mejor al combar todo el servo motor completo. \\n </s> |
<s>[INST] Poweflex 525 online changes Hello , Is it possible change parameters in online mode when connected to online plc station ,while drives are running , without inerrupting them ? If yes will setting be saved in drive if power loss would occured ? or it should be done offline? parmeter c121 comm write mode is set as default - Save on this setting parameter change should be written to eeprom right?, i have read also attention that repeated write of parameters can damage eeprom ,but if it is changed once it should be ok right? [/INST] Fitz The AOP is software that is installed on your PC... The AOP communicates directly with the online drive and/or it can save data to the offline project (on your PC). Most the the parameters can be changed while online with the drive (assuming the drive is not running the motor). Some parameter cannot be modified while the motor is running. When C121 = 0, the parameters are saved, they are saved to EEPROM. \\n </s> |
<s>[INST] Help I'm ac drive dumb. I have a 1305 AA12A HA1 If I have a 220 single phase input...will the output be 3 phase? I realize how silly that may sound but none of the literature I've read confirms yes or no. can I operate a 1hp 3 phase ac motor using 1phase 220? [/INST] Even though that drive will take a single-phase input, it has a 3-phase output so is designed to operate with 3-phase motors. The drive output power is derated; the table below will show you the output current and power available to your drive if it is powered by 1 ph. line. Just check to fall inside the indicated values with your motor. Hope this helps, - fuzzy logic \\n </s> |
<s>[INST] How to open the saved configure file .dcf in the Motion Viewer format for Kinetix 300 (Cat. 2097) Dear all,As we all know, We can save the Kinetix 300 configure file in the local disk in .dcf.xml format.My question is How to open the saved configure file .dcf in the Motion Viewer format for Kinetix 300 (Cat. 2097) ?when we offline to the Kinetix 300.Do we need any software just like as the Ultraware for Ultra controller? [/INST] We can not open the xxx.dcf.xml Kinetix 300 configure file with offline. \\n </s> |
<s>[INST] OPTIX 1.2.0.263 - well much testing has been done before posting this report of what i suspect is a possible bug. Please check the Trending operation with 6 or so pens , with the function FOLLOWING set to FALSE. Then go to application , select your trend page. You will note the Trend pens start from the center of the page , this is fine and im happy. Now grab the trend and move it back in time a few times , then wait a few seconds ( depends on your polling update time ) but here , the FOLLOWING function seems to be set as True . Once i have disturbed the trend chart back in time for veiwing , the chart continuously updates back to the far right of the screen , inhibiting you from reading the previous chart values. To prove there is an issue , I created a dynamic link with a check box for the Following function and placed it on the trend page. Again, first use , all is well , but 2nd use etc it fails to observe the functions command. This issue i found many days ago. Anyone else see this ? [/INST] Yes, I have seen this. I assumed the FOLLOWING property to be essentially a pause command. It does seem that manipulating the trend display overrides this function after a brief delay. This could be intentional and just not documented well or perhaps it is a bug. Nevertheless, I concur with you that it ideally should not be this way. There should be the ability to pause the trend and manipulate its view indefinitely.\n </s> |
<s>[INST] 1756-HSC Continuous counting... I am using an encoder on a process line and would like to accumulate length of material. I have an encoder wired to a 1756-HSC and am using it to measure cut lengths.I have an application program that runs in a periodic task of 10 ms. The PresentValue[0] is the input to a pulse multiplier:Mode = 1 RelativeWordsize = 32multiplier = 1000000 Output goes to InPlus on an UpDnCounter block. It works fine and is calibrated accurately except when the presentvalue[0] rolls over. When the rollover occurs I get a negative number on Pmul.Out and subtracts from the updown counter. How can I work around this? Thanks for the Help! [email protected] [/INST] Answer to your issue is in this statement, taken from PMUL online help: When applying this block, it is important to note that the feedback data should not change by more than ½ the word size from one scan to the next, if rotational direction is to be properly differentiated. In the example above, if the feedback device is moving in a clockwise direction such that at scan ‘A’ it reads 0 and then scan ‘B’ it reads –2000, actual change in position is equivalent to +2096 counts in the clockwise direction. However, since these two values are more than ½ the words size, (or more than ½ the rotation of the physical device,) the PMUL instruction calculates that the feedback device rotated in the opposite direction and returns a value of –2000 instead of +2096. So, which is the count range of your HSC ?You have to change the WordSize in PMUL to remain in the right range, following the examples below. Here some examples: count range 65535 to -65536 ---- set WordSize = 17 bitcount range 2047 to -2048 ---- set WordSize = 12 bitcount range 255 to -256 ---- set WordSize = 9 bit Informations are in Logix5000 Process Control & Drives Instructions Reference Manual pages 261-262 Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Ultra3K driving a LDC-C100 series Linear motor (460VAC) Summary: Motor moves only over short distance and reaches peak currentHi All, So we have this custom motor from Rockwell-LDC-C100series which is being controlled by the Ultra3K drive. The encoder we use has a 20um optical pitch with 1um resolution. The motor is mounted vertical ( we do have brakes, latches, and straps to avoid a free fall incase motor loses power etc) The total moving mass is about 50kg.The issue we are seeing is that, we are unable to travel more than 25mm ( even with low speeds of 5mm/sec) where in the current reaches its peak value (68A) and servo faults. We have checked and verified the following-U, V, W phase wiring ( using commutation test available in ultraware as well as manually trying all 6 combinations of U, V, W phases;) Hall effect sensor -S1,S2,S3 wiring ( when moving up-S1 leads S2 leads S3 and conversely lags when moving down, confirmed with physical scope as well as scope option in ultraware), encoder is reading correctly in the full length of travel. There are no mechanical parts in its path that may be causing this. Can anyone think of anything we may be missing here ? Thanks in advance. [/INST] Is this a brand new application you're trying to commission, or an existing installation that suddenly stopped working properly? \\n </s> |
<s>[INST] F100 on 4M When I was setting the communication parameters on one of the 4M drives (through the keypad), and after cycling power on the 480AC line to the drives, 1 off the drives was showing F100. (Parameter Checksum Fault). Forcing me to reset all parameters back to default, and then reenter them. What causes this fault! (or better, how can we avoid this). I don’t want my customer to have to do this, but remember having similar checksum problems on a GV300 systems years back. In that case the drives were on a DC bus and Rockwell claimed the problem was that the bus voltage dropped to quick.These drives are not on a DC bus.Guys, any thoughts here would be awsome! [/INST] Unfortunately it isn't documented a probable cause for this fault, just it is indicated to Restore Default Parameters and retry...It could be a random and false checksum error, but if it often reappears, then it is a true checksum fault and the drive will need to be replaced. - fuzzy logic \\n </s> |
<s>[INST] Powerflex 755 Hi: When I try to add new module on my I/O window in RSLogix 5000 I can't find this drive. How can I get It?For the application I need, the cpu is 1756-L55 Ver 15.3. Thanks [/INST] You can obtain the newest Drives AOP here: http://support.rockwellautomation.com/controlflash/LogixProfiler.asp This Drives AOP can be used with RSLogix 5000 V16 or later....this would require you to upgrade the processor firmware to V16.xx. - fuzzy logic \\n </s> |
<s>[INST] In Micro 850, What is a purpose of the green tags? _IO_Xx_ST_00 and _IO_Xx_CO_00 [/INST] _IO_Xx_ST_yy represents Global Variables for Analog input status. Analog input status values can be read from Global Variables IO_Xx_ST_yy. Where x represents the expansion slot number 1...4, and yy represents the status word number 00...02. Individual bits within a status word can be read by appending a .zz to the Global Variable name, where zz is the bit number 00...15. _IO_Xx_CO_00 represents Global Variables for Control bit states. Control bit states can be written to Global Variable _IO_Xx_CO_00.zz, where x represents the expansion slot number 1…4 and zz represents the bit number 00…12.\n </s> |
<s>[INST] Motion planner scan order? Hi there, Anyone knows in what order the axes are dealt with by the motion planner? Is this automatically resolved, so that (when possible!) a whole sequence of MAGs (and MAPCs) is always fully evaluated every Coarse Update? Think: (Axis) -> MAG -> (Axis) -> MAG -> (Axis) Or do I need to arrange the axes by means of naming etc so that complete one-scan evaluation is achieved? Thanks a lot! [/INST] A clarification: Take the example (Axis 3) -> MAG -> (Axis 2) -> MAG -> (Axis 1) Assume that the motion planner evaluates Axis1 first, then Axis2 and last Axis3. That would make Axis1 operate on 2 Course Update Times old values from Axis 3. The question again: Is the motion planner smart enough to evaluate Axis 3 first and Axis 1 last, or is there another way to control the scan order? \\n </s> |
<s>[INST] PowerFlex 750 DC Bus sharing Hello everyone, I want to use 2 Powerflex 750 stand-alone dc AC Drives in Shared DC Bus Configuration mode. The first driver is used to turn a large drum and when the supply voltage is cut off, it takes 20-25 minutes for the drum to stop. I want to continue energizing the 2nd drive from the DC bus for a portion of the time until the drum stops. The first drive goes to fault because its power is cut off and ends the DC bus sharing. What are the parameters that need to be changed for this application? [/INST] Hello Kivanc, the drive fault history can be viewed on the HIM - do you see any faults there? Brian \\n </s> |
<s>[INST] Panelview Plus 7 Performance series A x Internet Explorer Version. I am trying to visualize my cameras on HMI but I need at least Internet Explorer version 11 installed on HMI. My HMI is a Panelview Plus 7 Performance Series A, which is the internet explorer installed on panel view? it is possible to upgrade the internet explorer for version 11 or install edge on it? [/INST] On Panelview, Plus 7 Performance series A it'll never going to work even using ActiveX ME Web browser, because the internet explorer should be at least version 11, Microsoft Edge or Chrome. Panelview Plus 7 Performance series A is a windows CE embedded, very overridden working on Internet Explorer 6. That is one of the reasons it has a very bad performance. I would recommend you to go to an Panel windows IT embedded, can be Panelview Plus 7 performance series B or another industrial PC from any other brand. It will work fine.\n </s> |
<s>[INST] 4160 VFD Summary: Synchronous Transfer ProblemsWe have a 4160 synchronous transfer bypass system for two motors that will not synchronize with the fixed frequency buss to allow the transfer. ANy thaught on where to start looking? Could it be the isolation transformer? [/INST] Wow !! I guess this is with Powerflex7000 drives, best to leave it to the experts and get a Rockwell field support engineer involved \\n </s> |
<s>[INST] Kinetix 300 drive I have a Kinetix 300 drive, I am trying to set the IP address manually and I have followed all the steps. Enable DHCP to 1 and cycle the power, nothing seems to be happening, am I missing something? Am I not waiting long enough? Please help. [/INST] Sanders, I suggest to review the following technotes: QA41356 - Kinetix 300: How to setup IP Address QA40556 - Manually changing the last octet of IP Address on Kinetix 300 drive IN30426 - Kinetix 300 DHCP Not Working Please don't forget to LIKE and highlight the decisive answer: REPLY > Make Best Answer \\n </s> |
<s>[INST] PowerFlex 70EC I want to know what is the difference between 0-60 hertz on parameter 72? How is it going to behave at different increment? [/INST] Lee The Break Frequency is shown on p30 It is used to change the v/f line. \\n </s> |
<s>[INST] Issue with KB 56209 MSG about SERCOS ring Fault. Please refer to Knowledge Base 56209 I have do this test in the Lab, but with the MSG error. CompactLogix L43, firmware 17.2; 1768-M04SE; firmware 17.16; alais for 'Sm' 2094-AC05-M01; firmware 1.113; alais for 'ac05' 2094-AM01; firmware 1.113; alais for 'am01' message to read the error log in the SERCOS motion module: with Error Code: 16 [/INST] Never tested but, as far as I can understand from the technote, the target of the message should be the 1768-M04SE... did you configure the path accordingly ? - fuzzy logic \\n </s> |
<s>[INST] Centerline MCC 2100 I got a 2113 FVNR Size 3 that needs to be put back together. I can't figure out what the last few digits in the part number represent. 852AGP Any help would be great. [/INST] I can't find any breakout of how MCC part numbers are generated so I would say contact your local AB rep with the full existing part number and they should be able to help you figure out what it includes. Regards, RM \\n </s> |
<s>[INST] 753 Drive trips on 5028 SI Comm fault when stopping Summary: Powerflex 753 trips a 5028 SI comm fault, when drive is stopped, have DB brakesDrive setup-Powerflex 753 with Ethernet card, communicating with a Micrologix1400, running through drive wizard startup, and at the point where you check the direction of rotation, drive starts runs at entered speed, and when you hit stop icon on wizard, the drive trips a SI comm fault 5028, had wizard set for rapid stop and coast to stop, same results, have 4 drives in this setup and tried another drive and it also did same thing. any ideas? [/INST] George, have you seen this? https://rockwellautomation.custhelp.com/app/answers/detail/a_id/580277/page/1 \\n </s> |
<s>[INST] Power Flex 755 encoder card Summary: What might be reasons that causes encoder card failure in powerflex 755 drives. [/INST] We've encountered a number of ENC1 incremental encoder input card failures for PF750 drives (one customer's drive has eaten 3 of them, I think). We never found a convincing reason. Sorry, no solution, but you're not alone either. How many cards failed so far? \\n </s> |
<s>[INST] PF 700 Encoder Access On a PF 700, can the encoder count be accessed by ControlLogix through Ethernet? If so, what would be the most efficient way. I won't be using this information for precision positioning or anything, but as a way to roughly track the distance traveled on a chain. [/INST] I think a way is to use Datalinks, linking an Output Datalink to the parameter you need (i.e. Par. 414, Enc Position Fdbk).If you have RS5000 v16 or above you may easily setup this in the I/O configuration for your drive connected over Ethernet/IP; then you have your data available in the Controller Tags. (see attached screenshots)Have a look to the User Manual for 20-COMM-E and also the Aid 44844 (it is for Devicenet, but Datalink are the same also in Ethernet) in order to correctly configure your Datalinks. Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] Drive example apps? I'm trying to learn this new powerflex stuff and I learn best when I have example apps. (Manuals put me to sleep! :) ) Anyone have a good link to drive example apps? [/INST] Have you looked at the sample code library? There are examples there that show how to do drive control with ControlLogix. You can find it here http://samplecode.rockwellautomation.com Hope that helps! Cal \\n </s> |
<s>[INST] PF700S Torque mode Hi, When you used to control a winder using Min Spd/Torque mode P110. Which parameter is your torque reference and your min. speed reference? Can you share how you did it? Thank you, [/INST] The torque reference will be P427 (Torque Ref A Sel) or P431 (Torque Ref B Sel) and the [Minimum Speed] will be P038. Refer to : http://literature.rockwellautomation.com/idc/groups/literature/documents/um/20b-um002_-en-p.pdf Page 26. and http://literature.rockwellautomation.com/idc/groups/literature/documents/rm/pflex-rm001_-en-e.pdf for detailed VFD operation. \\n </s> |
<s>[INST] PF753 APPLICATION CAN WINDER APPLICATION IS POSSIBLE USING DEVICELOGIX IN PF750 SERIES ? WITHOUT PLC.................. [/INST] It Depends on the application. Need much more information. So my answer would be a great big MAYBE? \\n </s> |
<s>[INST] PF755 master/follower application - recommended encoder Summary: single channel / single ended or dual channel / differentialHi, I have an application in which I am hoping to use two PowerFlex 755 AC drives in a Master / Slave relationship in a roll-to-roll web handling application. My plan is to equip the master drive with a 20-750-ENC-1 single incremental encoder module and to equip my slave drive with a 20-750-DENC-1 dual incremental encoder module. I will have an encoder mounted on both the master motor and on the slave motor. I plan to wire the master encoder to both the master drive (as feedback for the controlled master motor) and to the slave drive (as an external reference). I will wire the slave encoder to the slave drive (as feedback for the controlled slave motor). I am hoping to use the electronic gearing feature to ensure that I can run the slave motor at a fixed ratio of the master motor. Ideally, I am hoping that I can achieve good performance (in terms of accurate speed control without motor cogging) within a 100:1 speed range (motor RPM ranging from 18 - 1800 rpm). With this in mind, I am planning to use a high quality vector duty motor. My application is basically a constant speed application, where the master roll and the slave roll are used to convey a continuous web material through a machine. The speed ratio is nominally always 1:1 because if the rolls do not turn at the same speed, it would either create slack between the two rolls or break the web. This being said, I do need the flexibility to adjust this ratio between approximately 0.998:1 and 1.002:1 to compensate for stretching or shrinking of the web material in a dryer that it passes through. I *think* there is a good chance I would be able to get the performance I want with independent drives (not using electronic gearing) by just entering set points in the desired ratio, using the same acceleration/deceleration settings for both drives, and making sure I issue start and stop commands for both drives at the same time. The reason I'd like to try the electronic gearing feature is because I think it might help me do a better job of coordinating the speeds of the drives during acceleration and deceleration. I figure if it turns out not to be unnecessary, I will only have wasted the extra cost of one dual-encoder module and hopefully I will have learned something about the electronic gearing feature that might help in future, more challenging applications. My question for today is, will single-ended, single-channel encoders of appropriate resolution be sufficient for achieving good speed control? Or will there be some advantage to be gained if I consider using dual-channel, differential encoders? Any advice or suggestions will be greatly appreciated. Thanks and best regards, Paul [/INST] Consider using an encoder splitter on the master encoder signal - master encoder goes into the splitter; output1 goes to the master drive, output 2 goes to the follower drive. https://www.motrona.com/en/products/signal-converters/level-converters-signal-splitters/gv210-pulse-switch-distributor-and-splitter-for-incremental-encoder-signals.html I think I'd go with differential encoders myself. In all other respects, you've got it wrapped up pretty well. \\n </s> |
<s>[INST] CCW - KINETIX_300 integration problems Summary: Having lots of problems while trying to integrate a KINETIX 300 with a Micro850Dear friends, Not having too much luck with this integration project that involves a Micro850, a PanelVien PV800 and a KINETIX 300 servo drive. The main issue as of right now is the fact that I cannot run the MotionView built in software from any of the 5 different PC´s that I have already tried. The weird thing is that I was able to run MotionView at the very beginning of the setup. So yes, at first, I was able to go online and even change the IP address from the factory one 192-168.124.200 to our own Network´s IP address which is 172.50.8.80. The one thing I did not do as I was supposed to do, and that was reseting the drive to FACTORY DEFAULT. That final step was not performed. Now, everytime I try to establish a connection between mi PC and the Kinetix 300 drive I get the error shown in the attached picture. The PC runs the java archive MotionView download with no problems, but when I try to open the file that is when it hangs up for a couple of minutes (supposedly downloading something) and then it gives me this other error (left side of the picture) saying the download cannot be completed. I have checked all possible causes from the hardware and the software sides. nothing seems to work. I will appreciate any help that can be provided. Flex [/INST] I guess you're encountering the issue explained in the following technote: 1044877 - MotionView does not launch after Java 8 Update 131 Hope this helps, - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] Using motor terminator for cable length more than 189 A Rockwell 1204-TFB2 motor terminator with the serial number: MEAB30Z6 has been bought in order to reduce PWM peak voltages at the motor terminal. The VFD and the motor specifications are as the following: VFD Power: 580 kW Motor Power:580 kW Voltage (rms at VFD output and Motor terminal): 580 V DC Link Voltage: 900 V Cable length: 250 meter Filter: a Series Reactor at VFD Output PWM Peak Voltage at Motor Terminal: 1700 V (Twice the DC Link) PWM Rise Time at Motor Terminal: 0.2 us PWM Rise Time at Motor Terminal: 3-4 us According to the 1204-TFB2 datasheet, the maximum cable length should be less than 182.9 meters. Unfortunately, the length of the cable in our study case is about 250 meters. A series reactor has been installed at the VFD output, which increases PWM rise time and reduces the reflection phenomenon at the motor terminals. In other words, using a series reactor reduces the peak voltage at the motor terminal in comparison to when this reactor has not been installed at the VFD output. However, is it possible to use 1204-TFB2 in this case study (in this case study, cable length is more than 182.9 meter)? In other words, the limitation of the cable length can be increased by using a series reactor at the VFD output? [/INST] Hamed, The maximum length of 182.9m (600 ft) is correct as stated on page 94 of https://literature.rockwellautomation.com/idc/groups/literature/documents/in/drives-in001_-en-p.pdf Which drive are you working with? For our drives we have tables that provide the options for mitigating reflective wave issues. For example our 800 Hp PowerFlex 755 table 56 is on page 139 of the same manual I provided above. For cables over 250m you would need a reactor and a damping resistor and also a motor insulation rating of 1850V or more. You should not use a reactor with a motor terminator because it can cause voltage spikes exceeding the motor insulation ratings. This is documented in our Knowledgebase QA27120: https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/686116 Unfortunately, you cannot safely use a motor terminator at that cable length. \\n </s> |
<s>[INST] STO during deceleration EDIT: moved to Drives and Motion community -FL I have some servos on K5700 drives. The STO get broke with a light curtain block. This works fine during the move, the servo stops and restarts with an opto, but if the light curtain gets blocked during deceleration the drive keeps going and actually overshoots the target. Has anyone else seen this? There is no brake, but the servo is under load and should want to stop. [/INST] Hello Morley, couple of questions for you: What Kinetix 5700 are you using ERS3 or ERS4 ? Are you using a wired safety signal to the drive or a CIP Safety over EtherneIP ? When you operate an STO on a Servo drive you stop the motor control. So if you request a safety stop action that directly does an STO on the drive , the motor will coast without any control whatever the movement you were doing. This is called a stop category 0. So this is normal that you can overshoot a target since no more control is applied to the motor. With the Mechanical and load inertia the motor can rotate freely for a certain time if you don't have a safety brake. Now you can deploy a different safe stop category. Safe Stop category 1 , called also SS1 . Now the SS1 will give you time to decelerate correctly your axis and stop if before STO occurs. The way of deploying this feature will depend of the answers you will provide on the previous questions. you can also look at this manual : Kinetix 5700 Safe Monitor Functions Safety Reference Manual (rockwellautomation.com) (Link updated) regards \\n </s> |
<s>[INST] PowerFlex 525 Firmware Summary: Upgrade? Downgrade?I have been using Firmware revision 1.005 for all new installations of the PowerFlex 525 drive with no issues. I have had issues with rev. 2.02. I am looking at the new firmware revision 4.001 and I cannot find information on it. Does anyone know if a firmware up/downgrade on new equipment will provide any benefits from what I am using now? Or does anyone have any issues with the latest firmware revision? [/INST] Welcome to the Forum ! I suggest to upgrade, my experience is good with this rev. Here the Release Notes: http://literature.rockwellautomation.com/idc/groups/literature/documents/rn/520-rn001_-en-e.pdf - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] Powerflex 700s Fault 27 ( IOC ) Intermittent trip Morning all! Hope to get some answers on this re-occuring fault that has us baffled. We have a powerflex700s as the lead drive on a front drum of a winder and are currently experiencing intermittent Fault27 ( Instantaneous Overcurrent ) trips. This drive has been on line for several years without issues but, for the last 8 months, it has been faulting on F27. We have done the following to isolate the problem yet it still trips and appears the frequency of trips is more often. 1.)Swapped drive to spare and downloaded running program. 2.) Autotune3.) Changed Motor4.) Temporary motor cable swap5.) Temporary tach cable swap6.) Lowered parameter 402 from 900 to 300 - PWM Bandwidth We have attempted to run an autotune, and believe to have done so successfully but still trips. We suspect tuning may help us but unsure where to go from here. Any suggestions, correct answers and I'll buy coffee? Regards, Thibs [/INST] first thing the manual says is reduce mechanical load...how did that affect it? \\n </s> |
<s>[INST] VFD DRIVE GV3000 /SE 230 - Analog Input Speed Control Issue I'm having problem with the speed control signal to the VFD drive Modle GV3000 / SE 230. It is an old model probably 12 to 13 years old. Orginally, a 0 to 20mA signal was used to control the speed of the motor through this VFD. But today the drive was not following the remote speed control signal, it just ran at minimum speed. Checked the parameters and jumper J4 and look correct. When a maximum signal is given i.e. 20mA the drive goes to the minimum speed (set by parmater P0003) and when a minimum signal is given the drive increase the frequency up to 15Hz (max speed is set at 60Hz). Re-wired the drive so a speed control signal from 0 to 10VDC volts was used as I thought the 4-20mA analog input signal receiver of the drive went bad. Jumper J4 was moved to pin 2-3 and the paramter P-0011 was changed to 2 (0 - 10 VDC). Still the same problem. When I increased the maxium speed paramter to a higher value, the drive will increase the speed accordingly when a minimum speed control signal is given. For example Speed Signal VFD Drive Speed Output In Hertz Max Speed In Hz set by P004 0 VDC 15 600 VDC 30 90 I would appreciate your feedback if you have ever encountered such a problem and were able to fix it. Regards, Charlie CamilleriMaintenance Technician [/INST] Look at OIM, see LED AUTO, this control by AUTO/MAN. If AUTO the speed reference source is come from terminal strip. Please download manaul from RA website D23359-460V NEMA Software.pdf \\n </s> |
<s>[INST] PF755 Spindle Orient Summary: Is PF755 Spindle Orient posible with absolute encoder Has anyone had any experience using a PF755 drive, 20-750-UFB-1 card and an absolute encoder using Spindle Orient Mode? I need to be able to run at a nominated speed the stop at a nominated position of the output shaft. [/INST] It was included in V2 firmware. See parameters starting at 1581 on page 196 of the programming manual ie 750-PM001B-EN-P. \\n </s> |
<s>[INST] kinetix 6000 and external encoder Hello I have successfully started up my first Kinetix 6000 with external encoder. Machine works but there is one problem. External encoder is on the other side of the conveyor and if it is lifted up (material jam...) motor starts with motion. It looks like it’s trying to find correct position. It would be better if motor is disabled when position error is too high. What needs to be done? Thanks, Janko [/INST] Position error is an item that is watched for an axis. In the axis properties, on the Limits tab is the setting for the maximum Position Error Tolerance. This is set when the axis is auto tuned. Along with that, on the Fault Action tab, is the setting for what function will occur when this position error limit has been reached. Disable Drive is a choice for this item. You may want to check these settings. Also, you could do a GSV to watch the position error (has to be selected as one of the Real TIme Axis Information items on the Drive/Motor tab) and create your own actions when this value is larger then some other value. \\n </s> |
<s>[INST] PF40P Replacement Issue We have recently installed some OEM equipment in our facility. It came with 5 PF40P drives. The first drive has a 22-COMM-E and then uses the DSI port over to the other drives. I am tasked with writing a procedure for replacing the drives when a failure occurs. I have several PF40 drives in plant in similar configurations and understand the DSI protocol and setting the A103(comm data rate) and A104(comm node address) parameters manually prior to downloading the .dno file to the PF40. However the PF40P does not have a keypad on the front. Am I going to have to attach a 22-COMM-E to the replacement drive, lauch DriveExecutive, change these 2 parameters, kill power, remove the 22-COMM-E and then commission the drive? I hope not. :smileysad: [/INST] Here from the User Manual, chapter 3 and page 2-3 : Parameters are programmed (viewed/edited) using either a DSI Remote HIM or PC programming tools (DriveExplorer™ or DriveTools SP™ software), a personal computer and a serial converter module, connected to the onboard RS-485 (DSI) port Drive Programming Tools - Descriptions and Catalog Numbers Serial Converter Module 22-SCM-232 or 1203-USB DriveExplorer Software(1) 9306-4EXP02ENE DriveTools SP Software(1) 9303-4DTS01ENE Remote Panel Mount, LCD Display 22-HIM-C2S Remote Handheld, LCD Display 22-HIM-A3 (1) Requires a Serial Converter Module. See also Appendix B for a complete list of accessories. - fuzzy logic \\n </s> |
<s>[INST] Continuous change of gearratio on 1 servo-axis Hello, We have an application which requires a continuous change of gearration of 1 slave axis to a master axis (f.ex. 1 change of gearratio per 500 ms).Currently we execute this by having 1 MAG-instruction which we call every 500ms with an updated gearratio. The clutch-setting in theMAG-instruction is active. We have RSlogix5000 V16 .For about 90% of the startups this setup works fine. But 10% of the cases it goes wrong and we see that the updated gearratio is not becoming active. What do we do wrong. Is there a better way for updating the gearratio continuously from 1 slave axis to the master axis? FV. [/INST] You might try creating an event task to perform the MAG instruction and have it run after the ratio variable has been updated. Also, in this event task, monitor the variable to make sure it is a different value then the previous one. This is only a test to make sure it has a new value. \\n </s> |
<s>[INST] Powerflex 4 drive with 1203-USB issues. Summary: Cannot connect to drive! Hello everyone. So here is my problem. I have a Powerflex 4 drive that I am using to control a 3 phase motor. To start with, I will let everyone know what I have, and what I'm trying to do, then my problem. 1: Windows XP pro SP3 on a Dell Latitude D610 2: RSLinx Classic 2.59 3: 1203-USB Flashed with the 1.004 firmware 4: Connected Comnponents workbench 2.0 So here is what I've done already. I installed the connected components workbench 2.0 which gave me all of the above. Then I plugged the 1203 into my USB port, and installed the drivers that I downloaded from AB. After that, I setup the driver in RSLinx exactly to the instructions listed in the manual. When I go to RS Who, I get nothing for a drive. So I looked around and see there was a firmware update. So I updated to the 1.004 firmware using the hyperterminal method. That worked perfect. No errors. Tried again, and it still didn't work. I know I'm on Com 4, because when I go to control panel, it tells me so. I used hyper terminal to change the drive to a master instead of AUTO, and did a reset, and that didn't work. I have even went to the extreme of reinstalling windows, and trying different options in the OS... No firewall, etc... Nothing. IT did connect one time, and now I cannot figure out what it did to duplicate that. When I upgraded the firmware, I ran the controlflash install program which put a bunch of folders under 0001. Then in hyperterminal I selected 0001/0078/2500 and the boot one first, then the combo one second. I'm not sure what all the other folders are for. Is this correct? Any ideas? Thanks in advance Pat [/INST] If I understand correctly, you can communicate via Hyper terminal, but not RSLinx. Is the main diamond shaped light on the 1203-USB blinking green? Does the drive have any other comm modules (e.g. 22-comm-E)? Is it part of a Multi-Drive setup? What are the settings you used with RSLinx? (Please list all items, or provide a screen shot) Generally, it should be: - RS-232 DF1 Devices - Device: 1770-KF2/1785-KE/SCANport - Baud Rate: 115200 - Error Checking: CRC Other options: - Is Hyper terminal closed? (RSLinx must be able to access the comm port) - In the RSWho window, right click on the driver and get what the properties are. - Is RSLinx browsing? (animated icon on driver; “Autobrowse” checked) \\n </s> |
<s>[INST] Rare Earth Metals in VSD construction As a point of discussion, was trying to investigate whether there was any reliance on rare earth metals for the construction of VSDs, more precisely in MV VSDs. Could one maybe look at the power cells as a starting point? [/INST] Hello Npendulo Could explain a litle more what you are looking for and why ? that will certainly help the community to try to answer you. regards \\n </s> |
<s>[INST] PowerFlex 70/700 System Error - No device Application Code Summary: Technote 52027On a barnd new drive installed this month we are getting the application code error. In response to a ticked ticket submission about this, I was sent the contents of the technote. The technote says The PowerFlex 70 main control pcb's aren't standard spare part items or field replaceable items. Prior to installation the board require several flash files that allow the PCB to work. The files are boot code files, application files plus the firmware files which need to flashed by the factory to the boards. All of these files are flashed at the factory during drive assembly.... If this is the case for a brand new drive Then, Why oh WHY, send out a drive that has to be sent back to the factory to work?!?!? Can anybody explain why this condition exists? Since 2008? [/INST] This sounds like you got a remanufactured drive which didn't go through all QC procedures. That sucks, to be sure, and there is simply no excuse for it. What has your distributor and your local Rockwell Representative said about this? They SHOULD be falling over themselves apologizing for the mistake. To be fair to Rockwell, this is not the normal experience; Rockwell does generally do a good job shipping functional new products. \\n </s> |
<s>[INST] Powerflex 755 with PM motor - Effects if moise in encoder feedback readings Hi everyone For a PowerFlex 755 with PM motor with incremental encoder. If we have noise and/or encoder inaccuracies that affect encoder feedback over time will this jeopardize motor commutation over time? On the first start after a power cycle, we do the PM Offset test and the relationship between that angle and encoder feedback is good, so we have proper motor commutation. But eventually if the encoder feedback is not accurate for any reason over time, will we loose that relationship between the commutation angle and the encoder feedback? Will we lose proper commutation of the motor over time? Can this cause Overvoltage faults? What other effects cuald affect having this issue with the feedback? Thanks in advance [/INST] Hi, Check your encoder cabling route, it must be far away enough from AC power cable. Check with OSC on your encoder square wave output , to ensure encoder can send correct output signal. Terence \\n </s> |
<s>[INST] Powerflex 753 Summary: Heat sink Fan When is the heat sink fan supposed to run? Is there a parameter that would make fan run all the time? [/INST] https://rockwellautomation.custhelp.com/app/answers/detail/a_id/66014 This article explains the fan operation. Frames 0-4 The stirring fans sometimes referred to as muffin fans are on anytime the drive is powered up The main fans also known as the heatsink fans will turn on when the drive starts and turn off thirty seconds after the drive-stops. The turn off is independent of drive temperature. Frames 5, 6, 7 The stirring fans sometimes referred to as muffin fans are on anytime the drive is powered up. The main cooling fan(s) also known as heatsink fan(s) turn on when the drive starts and turns off thirty seconds after the drive-stops. The turn off is independent of the drive temperature Frames 8 and above The door mounted fans on the cabinet doors of an IP20 PowerFlex 755 drive frame 8 and greater turn on when the drive is powered, running, and is drawing more than approximately 10% of drive rated current. Document 454153 - PowerFlex 755 door mounted fans explains the operation of these fans in greater detail. On IP54 drives the door mounted fans are removed and a blower unit is installed on the top of the cabinet. This blower performs the same function as the door mounted fans and operates under the same criteria. The main cooling fan(s) also known as bridge fan(s) or heatsink fan(s) turn on when the drive becomes active (started) and turns off thirty seconds after the drive-stops. The turn off is independent of drive temperature. Note: The Fans for frames 2-7 are 24 Volt DC Fans. They can be tested by putting 24 VDC to the fans to see if they spin. Also, check that the connector outputs 24VDC if the drive is started. If not, replace power interface board (frame 6 and 7). If frame 5 and below, replace drive. The heatsink fan(s) for frame 8 and above is a self contained fan and inverter. \\n </s> |
<s>[INST] Kinetix 5700 | Digital input | Registration | Scan time | Capture time | Cycle time Hi all, I got the request from a customer regarding subject. What is the scan time or Capture time or cycle time of Registration(digital input) ? I found below information on manual but, there is not specified 'scan time'. [/INST] Hello Kang1 I think that the registration input work on Interruption and Time stamping, so scan time (if we can call it like that) will be much below the registration repeatability. Why do you need this detail, since it we already provide all the relevant information for a proper calculation? What is your application needs ? On top of that you should also consider that the sensor reaction time and scan time are most of the time the bottleneck of a registration system. regards \\n </s> |
<s>[INST] Replace VFD in devicenet network Hello friends, recently a VFD 43A powerflex 70 Ec got damage, a kind of short, i am not sure. Now I need to replace the VFD. I have the VFD and the 20-comm-d. I actually changed the address from 63 to 36 (jumpers) and the rate to auto in the 20-comm-d. Is it possible to do this with the proccessor in run mode, I mean this is more less like turn off the VFd and the turn on, if it is not possible, what can id o? Thanks in advance. hector [/INST] Since you're using DeviceNet, it is possible to add on the fly as long as the drive is the same address and type of the one you're replacing. If it's new to the I/O configuration, you'll have to update the Devicenet scanner in the rack. You can actually do this without putting the processor in PROG mode by putting the scanner in idle mode by turning off O.CommandRegister.Run bit of the scanner and then download to the module. Address 63 should be left open since all new Devicenet equipment comes default to this address. Hope this helps. \\n </s> |
<s>[INST] Kinetix 5500 842E Encoder Summary: Problem to cut a foam boardI have an application using a Kinetix 5500, a motor VPL-B1654B-C, and an encoder 842E-CM-S, We are usign the encoder like a master and Kinetix like slave to cut a foam board, the distance to cut is set on the panel view. The encoder is measuring the distance when it is done, we are using a MAG to move the motor (table) to follow the board, down two pneumatic clamps, after that start a motor to cut, when the cut is complete, up the clamps, and the motor returns whit a MAM instruction, I am making test with out load to high velocity and the machine works good, but when it works with foam board the encoder move looks good, but the motor (table) vibrates too much, can someone help me why it happens? The encoder has the higher resolution. [/INST] Have you performed an autotune for the K5500 axis? Or are you using default tuning parameters? If you've done an autotune, can you tell us which choices you made to perform the autotune? Did you set it up as rigid or compliant? Hard, medium or soft response? If you've done an autotune and think that you have a good setup, note that I've found Rockwell's autotune feature tends to tune the axis too hot which might explain the chatter your describe. You may have to manually decrease the tuning parameters to ease the chatter. \\n </s> |
<s>[INST] Powerflex 700 Displayes Power poard checksum 105 on power up Help! [/INST] In the following image, the indications from the User Manual: Unfortunately, the second suggestion seems to be the one that applies to you... :smileysad: - fuzzy logic \\n </s> |
<s>[INST] What's the function of IAM and AM. Summary: Thay both are axis module,so what is the difference?Could you expalain what of their function.It seems to be difficult to find some detailed doc. to focus on it. [/INST] The AM Axis Module has connections on the front for motor, encoder, and auxilliary IO. It draws its power from the power rail. The IAM Integrated Axis Module, in addition to the connections noted above, has connections for input power and control power. The IAM has the converter which takes input AC and turns it into the common bus DC used by all the modules. There must always be an IAM on the left side of the power rail. And before you say it, I agree with you, Rockwell could have picked a more descriptive, intuitive name for the IAM. TJ McDermott \\n </s> |
<s>[INST] How to read warning messages before downloading (logix designer v31)? Recently, I want to summary the warnings of PLC programming. But, I do not download them to avoid the impact of normal production. Is there method to fix it? [/INST] You can Verify the Controller before downloading and it will spit out errors, warnings and messages.\n </s> |
<s>[INST] Powerflex700VC Output Current Summary: Powerflex700VC Output Current still present after stoppingIs this a normal phenomenon that the time I give a stop command to my VFD I can see that the “Output Frequency” is Zero, but I still get an ‘Output Current” and at the same time the VFD is also showing “At Speed” displays on the HIM. It will take for about 3 to 4secs before ‘Output Current” goes to “Zero” and the “At Speed” change to “Stopped”. VFD deceleration time is set 5secs. I am having a PowerFlex700VC drive, 400V, 56A with a 20-CommD adapter. What I understand (maybe I’m wrong) is that when you give a stop command to the VFD after the deceleration time set elapse the VFD will shut down it circuits immediately and goes OFF. Thanks, hope someone could enlighten me. [/INST] I don't thinl it's normal. Perhaps it is only a display problem. You can measure the current with an clamp and see if the indication on HIM is real. \\n </s> |
<s>[INST] Battery for Powerflex 753 755 real time clock Summary: Information about the battery for this function of the drive The Powerflex 753 and 755 have a clock on board that can be set to current time, but does not maintain it through a power cycle. There is provision to install a CR1220 battery on the main control board of each drive, but other than that, there is not much more about this feature. Some details I learned today from an on-line chat with Tech Support: The battery can be expected to last about 10 years. It is used only when the drive is not powered. If the real time clock is set, and then power is cycled, one of two things will happen: If the battery is installed, the clock will maintain its setting through the power cycle. If the battery is flat or not installed, event 206 will be logged. Tech support thinks this is an alarm (not a fault). https://rockwellautomation.custhelp.com/app/answers/detail/a_id/110309 The link above is a knowledgebase article about how to install the battery. TJ McDermott Systems Interface, Inc. [/INST] nan \\n </s> |
<s>[INST] How to configure AB OEMax Servo motor to Kinetix 300? What the [ halls order ] means? How to configure AB OEMax Servo motor to Kinetix 300? In Kinetix 300 Motor Database, Custom Motor.Feedback.Encoder tab There are 4 item [1] PPR before quad _2500___ [2] Halls order _3__ [3] Inverted [4] B leads A for CW ---------------------- AB OEMax servo motor RSMZ-04BA1ANK3 with 2500 incremental encoder interface. ---------------------- What is the [Halls order] means??? It look like a very strange parameter. I can check that the motor running about 3/4 rotation during the autophasing period. then it till trigger Fault Code 128 during autophasing ------------------ I got the error message just list below: Autophasing error. Invalid hall codes or combinations, encoder missing or motor can not rotate (obstruction, not enough current etc. Load has to be disconnected from the shaft !) Please correct and re-try. --------------------- Does anybody could help me? [/INST] Looking for the same type of answer. I can't even see how to post a new subject. What does Halls order mean??? We got an Hiperface Stegmann encoder. On a K300. What Halls order to select? \\n </s> |
<s>[INST] CENTERLINE 2100 ETHERNET COMMUNICATION WITH CLX SYSTEM IN REDUNDANCY Best regards I send a problem that is presented in a CLX redundant system with a CCM centerline. I appreciate if you have any opinion on the possible cause and solution THE ARCHITECTURE OF A REDUNDANT CONTROLLOGIX SYSTEM THAT CONSISTS (SEE FIGURE): - CONTROLOGIX PROCESSOR 5570 1756-L73 REV. 32.051 - ETHERNET MODULE 1756-EN2T REV. 11.001 - ETHERNET MODULE 1756-EN2TR (REMOTE I/O MANAGEMENT) REV. 11.001 - IMPROVED REDUNDANCY MODULE 1756-RM2 REV, 20.010 EN2T COMMUNICATION MODULE IS CONNECTED TO SWITCH STRATIX 2000 (NOT ADMINISTRABLE), WHICH IS CONNECTED TO SWITCH STRATIX 5700 (ADMINISTRABLE), LOCATED IN A CCM INTELLICENTER CENTERLINE 2100. - FOUR VDF POWERFLEX 755 (REV 14.002), WITH OPTIONAL MODULE 20-750ENETR (REV 1.002) - TWO SOFT STARTER SMC FLEX 150 (REV 6.008) WITH MODULE 20-COM-E (REV 5.002) - FIVE E300 / A (REV. 6.1). FORMING A STAR TOPOLOGY ALL MODULES, EXCEPT FOR SWITCHES, ARE MAPPED IN THE PROJECT I/O TREE (STUDIO 5000 LOGIX DESIGNER PROFESSIONAL EDITION REV 32.01 IS BEING USED) PROBLEM: THERE IS NO COMMUNICATION BETWEEN THE EQUIPMENT INSTALLED IN THE CCM AND THE PLC. IN THE I/O TREE ALL EQUIPMENT APPEAR WITH A YELLOW TRIANGLE. HOWEVER, BY ENTERING THE PROPERTIES OF THE EQUIPMENT, THE PARAMETERS CAN BE OBSERVED IN REAL TIME, BUT THEY CANNOT BE ACCESSED THROUGH THE PARAMETERS CREATED IN THE DEFINITION, FROM THE PROCESSOR'S TAGS FOLDER. FURTHER, NO TYPE OF COMMUNICATION FAILURE IS INDICATED, EXCEPT FOR THE TRIANGLE [/INST] nan \\n </s> |
<s>[INST] How to use 0-10V votage to control the 1336PLUS with the module TB-2? How to use 0-10V votage to control the 1336PLUS with the module TB-2? How can i setup the parameters on the interface of 1336PLUS? [/INST] Following a screenshot with the wiring and the minimum parameter needed to use the 1336 PLUS (1336S) with 0-10 V reference. (just be aware if you're asking about 1336 PLUS II -1336F- configuration is different :smileysurprised: ) Reference is 1336 PLUS User Manual Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Gearing status Hi everyone, Does anyone know if there a status bit present in the motion, indicating that no other axis is geared to this axis?Because homing a master axis with a slave still geared to it makes the slave axis do unexpected movements... If such a status bit does not exist, is it something for the development team to incorporate this? Best regards,Cee Ya [/INST] There isn't a bit available to do what you wish. You'll have to check all the GEARING STATUS (or POSITION CAM STATUS) bits of all the possible slaves of your master to be sure they're off before issuing the home routine. \\n </s> |
<s>[INST] Data Links in RSLogix 5000 Ver.16 If you define a data link that is type Dint, do you have to leave the next open field undefined? Is each data link field only a word? Thanks in advance. [/INST] AJB111,data link length depends upon the drive.i.e normally for pf 70 it is 16 bit i.e one word.for pf 700 it is 32 bits i.e 2 words.So if you want to store 32-bit parameter using 16-bit datalink both datalink a1 & a2 will store lsb and msb respect.Hope it helps. \\n </s> |
<s>[INST] Continous Motion Control I have a system that uses Kinetix 6000 drives to control servo motors for positioning. I was wanting to know if there is a way to use a continous move command that will follow a setpoint from a feedback device. So if the signal goes positive the servos will go forward and if the signal goes negative the servos reverse. I can only see motion commands that exucute once, not one that is continous. Is there a way to do this? [/INST] Others have asked similar questions. Some options you can consider:- 1.Set the absolute posiiton of the servo to zero at its mid so that it can swing positive and negative (a home routine would be required on power up)Scale your PID output to correspond to absolute position.Every time your PID block is done - just execute an absolute MAM (just ensure you are't doing this too quick an update).Note - it doesn't matter if there's no new position to go to - if the servo is alreadt at the destination - it will go no where with a new absolute MAM to the same place. 2. If you want to do something with incremental moves instead, just periodically refresh an MAM instruction at a chosen rate again. \\n </s> |
<s>[INST] Ultra 3000 hardwire enable I have been wondering if the hardwire enable on the 3000 should be used with the sercos enable command ? If we use the sercos, servo on as the enable command for the drives, should the hardwire enable on the breakout board be used or not or should we leave all control to the sercos loop. I encountered a drive in this condition that would occasionally make a humming sound as it was waiting for a start and when the hardwire enable was removed from drive config and the breakout board this humming went away. There are a few others that do the same thing but I haven't had a chance to get at them. Any knowledge on this condition would be appreciated. [/INST] It is possible to control the enable of the Ultra 3000 SERCOS drive without having to connect 24 volts to the Drive Enable input (pin 31) of the CN1 connector. Using Ultraware, the Digital Input 1 is used for Drive enable. If the input is changed to unassigned, the drive will be enabled on power up. There will be no need for an input to pin 31 to enable the drive.Be aware that, in this case, the motor could start moving on power up. :smileysurprised: - fuzzy logic \\n </s> |
<s>[INST] Looking for an AC Vector Drive Recommendation Hi, I am wondering if Rockwell has an AC vector drive that would meet the following requirements: (1) Power 220 VAC 3 phase (2) Capable of closed loop speed control using feedback in the form of a frequency (from and encoder or ring-kit w/ open-collector speed sensor). (3) Ability to display measured speed (from speed sensor) and to allow set point entry in scaled engineering units of my choice rather than Hz or even motor RPM. (This would be for a web handling machine, so I would like to be enter speed set points in ft/min and have actual speed also displayed in ft/min). This will require the drive to allow me to enter a scale factor to relate feedback from the speed sensor to ft/min taking into account my gear reductions, roll diameters, etc. (4) Allow set point entry using a built-in interface on the drive itself (keypad w/ LED display) rather than requiring the use of an HMI (5) Ability to follow a master speed reference that would be supplied to the drive as a frequency. Any advice will be greatly appreciated. Thanks in advance, Paul [/INST] Please explore TechNote 581453 \\n </s> |
<s>[INST] Bootp useage over multiple network Summary: How do you Bootp across different networks ? ? ? Is it possible to Bootp to a VFD making a request on a 192.168.63.nnn network if I am on a different network........ 192.168.60.nnn Are there any recomentations when dealing across a facility with many different private networks used for isolation when dealing with a central Bootp Server. Any thoughts or comments are welcome. I have not been exposed to anything but RSlinx Classic and I am using BOOTP/DHCP SERVER 2.3. Thanks for any assistance. jim w [/INST] For your particular example, I KNOW if you set your computer's subnet mask to 255.255.252.0 (note the difference of the third quad from standard), you will be able to look across the entire .60, .61, .62, .63 subnet. \\n </s> |
<s>[INST] Powerflex 525 No Jog Reverse Summary: Jog Reverse not workingHi all, I have a Powerflex 525 hardwired for jog forward on Dig in 3 and Jog reverse on Dig in 5 , Jog forward works fine ,Jog reverse does not work. There is no frequency output and Dig in status shows there is an input at input 5 , If i switch the jog functions to Dig in 5 Forward and Dig in 3 to Reverse the forward works fine on Dig in 5 and the reverse does not work on Dig in 3. It seems jog reverse does not work at all on any input.Thanks [/INST] What is parameter 544 (reverse disable) set to? What is parameter 93 set to (10V bipolar enabl)? \\n </s> |
<s>[INST] Powerflex DC HIM Copycat - Firmware Revisions Summary: Can a parameter set from older firmware be loaded into a drive with a more recent firmware? I'm new to RA Drives and this question came up. If you have a HIM for the Powerflex DC with a set of parameters stored on it. After a customer has failure on the drive and installs a newer drive with an updated firmware version. Will the HIM correctly download the parameters into the newer drive with the updated firmware without errors? Thanks [/INST] nan \\n </s> |
<s>[INST] Fault Times and Power Up Marker We trying to make sense of the PF700's Fault Times. Is it possible to read the current value of the 'Power Up Marker'? It appears the value in Parameter 242 [Power Up Marker] is only updated when a new fault occurs. The thought was: if we had access to the real-time 'Power Up Marker' value we could determine the age of Faults 1-7 Thanks... [/INST] I suggest to take a look to the following technotes, to get infos about Fault time... Aid 46598 - Aid 63837 - fuzzy logic \\n </s> |
<s>[INST] powerflex 70 start-up After power is applied to my powerflex 70 drive, the him display shows Initializing on top line and connecting to on next line. The drive status indicator is flashing yellow, any hint's as what would cause this. [/INST] That means that the HIM cannot establish a comm link with the drive. Try removing and reseating the HIM in the pocket. Try removing and reseating the cover on the drive making sure the upper right-hand corner of the cover is pressed tightly against the frame. If those don't help, and you have another drive like this one, swap the covers and the HIMs as a unit. If the problem follows the covers, the problem is in either the cover or the HIM. Then try swapping just the HIM to isolate the problem. If the problem stays with the drive, the drive needs to be replaced. \\n </s> |
<s>[INST] Using a VSD with a Demag conical brake motor Summary: Demag Conical brake motor can be used with an ABB ACS 800 drive, is there a suitable Rockwell productA Demag conical brake motor can be used with an ABB ACS 800 drive. Is there any AB Powerflex Inverters which are suitable for this task? [/INST] We've actually done this with PF753 drives, without knowing before hand that the motors were conical rotor. The crane bridge had 6 motors running off one PF753, and it worked surprisingly well. Only at the slowest speeds did the rotors not release. It took some tuning of parameters P60-P63 to get something the operators thought was good. Never mind that it was VERY qualitative and I think they said one test run was better than another despite the fact that we'd not changed anything that time. \\n </s> |
<s>[INST] Safe Torque Off monitoring with redundant output Summary: I am using a PF755 w/ STO option and want to maintain a Safety Category 3. The STO board's inputs are SP+ and SE+. In Logix 5000 I am planning on using the redundant output instruction (1734-OB8S) w/ one output going to SP+ and the other going to SE+ and the Hardware Enable at TB1-1. The manual says that there is not a monitoring contact w/ the STO. Do i need a monitoring contact for use with the Feedback 1 and Feedback 2 to maintain Safety Catagory 3? If not, should i use anything on FB1 and FB2? [/INST] It depends on whether or not you have your PF755 connected to the Logix platform to use CIP motion or if it is connected as a regular drive. In CIP motion, you are not permitted to use any of the drive I/O cards. As a regular drive, you are. You could then task one of the outputs to be the monitoring contact. I agree with you, Rockwell made a mistake not putting the monitoring contact on the STO card. \\n </s> |
<s>[INST] Motion control EDIT: removed weird formatting for font coming from translation cut/paste -FL hello everyone, I would like to know if anyone can help me with handouts, manuals or tutorials on how to work with motor control. where I am currently working we have kinetix of different models such as: 350, 6000, 5700 and even kinetix 2000 working in sercos network and ethernet ip. I would like to look at the program and understand each motion block, know what each one does so that I was able to solve problems. thanks in advance [/INST] wafer motion-rm002 motion-um003 motion-um001 motion-um002 motion-rm003 \\n </s> |
<s>[INST] Powerflex 700 speed control, speed units RPM I have a couple of issues using ControlLogix to control the speed of a PF700 with parameter 79 (Speed Units) set to RPM. The desired speed is set from the PLC logic by assigning a value to the controller tag MyDrive: O.CommandedFreq. One might expect this value to be in RPM, but it isn't. By trial and error I find I need to multiply the desired speed in RPM by 13.654 before storing it in CommandedFreq. This gives a 'Commanded Speed' (parameter 2) in the drive which corresponds with the desired speed in RPM. Where does this scaling factor come from? I'm not getting a linear response from the motor in terms of the actual speed achieved. If I set CommandedFreq to 5000 then I get a Commanded Speed (P2) of 366.2RPM and a Speed Feedback (P25) of 366.2RPM - perfect. But a CommandedFreq of 10000 yields a Commanded Speed of 732.4 (perfect) but a Speed Feedback of 754.8. P23 Speed Reference always matches the Commanded Speed, but the motor is actually turning at the speed indicated by Speed Feedback. So the faster I ask it to go the more it overspeeds. Are there some drive parameters which need tweaking to address this? If anyone can point me at some relevant doc for this stuff that would be a great help. None of the manuals make any reference to the .CommandedFreq units being anything other than Hz (or implicitly RPM if Speed Units is RPM). Mike [/INST] Helpful chap at Rockwell TechConnect may have solved this for me - doing some calcs & checks, will post solution if it works. Mike \\n </s> |
<s>[INST] power flex drive 753 failure after power recycle We have using approx fifty power flex drives in our plant and have had little trouble until the other day. We had a scheduled power outage with the power company they disconnected all phases at on time and repowered us after one hour. after that we noticed we had one drive 55 kw rating that did not power back up and are fed from the same line as ones that did. we checked voltage at the drive line input and is fine. we are at a loss as what and why this has happened. [/INST] Do you get absolutely nothing? No cooling fans, no HIM light, nothing at all? Have you inspected the interior of the drive? Has a capacitor failed catastrophically or vented (look for goo where no goo should be)? Do you have a spare control board? Install that and see if the drive powers up. \\n </s> |
<s>[INST] PowerFlex 70 Accel 1 & Accel 2 timing I have a PF 70 EC on Cnet and want to use Accel 1 and Accel 2 inputs to change the machines ramp up time part way to the full run speed. example: I want the machine to ramp up from 0 rpm to 115 rpm with a 5 second Accel and then turn Accel 1 low and Accel 2 high and ramp up from 115 to 130 rpm with a 20 second ramp time. My question is what will happen when the drive is ramping up to my 130 rpm run speed with the Accel 1 input high and I put Accel 1 low and then turn accel 2 high part way through the ramp up? will the drive fault or will it just accept the new acceleration time? [/INST] Zazzin,i think it should be working.The drive will actually ramp up to the desired speed as soon as you switch over to the next accel time.Hope it works. \\n </s> |
<s>[INST] Kinetix 5500 Home and registration input Hi i have a Kinetix 5500 drive where i require 2 registration sensors and a home switch. with the Kinetix 5500 drive you have 2 inputs available and these inputs can be selected as the functions DI1 - Home & Registration 1 DI2 - Registration 2 When using the Home & registration input is it plausible to use 2 sensors for 1 input or is there a better way by using another input for the 3rd sensor on remote IO or the main PLC rack ive tried searching the RKB but cant find anything Thanks Andy [/INST] Hello @ndy. I never tested 2 different senors on the 1st input of the K5500. Look in the manual 2198-UM001M to see if the internal digital input circuitry is compatible with the sensors that you would like to use (Page62). To avoid damage on the output of the 2nd sensor if the 1st one is active , you can use diodes. But I never test it. The other options are the following, use a PLC digital input to generate the Home input. but in this case you have to create you're own Homing cycle. Or use a time stamped input to create a Soft registration input (more complex to implement), the 2nd option is not as good as a real registration for very dynamic application. regards \\n </s> |