<s>[INST] How to gain full torque from motor at low speed I have an inverter 1305-3HP which I scaled 0-10V = 0-50HZ for a 4 poles motor. It has been observed that the torque of motor at 1-3HZ is not sufficient to turn the load smoothly. Kindly help me which parameters should I adjust to compensate it and also that how I can program that drive for “Sensorless Vector control”. [/INST] Unfortunately, the 1305 is a Volts-per-Hertz drive, so it cannot be configured as Sensorless Vector. :smileywink: This is the why it isn't easy to get torque and stability to these low frequencies. Only way you may try to play with DC boost (par. 9) to add some DC voltage to the running drive at low frequencies.Take a look to the User Manual, pages 5-18 / 5-19. Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] ULTRA 3000 INDEXING DRIVE I have an Ultra 3000 Indexng drive in service that has started going to home instad of performing the indexing move. The drive has been in operation roughly 6 months with maybe 150 hrs of usage. The program for the drive is used on several other machines and has no problems; 1 year in service. The machine is at my customer's facility so I do not have access to it. Has anyone else seen this issue or have any advice they could pass along?Thanks [/INST] Hi, this is really strange :smileysurprised: , anyway, are you sure nobody has changed something in its configuration? Do you command actions via Digital Input or network ? Maybe something has changed down there and now the command normally used to index is really used to Start Homing... I think it will be needed to connect the Ultraware in it an see what happens... - fuzzy logic \\n </s> |
<s>[INST] Axis Status bit or data tag Summary: Motion group axis status informationHi everyone, I have configured some powerflex 755 drives in the ControlLogix program motion group. I can see that there is Status category under the Axis properties. Double click the status category and in the open window, it shows Motion status, Axis status, and Digital I/O. There are some items under Axis status, such as DC Bus up, Position Lock, standstill, etc. I try to bring the Axis Status to the HMI display. Where can I find the bit or data tag related to these status in the PLC program or manual? [/INST] It is <NAME OF AXIS>.DCBusUpStatus, .PositionLockStatus, .VelocityLockStatus, etc. In your case the name of the axis would be MA_TFR01. \\n </s> |
<s>[INST] Kinetix 5500 excessive velocity fault Summary: Two drives in same motion group fault simultaneouslyWe have a machine with four 2198-H008-ERS in the same motion group, all with VPL-B0752F-P motors. The power, bus and control are connected with the bus system. In the ladder logic, they all are treated as if they were the only drive, although they operate as pairs. We are experiencing Excessive Velocity Error on an erratic basis(once or twice per shift). The last event was that both drives in one pair faulted at exactly the same time. This may be a clue, just not for me. We have adjusted the Velocity loop parameters in various ways to try to eliminate these faults. [/INST] I would try increasing the velocity loop error tolerance and let the position loop error tolerance catch the real fault (jams, etc.). \\n </s> |
<s>[INST] Powerflex700 fault 64 Hello, I've a pf700 with 37kw, 60A, 150 hz, 9000 rpm, I configure pf with quickstart guide, and when it start the motor rotate a little and appears fault 64. What can be wrong? [/INST] Welcome to the Forum ! Here a screenshot from the User Manual. - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] I would like to know if I can install RSLogix 5000 V20 (or another version) on a PC with Linux operating system? [/INST] RSLogix and Studio 5000 are not supported for the Linux OS distributions. You could use software like WINE to try and make a compatible environment, but honestly I can't see how it would be worth the headache. Just stick with Windows.\n </s> |
<s>[INST] Factory settings Maxpak III Summary: How to reset to factory settings Hello, I have a CD drive Reliance Maxpak III, and I want to restore factory settings originates. As I can do from the keyboard? Thanks [/INST] Hope somebody will be able to help on that, I'm not, unforunately. In the meanwhile, I may suggest a website where you may find all the legacy Reliance drives literature. http://www.reliance.com/literature/index.html Just drilling down under Drives, Manuals, DC Legacy Drives, MaxPak III, you might find a manual with some indications. - fuzzy logic \\n </s> |
<s>[INST] Save/Record Fault Code of PowerFlex 700s By Ethernet/DeviceNet or ControlNet, is there any solution to record the fault code in RSLogix 5000? thanks lots [/INST] I'm looking at old code we used on a standard system. We used Ethernet and issued a MSG command after the Drive:I.Faulted bit goes true. The MSG command was CIP Generic, service type Get Attribute Single, Service Code e, Class 97, Instance 1, Attribute 0. Destination is a UDT; construction shown here: \\n </s> |
<s>[INST] Cabinet to install PF755 Summary: Cabinet to install PF755Hi, I would like to know if rockwell Automation supplies a box or small cabinet as option to install the drive into it, it's about PF 755. if it's possible i want to have its picture or datasheet. Thank's [/INST] There is an option for a packaged PF755 drive. I suggest you avoid it unless you have both a lot of time and a lot of money available. Look here for more information: https://literature.rockwellautomation.com/idc/groups/literature/documents/td/750-td002_-en-p.pdf Even though these are called FasTrac, they are assuredly not fast. My company builds electrical panels; the local Rockwell representative often asks us to build equivalent packaged drives because Rockwell's lead time is so long. Rockwell does not sell enclosures for drives. I'm guessing you already have the drive in hand and now need to make a complete system. If you need more assistance from us users, I suggest you give us more information. You said PF755 but neglected to say how big it was. The PF755 comes in 7 frame sizes that are wall mount. The more information you give us the more detailed the solution we will be able to suggest. Hoffman, Saginaw, and Rittal all manufacture nice enclosures for drives. Do not forget to do heat calculations to see if you will need ventilation or air conditioning for your system. \\n </s> |
<s>[INST] Offset during dynamic gearing between virtual axes Hi Everyone , I would like to gear 2 virtual axes during either a run or before axis moves. In order to do that , I used following solutions but still got an offset when it was geared with ratio other than 1:1. 1) Using MRP Absolute to move slave axis to master's position then latch gearing. (1:1 it works but if the ratio is different , there is always big offset) 2) I calculated the actual position difference between master and slave and use this as failure to make relative move with MRP. ( I got 0.08 position difference at the end which might be ok but still not precise enough for me) ** Note : Offset happens when gearing ratio is different than 1:1. Is there any more reliable alternative to do it ? Thanks in advance. Sertac [/INST] Hello srtc the big advantage of virtual axis is that they are perfect (not position or velocity errors). So the issue that you have can not result of a bat tuning or mechanical setting...etc. It is certainly. a MAG setting or axes setting. could you give more details on this please ? to answer your 2 points: it is normal that if you do not have a 1:1 ration you will see a difference on your axes. are you using Ratio or Mastercount/slavecounts ? what ratio format have you selected ? are you using the clutch ? all those parameters will impact the gearing relation between your master and your slave. review the Logix 5000 Controllers Motion Instructions (rockwellautomation.com) manual (p112 to 124) to know more about those parameters. TIP: you can also use MAPC to do gearing, regards \\n </s> |
<s>[INST] Speed reference on 753 drive Summary: Too much speed on the motorHello everybody, My motor is running at the speed of 55Hz, but my reference speed is set at 50Hz, what could be the problem? Mokhoele Mahao [/INST] Mokhoele, it would take very little time to troubleshoot this if you would include the DNO file from DriveExecutive or whatever file format CCW uses for VFDs. You've given precisely zero useful information to help us help you. If you cannot get a DriveExecutive file or a CCW file for this VFD, you will have to tell us all about this application. How is the drive configured (flux vector, sensorless vector, V/Hz), what feedback, command speed source, and on and on. there are dozens of parameters affecting the operation of the VFD. You haven't even told us what the load is. Best chance for us to help you is to give us complete information about the application. \\n </s> |
<s>[INST] Powerflex 700 series A rev. 3.003 doesn't stop (error F24) Hi everyone. I have problem with one powerflex 700 drive. It happens when the drive tries to stop. It decelerate on 30 RPM in a few seconds and after that goes on 60 RPM and continue to run on that speed until error message decel inhibit (error F24). Any ideas. [/INST] User Manual gives indications about this fault... The drive is not following a commanded deceleration because it is attempting to limit bus voltage. Actions: 1. Verify input voltage is within drive specified limits. 2. Verify system ground impedance follows proper grounding techniques. 3. Disable bus regulation and/or add dynamic brake resistor and/or extend deceleration time. Refer to the Attention statement on page P-4 for further info. Parameter 238 bit 6 is the location to turn this fault on or off. By factory defaults this bit is on.Parameter 161, 162 and 160 are the bus regultation parameters that can be adjusted for application if the bus regulation is desired. See also Reference Manual for more infos about Bus Regulation. - fuzzy logic \\n </s> |
<s>[INST] axis feedback status Hi guys, When giving an MAG (motion axis gear) instruction, does anyone know if there is a (timing) difference between:Axis.gearingstatus and the MAG.IP status bit? also, when giving an MAM instuction (motion axis move), is there a (timing) difference between:Axis.MoveStatus and the MAM.IP status bit? cheers,C [/INST] From my testing, doing a trend on these status bits, there is no time delay that I can see between the motion control bit and the status bit. \\n </s> |
<s>[INST] Power Flex 753 - Change output relay configuration of Fault Summary: In the parameters of RO0 output from port 4, I want to set fault state of parameter 935, but it does not give me the option.How can the relay output of a PowerFlex 753 I/O module in port 4 be programmed to change state based the fault status of the drive? What status parameter would you link to monitor the relay output to change. In the parameters of RO0 output from port 4, I want to set fault state of parameter 935, but it does not give me the option. [/INST] If you go to slot 4, parameter 10, that is the place you configure the R0 output. The first thing you have to set is what port will provide the information. You need to set port 0, the drive itself, to get drive fault. Then you select which parameter of port 0. For your situation, you pick 935, Drive Status. Finally, you pick bit 7 - Drive Faulted. I think you missed setting port 0. If you set the port to 4 (the IO card itself, you don't get the configuration you want. Setting it to port 0 does. Let us know if this worked. \\n </s> |
<s>[INST] smc 3 dip switches Im trying to find information on the dip switches for the smc 3 i cant find any literature on this drive on ab.com [/INST] Try to take a look to the following technotes: Aid 24364 - Aid 35399 - fuzzy logic \\n </s> |
<s>[INST] PF 753 FV mode Fwd Rev speeds not same Summary: Forward and reverse speeds do not match for same POT setting I am using a PF 753 in FV mode. Speed and Torque references provided through potentiometers. Motor runs fine up to 60hz in fwd but only about 36hz in rev. Any ideas why? I am considering reversing contactors to facilitate direction change. [/INST] if you have a DNO file from DriveExecutive or CCW, can you upload it? \\n </s> |
<s>[INST] Kinetix 600 IAM Replacement Issue I had a drive with a E35 fault but we did not have any supply voltage problems. After replacing the drive the display on all the drives in the rack would only cycle up to phase 3 and never go to 4. We troubleshot this for a couple hours but to make a long story short we tried 2 more drives before we found one that worked. We have not been able to explain what may have caused this....bad drives......wrong revision [/INST] AID 48895 FYI \\n </s> |
<s>[INST] 1395 DC We bought a cermona lathe in Canada and moved it to Russia . It has a 1395 DC drive and a SLC 500 PLC on it. Will it work on 50 HZ. Jeff [/INST] Yes, the 1395DC will work at 50 Hz. Take a look to the essential publications from this technote: Aid 48544 Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] PowerFlex 525 and SafetyActive bit Summary: How does SafetyActive work? Hi, I have 37 PF525 and we are trying to get some kind of feedback from the drive that the safety (S1 & S2) is enabled. Online chat tech support has told me to use b006 bit 5, which is the DriveStatus register. Bit 5 is the SafetyActive bit. I monitor this bit, but is state never changes. I can remove 24VDC from S1 and S2 and the bit is still off. It never turns on. Is there a setting to turn this bit on? Thanks, Denis. [/INST] Denis, only when both of the Safety Inputs S1 and S2 are de-energized (no matter the drive is faulted or not), the bit 4 -Safety Active of parameter B006 [Drive Status] will be ON. It is bit 4, though. - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] Electrocraft DDM-030 Hi, My company has an old printing press with a Electrocraft drive DDM-030 servo drive that seems to be acting up. I am trying to find a manual on it but I have been having no luck. In my searching, I found a few things that make me think that Electrocraft (or at least this line of drives) might have been taken over by Rockwell / AB. I was wondering if anyone here might be able to tell me where I could find a manual for this drive. Thanks and best regards, Paul [/INST] Paul, as far as I know, Electro-Craft DDM-xxx Servo Drives could be replaced by 1398-DDM-xxx (AB Ultra Series, it is also obsolete) ; I think you could search for 1398-DDM manuals instead, inside the Literature Library website. Here some infos about Electro-Craft / Rockwell Automation : http://www.rockwellautomation.com/legacy/motion-control/electrocraft.page - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] PF 400 drive communication to a CompctLogix Controller using MSG My applications requires reading the current from a PF 400 through an MSG block but I don't know how to set it up. Can you give me help? [/INST] See the Explicit Message examples on the Communication Module User Manual... Ethernet/IP - chapter 6Devicenet - chapter 6 - fuzzy logic \\n </s> |
<s>[INST] Kinetix6k how to read the motor data coming from the servo Hi allhow is it possible to read the motor data sent by the RS485 chip in the servo back to the Kinetix 6k?I would like to check if the motor sends the correct data which I can find on the plate.I was trying to use the Drive Executive but apparently it's made only for PowerFlex.With the Drive Explorer it didn't work also. Any suggestions? Best regardsUli [/INST] There is no published way to access the RS485 communications between the drive and motor. The drive checks to see that the attached motor catalog number is the same as the motor under the Drive/Motor tab of the Axis Properties. If these do not match then the SERCOs network will not boot up. You can connect to the drives using either DriveExecutive or DriveExplorer, but not through the SERCOs card. It requires either a 1203-USB or 1203-SSS to connect to the round mini-din connector on top of the IAM next to the SERCOs connectors. All this will allow you to do is see the drive parameters. \\n </s> |
<s>[INST] Kinetix 5500 FLT M02 Motor Data Range 17 I have a Kinetix 5500 servo drive with a fault Init FLT M02 Motor Data Range 17. I can't find anything that tells me what that fault is. [/INST] Hello Carbo There is a mismatch between the encoder and the motor data file Is it a new installation ? if it's the case check the encoder wiring (data Chanel or DSL) if not inverted. you can found detailed descriptions about the M02 fault in our knowledge base QA39044 or QA32377 Regards \\n </s> |
<s>[INST] Fault E12 Summary: Kinetix e12 fault with Safe Off What is an E12 fault. It does not show up in the Kinetix fault list? [/INST] \\n </s> |
<s>[INST] Communicate Power monitor 3000 with MODBUS RTU Summary: As PM3000 Manual claimed that it supports MODBUS protocol, but i got exception code 2 when reading the registers according to Data table. As PM3000 Manual claimed that it supports MODBUS protocol, but i got exception code 2 when reading the registers according to Data table. Are there some body who has communicated wth PM3000 via Modbus successful? Any hints are highly appreciated . Many Thanks! Min [/INST] Welcome to the Forum ! I suggest to post details about communication settings you're using for your tests... also add some infos about wiring and connected device. Details of items you're trying to read could also be useful for Forum's users in trying to help. - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] 1305 frequency The frequency on my 1305 always resets to 0 after a shutdown. Can I get it to resume to an existing frequency that it was when powered back up? [/INST] pat, I guess you're using the HMI to set your Frequency Command, by the Increment / Decrement arrows, right ? Then, cycling power to the drive will set the frequency command to the value stored in HIM memory. :smileysurprised: Pressing both keys simultaneously stores the current HIM frequency command in HIM memory. The Speed Indicator LEDs will flash momentarily to indicate a successful save (if speed is above 20 percent); so the next time you restart, you will start from that value... obviously it cannot be the same as it was before the drive was powered down, just a fixed starting frequency you may decide. Hope this helps, - fuzzy logic \\n </s> |
<s>[INST] Migrating from Kinetix 300 to 5100 I was told that the 300 was no longer available and that the 5100 was the direct replacement. Is there any programming that would need to be done when I do the swap? I apologize if it's a silly question but I have never upgraded these before and I appreciate any advice/help anyone can give me. [/INST] Hello Jeff You have a very valid question ! not silly at all. So you are right the Kinetix 300 have a lifecycle status set to End Of Life. So it's a good idea to consider future replacement. For that Rockwell Automation have prepared a document to facilitate the migration process this is the link to this document : Kinetix 300 to Kinetix 5100 Servo Drive Migration Guide (rockwellautomation.com) So I strongly recommend you to review this document and see if you feel capable of doing this. If not, Rockwell Automation can always assist in those migration process, for that you should engage our local organization or a distributor. Let us know if you need more details Best regards \\n </s> |
<s>[INST] PowerFlex 525 won't communicate with CCW or Logix 5000 Summary: PowerFlex 525 communicates with controller but not CCW or Drive tab in Logix 5000Hi Guys, I seem to have an issue communicating to my PowerFLex 525's via CCW or the drive tab in Logix 5000. I'm trying to change some parameters. I have 5 drives and all of them do the same thing. The PLC is able to communicate without issue. Can anybody think of a reason why my PC is being blocked? Thanks [/INST] What do you see in RS-Linx? Do you see all devices there? Is this the first time this computer has used CCW to communicate with Rockwell devices over Ethernet? It's possible your computer's firewall is blocking CCW. What PLC is working for you? Can you talk with that successfully? What version of CCW do you have? Have you installed the latest drives database for CCW? \\n </s> |
<s>[INST] Mam error code Summary: err 05mam err 05 means what? who meet this and solution, thanks! [/INST] with this little infromation you should not expect any reply \\n </s> |
<s>[INST] Motor cable length restriction of PF753 with 1321 reactor Hi, Checking this restriction on Installation Instruction, the following information confused me. Why a better insulation motor (1350V) has shorter cable length restriction that the other one (1200V) has? Terence Yang [/INST] Hi @Terence Yang, it looks like there is a typo inside that table. I'll double check with the Engineers just to be sure, and let you know. Thanks. fuzzy logic Please don't forget to use the LIKE button and highlight the decisive answer : REPLY > Make Best Answer \\n </s> |
<s>[INST] Local and Remote HIMs not booting Summary: A pair of Enhanced HIMs will not boot on powerup with PF70 I went around the block all day on this one. I ended up with a less than optimal solution. What I have is a 2HP Powerflex 70 in Frame B. I wanted to put a 20-HIM-A6 in the local Port 1 slot and a 20-HIM-C6S remotely. These are both Enhanced HIM devices. They refused to boot - backlights come on, but no boot. If I remove either HIM the other will boot and I can reinstall the removed device and it will boot, as well. All devices communicate when they are booted. Why will these two not boot on powerup? I can get an A3 and the C6S to boot properly, but I really wanted the A6 in the Local Slot. Ideas? [/INST] What firmware are the HIMs? We've discovered a bug with firmware 2.003 for A6 HIMs in that they will not scroll if more than 3 items are to be displayed. I wonder if you have discovered another firmware problem. For that matter, what is the firmware of the drive? Is it up to date? \\n </s> |
<s>[INST] Powerflex 523 - Using Preset Frequency Set Points Hello, I could use some assistance in setting up a PowerFlex 523 for a blower application with multiple preset speed set points. From a digital input perspective, it needs to have just one 'run' command to start and stop the drive. According to the manual, three other inputs can be setup for preset frequencies. Terminal 1 is jumped to terminal 11 Dig input 2: Would like to use this as an 'run 'input. +24 VDC at this terminal should start the drive. It should then look at the preset frequency bits to determine the speed reference. Removing +24 VDC should make it coast to a stop. Dig input 5: Preset frequency bit 1 Dig input 6: Preset frequency bit 2 Dig input 3: Preset frequency bit 3 Here are some of the current settings: P43 – 0 Hz P44 - 60 Hz P45 – 1 P46 – DigIn TrmBlk P47 – Preset Freq P48 – DigIn TrmBlk P49 – Preset Freq P50 – DigIn TrmBlk P51 – Preset Freq T62 – 2 Wire FWD T63 – Preset Freq T64 – Edge trigger T65 – Preset Freq T66 – Preset Freq A410 – 0 Hz A411 – 5 Hz A412 – 10 Hz A413 – 20 Hz A414 – 30 Hz A415 – 40 Hz A416 – 50 Hz A417 – 60 Hz With these settings, as soon as +24 VDC is applied on digital input 2, the drive starts and ramps up to 60 Hz. It coasts to a stop once the 24VDC is removed. It completely ignores the preset frequency bits. This is probably a configuration error as two different drives are behaving exactly alike. Please let me know what needs to be changed so the drive uses the A410..A417 values for the speed. Thanks [/INST] Welcome to ENGAGE, @Sid Gopal ! You should change P049 and P051 to a different Speed Reference source than the one selected for P047 You can for example set P049 to 1 and P051 to 2 No two speed reference can have the same value. Cycle power to the drive after setting the parameters. Hope this helps, fuzzy logic Please don't forget to use the LIKE button and highlight the decisive answer : REPLY > Make Best Answer \\n </s> |
<s>[INST] Ultra 3000i E55 fault Ultra 3000i E55 fault.when power on/off ,it wii show E55 error code. [/INST] Two main possible reasons: Personality EEprom Data Corruption, due to noise - not field fixable, you must return for repair (prevention is possible, verify proper shielding and grounding) If you have a small unit (.5kw, 1kw and 2kw) problem could be related to the 5vdc Auxilary Control power voltage.If it is not a precise 5.1vdc and free from noise, it may generate E55, User Parameter Checksum. You may try (for testing purpose) to remove the external 5vdc supply voltage from pins 2 and 3 of CN-1, power the unit and see if E55 occurs again. If not, the 5 Vdc external power could be the problem. Using a CN-1 BreakOut Board 2090-U3CBB-DM44 that has a filter inside could solve the problem. If you have a sercos drive, use a 2090-U3CBB-DM12 instead. Hope that helps... - fuzzy logic \\n </s> |
<s>[INST] 2364F RGU Notch filter specification to meet IEEE-519 harmonic standard Hi all,is there anybidy who are familar with this issues?Because many customers need our common bus drive system to meet IEEE-519 harmonic standard,and I refer to manuals which shows that a notch filter will be needed at front of RGU .But I don't know the specification for each RGU.Many thanks to everybody here firstly. [/INST] I believe this is old product, I have not heard of a 2364. The current active front end is a 700AFE or a little older, but still available 1336R. The 1336 is for smaller applications and the 700AFE is for higher current. The sizing is done based on current requirements. I have only done this with single motor applications so the sizing is easy, for multi-drive applications the easy way is to get Rockwell drives managers to help out by giving them the motor sizes on the application. These do not require a notch filter on the input. The other option for IEEE-519 is a harmonic filter. TCI has one and MTe has one to meet IEEE-519. These would be typically be smaller applications as well where you will not have a lot of regen. \\n </s> |
<s>[INST] SMC Flex ethernet/IP integration Hello ! I was thinking in integrating SMC flex with 20-COMM-E (ethernet/ip) in a project but wasn't able to add them to my IAB project. I know they can work, but it's very extrange that they don't appear in the list of ethernet/ip devices !!. If somebody knows anything about please reply.Thanks !! [/INST] just check whether your ip address configured in i/p devices is correct.it may be a reason. \\n </s> |
<s>[INST] PF 753 on conveyor belt Summary: any advice to improve the performance of the Drive ? [/INST] You're going to have to give us a lot more information if we're going to be able to help. If possible, start by uploading the DNO or CCW file. Some information about the application will also be useful. \\n </s> |
<s>[INST] the replacement for 2094-BM02 Our system is using 2094-BM02. Now, 2094-BM02 was broken. Can we replace 2094-BM02 by 2094-BM02-S ? Do we need to change anything in program of Controllogix ?Please help to advise detailedly the difereence between 2094-BM02 and 2094-BM02-S [/INST] 2094-BMxx drives without safe off are Silver Series products. The –S (Safe-Off) Kinetix 6000 is a direct drop in replacement; the Kinetix 6000 drive firmware is the SAME for safe off or non safe. So, as far as I know, you may replace it without changes in ControlLogix program.... Hope this helps, - fuzzy logic \\n </s> |
<s>[INST] Control of Ultra 3000 I am going to use ultra 3000 index drive to control a movement on condition from the first spot to the second pot and back to the first spot.Back and forth repeatedly.I want to use preset position mode.I can set the second spot as preset postion 0 and the first spot as preset position 1.I also need to set drive input to active drive move to preset positon.From the manual,it said i have to set digial input 8 as preset select 0.When it is off ,drive controllded motor moves to preset posion 0.When it is on motor moves to preset posion 1.I donot want to control a movement between two places deponding on change of status (off /on)on only one input.I'd like to control a movement just when one input is on. When it is off ,nothing to do.Can I use preset posion 1 and 2,also preset select 1 and 2 on digital input 7 and 6?So I donot need to use preset posion 0 and preset select 0 for input 8.Thus,only when input 7 is on goes to preset posion 1 and only when input 6 is on goes to preset position 2 and back and forth.Can anybody help me with this?Thanks [/INST] This thread has been started also in the Motion Control Board (that is the right place :smileywink: ) Here the LINK to that thread, containing also a reply. - fuzzy logic \\n </s> |
<s>[INST] Error Connecting to PF70 Using Drive Executive over RSLinx I have connected to several drives using Drive Executive Lite and RSLinx over an ethernet link to 20-COMME adapters in PowerFlex70 drives and configured them. Now I am getting an RSLinx error when trying to connect that says it cannot upload the device definition from the path. It also says: 'The following error is created by RSLinx: DTL_E_Fail, I/O completed with errors.' I can access other Rockwell devices online from the same link. Can anybody shed any light on this? [/INST] Hi rtissier, and welcome to the Forum ! Try to take a look to the following Knowledgebase technote: http://rockwellautomation.custhelp.com/app/answers/detail/a_id/58381 Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] MAM instruction 'stuck'??? Had a weird one at a customer site yesterday (about 4000 miles away from where I'm sitting unfortunately). Machine hasControlLogix, lots of servos & motion control. One particular axis would not move from one particular MAM instruction. Other MAM instructions on the same axis worked fine. The one which wasn't working had it's EN output set and all other outputs clear. Toggling the rung-in condition made no difference to the instruction or its outputs, it just wouldn't do anything. Other MAM instructions in the same routine operating on the same axis with exactly the same parameters worked fine. In desperation I got them to upload/download and it was then OK. Anyone had anything like this happen? It smells like a ControlLogix bug. Mike [/INST] Digging back in time I see that I've come across this before (different machine - one I was programming unlike the one I was trying to support yesterday). I actually raised it as a case with Rockwell and got this answer: Before you execute a MAM instruction, put an interlocking tag in there indicating the Axis_Servo_Drive.ServoActionStatus Boolean is a 1. Are you sure no other instruction may not be completed before the MAM is executed in the program? The instructions 'hang up' like this sometimes because during the scan when the rung is true, the axis cannot complete the instruction to be true. In otherwords, the .EN will stay true until the process of enabling the instruction is complete and the rung goes false. Thank goodness I keep my emails! Mike \\n </s> |
<s>[INST] Fails to control PF4M by RS485 Summary: RS485 Control PF4MController: CompactLogix L30ER Drive: PowerFlex 4M HMS Anybus communicator 7007 ( EtherNet/IP and Modbus TCP)S Step: Configure Anybus 7007 : 1:Read two register 8448 ( Logistic status ) and 8449 (Fault Code) 2:Write commands words 8192 (2000) /11000100110000 0011 0000 0001 0010 3:Write 8193 (2001) to set the run Frequency Step:Confirgure PF4M P106:5 P108:5 C302,303,304,305,306 As the result: PF4M doesn't run, and the 8448 is : 0000 1101 0000 0110 [/INST] nan \\n </s> |
<s>[INST] Powerflex 700 Error 75 I have a control panel that contains 2 Powerflex 700 Drives. Drive 1 we will call Rotation Drive, Drive 2 we will call Lifter Drive. The drives are communicating through a 20-COMM-D Adapter Card on devicenet of 14 nodes. Occasionally, say once every 8 hours, the Lifter Drive would freeze up with a fault [/INST] Inside the Forum there are many topics about this error... try first to search the drives Board using 75 as keyword... it could be related to noise problem...try to take a look to the following topic and indicated suggestions: http://forums.rockwellautomation.com/t5/forums/forumtopicpage/board-id/Drives/message-id/921#M921 About ferrite cores, see the Installation Instructions ... this document is for PF700s, but is similar for PF700 VC. Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Kinetix 6000 - How to add a custom motor? I have to set up a system in wich I need to add 2 pacific scientific servo motors to a Kinetix 6000 servo drives. I can't see the option in the RSLogix 5000 to use a custom motor. Anyone knows how to do this? [/INST] hlozano, a user cannot add his own a custom motor inside RS5000... you need to request your local RA representative to have the custom profile created for you, giving them all the datas about the motors. Anyway this procedure should be approved from RA before they start with analysis and profile definition... so I think it isn't quick to get...:smileysad: May also try to ask if there is already a profile created for your motor... take a look to the following thread: LINK Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] Kinetix 300 - setting Negative Motion Polarity over Ethernet/IP? Hi , I am starting a project for which I am leaning towards using a 1769-L24ER-QB1B CompactLogix PLC. I will also be using a Kinetix 300 servo drive (2097-V33PR3) for web tension control. The Kinetix 300 will be following a -10 to +10 VDC control signal from a Dover Flexo Automatic Tension Controller. I’ve used the Kinetix 300 in this manner twice before and it worked great. The one thing on this job that I have not done before is that I would like to be able to use ethernet comms from the CompactLogix PLC to set / reverse the direction (counter-clockwise/clockwise) that corresponds to a positive / negative control signal. On my previous two projects, I was able to change this manually by using MotionView OnBoard to check (or uncheck) the checkbox for Negative Motion Polarity (on the MotionView | General tab). Now, rather than having to log on to MotionView, I'd like to be able to control this setting from within my PLC program. I have added the 2097-V33PR3 to my RSLogix 5000 project IO tree, but when I look through all the tags that came along with the Drive Instance, I don't see anything that resembles a Negative Motion Polarity setting. Can anyone tell me if / how I can get at this setting? Also, I have read that the 1769-L24ER-QB1B CompactLogix PLC that I plan on using does not support Integrated Motion over Ethernet/IP, and I am aware that there are CompactLogix PLC's that do support this. If the only thing I want to do with this drive over Ethernet/IP is to change/set the Negative Motion Polarity setting as I've described above, do I need support for Integrated Motion over Ethernet/IP? Thanks in advance, Paul [/INST] The K300 does not use CIP motion, so using the L24 processor to control it is not a problem at all. I've used the K300 with CompactLogix successfully for position control. The accelerator toolkit has some nice code that mimics CIP motion commands. I do not know specifically which command would do the negative motion polarity though. \\n </s> |
<s>[INST] Kinetix 5300 Fault - PWM Frequency Reduced Hello, When I trigger the MSO block of the Kinetix 5300 drive, I get the 'Physical Axis Fault - PWM Frequency Reduced' error after a short while, even if I do nothing. I couldn't find anything about this problem and its solution in the docs. Does anyone have information? [/INST] Hello Gamze, This is a very strange fault indeed, because you can't adjust the PWM, so it must be a protection . It seem that the system foldback due to an overtemperature... but never seen this before Some questions for you : Is it a new Drive ? Check the drive temperature (you can check the Drive Temp on the drive Web page.) did there is any load attached on the motor ? if yes disconnect the motor from the load. and test again Run an Hookup test load disconnected and them an autotuning Make also sure that you have the latest FW on the drive. What is the drive and Motor ref ? Regards \\n </s> |
<s>[INST] Servo Motor Swapping Question We have a machine currently using an Allen Bradley kinetix motor (MPL-A320P-MJ22AA). A few years ago we had ordered a replacement/spare motor for this, not sure from who or when exactly, but its has a different part number (MPL-A320P-MJ72AA). This new motor has different connections on it for control and power and now we actually need to use this motor. Currently this motor is static and the cables for power/signal run from the motor to a Kinetix 6000 drive. Is it as simple as just getting a new set of cables that fit these new connectors on this new motor and drive and just replacing it all out? I was looking at the manual for this family of motors (https://imgur.com/a/BxWuX) and was looking at the different connectors and what pins lead to what and not everything lines up perfectly. Does that matter? Is it worth just trying , or is there a risk to damaging the drive/motor if the cables arent correct? If its just a matter of getting new cables, which cables do I need to get. A push in the right direction is all I really need, but the more information I can use the better. [/INST] The switch from 2 to 7 in the part number is when AB went from the bayonet connector to the SpeedTEC connector. I think they made short jumper cables to go from bayonet to SpeedTEC, at one point. As you suggested, it's probably easier to get a SpeedTEC set of cables and re-wire the drive end. \\n </s> |
<s>[INST] Kinetix 350 2097-V33PR3-LM Summary: Kinetix 350 2097-V33PR3-LM on single phase 208Will a Kinetix 350 2097-V33PR3-LM on single phase 208 drive a TLY-A2530 motor? Does the drive require all 3 phases? I keep getting a Feedback Loss. [/INST] You'll be power-limited but should be able to run the motor. Feedback loss is unrelated - you have a feedback problem. \\n </s> |
<s>[INST] Powerflex 700s Phase II - Disable Motion Control. We have a Powerflex 700s phase II firmware 4.002, but the enconder card is burned. We want to disable it to use the Drive wihout motion control. We try some configurations found it in the web, but the parameters mentioned are different of the parameters that we have in the Drive. When we start it from the HIM, the Drive stop immediatly but we don't have any failure. We changes the parameters: 222 - Sensorless [Mtr Fdbk Sel Pri], 223 - Motor Sim [Mtr Fdbk Sel Alt], 485 - V/Hz [Motor Control Mode]. We don't have any failure before we try to start the Drive. Any sugestion or Do you know if is it posible to use it whitout motion control? [/INST] Parameter 677 stop owner should indicate where the stop command is coming from. This should help in tackling this issue. Also you can check bit 30-28 in Parameter 152 [Applied LogicCmd] to determine how the Speed Reference Select Inputs has been set to the drive. Parameter 27/28 will need to be checked along with Parameter 10/12.\n </s> |
<s>[INST] PowerFlex DC Speed Regulator and Currrent regulator update rates Hi Everyone Can anyone give me the value for loop update rates for PowerFlex DC.I just need to consider the drive response for an application. Thanks in advance [/INST] Did you already have a look to the User Manual - App.A-3 ? Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] PF 700 F5 Fault - Summary: Is this a bad cap problem or do I replace the drive2009 PF700 throwing an F5 Fault the instant the motor is called to run. Troubleshooting guide says that if this happens when the drive is accelerating its most likely incoming voltage. . . Incoming voltage is fine, Input Waveform gets distorted when drive attempts to start the motor (as the pic below shows). Motor tests fine. Buss voltage is around 750VDC when not being called to run Is there a capacitor issue at play here or does the drive just need to be replaced [/INST] Sounds like your AC line is high. The DC bus on a 480V drive should be around 680V when stopped (480 * sqrt(2) = 678.8). From the screen shot of your power quality meter the AB voltage is almost 500V. Verify the taps on the incoming transformer are set correctly. \\n </s> |
<s>[INST] Difference between two type of motor Hi, we have many motors of MP Series, MPL-B4540F. But some motor have this serial MPL-B4540F / KK 24AA, some have this serial MPL-B4540F / SK 24AA. What is the difference between this type of motor. Are compatible ?Thanks [/INST] Welcome to the Forum ! I've attached a .pdf printout of the MPL motors Catalog number descriptions, taken from the Selection Guide, page 36... -KK24AA seems to me an incorrect catalog number, maybe -HK24AA? Hope this helps, - fuzzy logic \\n </s> |
<s>[INST] Powerflex 755 bus voltage HIM display does not match measured voltage Summary: Drive has failed, but HIM is not helpful in diagnosing the problem Over the span of a day, A 480VAC PF755 drive configured for CIP motion initially was reporting DECEL INHIBIT faults. Then it began reporting BUS OVERVOLTAGE faults. The end user noted that the bus voltage shown on the drive HIM reported 680V dc bus voltage. At the time of measurement, the line-in voltage showed 470VAC. The end user measured 240-300V bus voltage. That surprised me so much, I had him measure a second drive in the system. It measured 680V (or close enough to the HIM display of that drive not to question it). Remeasuring the bus voltage on the suspect drive, the user got 300V bus voltage, with voltage fluctuations as low as 0V. Replacing the drive got the system operational again. My concern is that the process values on the HIM are worthless. The HIM reported 680V bus voltage the whole time the user measured much lower. Any suggested explanations for this? [/INST] most likely the voltage feedback board is faulty therefore the HIM cannot display the correct value. \\n </s> |
<s>[INST] Powerflex 525 - Coasting after step logic Hi, I have a PF525 connected to a geared PM motor with an encoder mounted on the shaft. When I issue a step logic step after the profile finishes the drive creeps a bit. Any ideas why? Thanks, Thomas [/INST] Have you performed an Auto Tune successfully? If done properly, you may need to manually adjust the values of the following parameters 566 [Pos Reg Gain], 565 [Pos Reg Filter], 538 [Ki Speed Loop], and 539 [Kp Speed Loop]. I also suggest using the wizards on CCW (Connected Component Workbench). Have you utilized one of the StepLogic Setup Wizards? \\n </s> |
<s>[INST] 755 - No fault, no alarm - RUNs but produces no output Summary: Drive is ENABLED, but T1/T2/T3 always=0, HIM says there's an output Power the drive. (No on-site firmware updates have been done…running just as it came from the factory – 11.001) Reset the drive, and each peripheral device, to Factory Settings, using the HIM. Measure the DC+/DC- terminals, = ~680VAC Run the HIM-driven commissioning steps (with exception of autotune), and tell the drive that the HIM should be able to start/stop the drive. Attempt to run the drive. Drive front panel shows an output (in this case, 15HZ), and also it shows an output voltage (~120V). HOWEVER THERE IS NO OUTPUT ON THE T1,T2,T3 TERMINALS. Repeated the effort by loading a parameter set from a good drive, and running the drive from Drive Executive (directly connected to drive with ethernet cable between drive and laptop…just as with the prior good drive). All indications are that the drive is running and producing an output, but nothing shows on the output terminals, wired to a motor or open loop. Removed SafeOff connector, and indication changes from Enabled to Not Enabled. So, the summary of the problem is that both the HIM and DriveExecutive show that the drive is creating an output, both in HZ and volts, but nothing is measured on the drive terminals, connected or unconnected. My biggest concern is why the Drive Output Volts parameter, which claims to be representative of the voltage on T1/T2/T3 would differ, at ALL. Cat. No: 20G11ND5P0AA0NNNNN Series A Firmware: 11.001 Serial Number: 40575849 Options: DriveLogix Ethernet/IP SafeOff Encoder 24I/O HIM [/INST] There's nothing wrong with your procedures for startup. We've encountered this problem a couple of times; replacing the drive is the only solution we've discovered. Rockwell has provided no explanation at this point. \\n </s> |
<s>[INST] PowerFlex 525 7.001 Firmware Update Not Flashing. I am trying to flash the firmware of a PowerFlex 525 from 5.001 to 7.001 without success. I am using ControlFlash 15.07 with Windows 11. I am able to see and pick the drive in ControlFlash, but it errors out at the end. The message I receive is ERROR: Update to target device failed. Press View Log for more detailed information. Has anyone else experienced this issue? [/INST] Please open the log file as it will provide information about why the flash was not successful. If the firmware in the drive becomes corrupt, you might try flashing via USB.\n </s> |
<s>[INST] finger-safe PowerFlex 750 Just curious, if I need to make a PowerFlex 750 finger-safe is it better to use the power terminal guard (20-750-ptg...)or the NEMA 1 kit? I have experience with the NEMA 1 conduit boxes but I want to know if anyone has used the 20-750-ptg1 kits. [/INST] Aaron, I had to dig a little bit for this, but I was able to find a drawing within SAP that shows the power terminal guard: Kits are only available for the Frame 6 and 7 drives. Its a clear sheet (possibly lexan), and as you can tell you could still access the terminals from below. The NEMA 1 kit is fully enclosed, so if you're trying to restrict access/make truly finger safe, I think the NEMA1 kit is the better option. Though I do think you could use both if you wanted, I believe the power terminal kit fits within the NEMA1 kit. If you're working on a Frame 1-5, your only option would be the NEMA1 kit. Hope this helps! \\n </s> |
<s>[INST] Kinetix 350 - 2097-V33-PR1-LM InPosition very slow Summary: Kinetix 350 - 2097-V33-PR1-LM InPosition very slow Kinetix 350 - 2097-V33-PR1-LM InPosition very slow: I am using 1769-L33ERM, linked to Kinetix 350. I have established the communication between the drive and the PLC. I am at the initial stage trying to test the Move commands to the drive. Used the MSO command to ON the servo. Then the MAM command to move the servo in Incremetal type. I am using the Rotary Transmission, High response, point to point type. I move it 360 deg for one full revolution. The speed is 4500 rpm, The acc is 5000 /sec2, The decc is 5000 /sec2. It takes nearly one sec to reach 358+ and another two secs to reach 360. I am not sure why it takes so long to reach the inPosition. Is there any othere important settings to be done. If manual tune can solve it, what are the parameters I need to change to make it InPosition faster. Thanks in advance for your help. [/INST] The model of Motor I am using is MPL-A1510V-Hxx2 \\n </s> |
<s>[INST] POWERFLEX 755 profibus Summary: reference & feedbackshello; can anyone help me on how can i send reference to the powerflex 755 throught profibus, (im connecting with the drive, i can send command word and receive status word) [/INST] Welcome to the Forum ! Try to read the following technote: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/505633 Hope this helps, - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] F-4050-Q-H00AA replacement Summary: i need to replace F-4050-Q-H00AA motor which is not present now in AB ?? [/INST] Welcome to the Forum ! F-series motors business has been taken over by Elwood Corp., an Encompass partner. 554584 - F-Series, H-Series, N-Series, W-Series Motors and Cables - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] FT Optix Open popup on a value change. Currently I'm working on a project in FT Optix. I've been working in it for a while now but I can't figure out how to open a popup in the runtime when a value changes. In the PLC there is some code running and when this is done, a value changes, when this value changes the popup needs to open. This popup should be able to open on every screen on the foreground. [/INST] If you go to the variables in your project you should see the Events section of the properties tab. You can add an event by clicking the plus sign in the top right corner of the properties tab and select Changed Event. Then you can use that event to open a popup by linking it to the UI commands for opening a dialog window (OpenDialog).\n </s> |
<s>[INST] Why doesn’t the top of an AM have the connectors for incoming power and contactor enable? Summary: Why doesn’t the top of an AM have the connectors for incoming power and contactor enable? Why doesn’t the top of an AM have the connectors for incoming power and contactor enable? [/INST] Because the first module in the Kinetix rail, the Integrated Axis Module (IAM) has those connectors. The Axis Modules use the DC bus from the Kinetix mounting plate, and don't need their own incoming AC power or contactor. \\n </s> |
<s>[INST] SCM-FLEX wiring to e-stop safe-off system I have SCM-FLEX soft starts that are wired as per typical start-stop control via DPI communications with a control relay wired to aux [/INST] nan \\n </s> |
<s>[INST] Powerflex 40P I have an application where I am trying to use a Powerflex 40P. Basically when the machine is in manual mode I want to be able to jog fwd, and bwd. When the machine is in auto, I want to be able to move to two set positions. I am using an encoder. I have the drive set up using Position Step Logix, and I can get the drive to jog fwd, and rev and I can get the drive to go to the first position but I cannot get it to go to the next position. The first position is 1000 units past home, the second position is at 500 units past home. I the encoder set for quad check. Any ideas? [/INST] May you better describe the situation when the first position is done...drive status ? Did you configure the Logix to go to step 1 after step 0 done ? Just give us more details, to get more help from users ! :smileywink: - fuzzy logic \\n </s> |
<s>[INST] KINETIX 6000 2094-BM01-S FIRMWARE PROBLEM Summary: Stuck at 02 codeDear All, 2094-BM01-SA0192 was installed on a machine, now we are installing 2094-BM01-SB1111 Problem is that when we Power ON, it start showing 0,1,2 and remains on 2 while in old SA0192, it goes to 1,2,3 and 4 then comes to normal display. can anyone suggest the solution? waiting [/INST] Did you adjust the drive entry in the IO tree of the PLC controlling this axis? \\n </s> |
<s>[INST] Converting from Hyperface to standard encoder. Summary: Kinetix 6500I am looking to convert one of our machines from a Hyperface feedback to a standard 1024 Incremental encoder, and wanted to know if I change the interpolation and the counts in the feedback properties would anything thing else needed to be changed also? Thanks, [/INST] You're changing from an MPL type motor down to a TL or TLY motor? I think you've covered the places that need to change. \\n </s> |
<s>[INST] Line reactors Summary: Motor sizeGood day, 1. What size of the motor do a connect reactors on the input and out of VSD? 2. The line reactors have two ratings e.g A1 & A2 = 80A and B1 & B2; Ith = 120A and what this means? M. Mahao [/INST] Hi, if I get your question right, the side depends on your particular installation or application. Basically you utilize a reactor connected to the input of your VFD to help to protect your VFD against disturbances of your power line and also to reduce the total harmonic distortion in the line introduced by the VFD. Basically you utilize a reactor between the VFD output and the motor to protect your VFD against reflected waves in installations where the motor and the VFD are “far” from each other and also to protect some motors from non-sinusoidal wave forms. There can be some other reasons why you want to use a reactor. If you utilize an input reactor connect A1, B1 and C1 to the line and A2, B2 and C2 to the VFD input terminals. If you utilize an output reactor, connect A1, B1 and C1 to the VFD output terminals and A2, B2, C2 to the motor In your case 80A is the rated fundamental amps and Ith = 120A is the max amps Hope this helps Bye \\n </s> |
<s>[INST] Can 1203-GM1 adapter fit into PF70EC? Hi, There are few AN/KB stated 1203-GD1, GK1 & GM1 can be re-used on PF70EC, if firmware revision is 2.08 or higher. But can it be fitted, physically to the 20-COMM-R adapter of PF70EC? Thanks. [/INST] No, they are anyway external interfaces... Fit an external 1203-GD1, 1203-GK1 connected with a SCANport cable 1202-C03 into DPI Port 2 of the drive. An adapter with firmware frn 2.08 or later will be required, so the existing adapter can be re-used if suitable. - fuzzy logic \\n </s> |
<s>[INST] MAR.PC delay Summary: In trend I can see that input is armed and I also se that.Reg1InputStatus is 1. Status .RegEvent2Status needs approximately 2 s. Please help me understand MAR.PC delay. We have 11 years old machine with clx L61 and kinetix6000. Last year firmware was updated from v13 to v20. From last weak one registration input on one axis works extremely slow. It takes 2 s to react and in the mean time axis moves to far and registration position is out of the limits. In trend I can see that input is armed and I also se that.Reg1InputStatus is 1. Status .RegEvent2Status needs approximately 2 s. Sequence is: MAS axis MAS.pc starts MRP MRP.dn starts MAR MAR.ip starts JOG .RegEvent2Status calculates end position JOG is merged in to MAM absolute position Thank you [/INST] How do you determine the 2-second delay? Are you trapping the time using code, or simply watching the bit change state from your computer? Doing the second is not a good way to determine true latency of the system - communications with your computer are the lowest priority of the PLC. You said the firmware was changed last year. Did the MAR work correctly after the firmware update, and the anomalous behavior started very recently? If that is the case, what else changed in the system? Are you running a new product on the machine, one with different parameters than previous ones? \\n </s> |
<s>[INST] Powerflex 525 Output voltage Lower than rating Summary: Powerflex 525 Output voltage Lower than ratingHello, regarding the specs of the powerflex 525, if the output Voltage specifications says :0..460V, 3 Phases, I am guessing I can use this to drive a 230VAC motor? I have an application where I have 480VAC and a 230VAC motor. There are PF525 with 120VAC 1 Phase input, 3 phase 230VAC output but that requires to upsize my 120VAC transformer. If I can just put the 230VAC motor on a 480VAC drive, my transformer will keep a reasonable size. Thanks! Antoine [/INST] I would recommend reading this technote: https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/516206/loc/en_US Luckily, it is an article listed for everyone. Short answer is that it is theoretically possible but you're most likely going to burn up the motor. The 230V motor most likely will have insulation rated for 230V, not 460V. A stepdown transformer and 230V VFD is the correct solution for that motor. Alternatively, get a 480V motor to eliminate the stepdown transformer. If you decide to try using the 230V motor on the 460V VFD, let us know how well it worked and how long the motor lasted before frying (if it did). I'm not being facetious - you might learn something that all of us could use. \\n </s> |
<s>[INST] 3600 RPM Motor on VFD? I have an application where I need to run a pump at 2400 RPM to achieve the desired pressure. I currently have a 20HP 1800 RPM motor running at 70 Hz. (2000 RPM)I cannot increase the speed (Hz) more or my drive trips on OL.I am looking at increasing the motor HP and Drive size and/or changing the motor to 3600 RPM.Has anyone ran a 3600 RPM motor on a Powerflex at 45Hz or so? We have considered changing the pump, but that requires a larger motor, Powerflex Drive and cable anyway.I am looking at the above approach to avoid the pump purchase. Any Thoughts? [/INST] Cygnusx1, when a motor goes above it's base speed, in your case 1800RPM, the torque will begin to drop off as the speed is increased. See the formula and torque curve below:HP = TN 63,000Where, T = Torque (in-lb) N = Speed (RPM) As the motor speed goes up (N), the torque has to go down to maintain constant HP. To go to 2400RPM, you will have to run at 80Hz. Your torque will drop off considerably. If you go to a 3600RPM motor, you will be in the constant torque area of the torque curve for you full range and you will be running at 40Hz. If you use an inverter duty motor you shouldn't have a problem. \\n </s> |
<s>[INST] Kinetix 5700 CONECTING state stuck Summary: The servodrive kinetix 5700 connected to a MPL-B680D-M motor first time setup.Hi I'm doing the first setup of a 2198-S086-ERS3 kinetix 5700 connected to a MPL-B680D-M motor and it has also a 2198-P070 servo power supply. It is stuck at the CONECTING state, the power supply also stop at the same state. I look the Logix Designer modules information and there is no clue of an error. [/INST] What else is in your Motion Group? Do you have another axis in the motion group where the drive is not physically present or the motor not connected? In Rockwell's implementation of CIP Motion, all axes must detect their physical drives / motors or you'll get stuck exactly where you are. To get around this, you can inhibit the missing drive in the IO tree. If a drive is inhibited, the Motion Group will ignore it. If the drive is not inhibited and is missing at the type of system power-up, you get the problem you have. \\n </s> |
<s>[INST] Flash the PF400 to latest firmware Customer requested to flash PF400 to latest firmware and we do not have AK-U9-FSLH1 Serial Flash Module. As know that AK-U9-FSLH1 kit no longer sales. Any other alternative method to perform PF400 Flash?? Can we use 1203-USB to perform PF400 Flash?? [/INST] Welcome to the Forum ! Please contact local Rockwell Automation office to get a field service engineer to perform the firmware upgrade on site, or send the drive back to Rockwell Automation for firmware upgrading. - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] PowerFlex 4M Programming Power Greetings Drive World, Does anyone know whether or not it is possible to connect an external power supply to the PF 4M to provide programming power to the drive without powering up the entire drive? Apparently some of the competition to this drive can be powered up in a single phase format to allow for parameter programming, but not operation. Thank you. [/INST] A long time ago you could just power up the middle phase and it would work but not on today's drives. The drive has to be powered up to run the HIM but if you're using a 22-Comm-x (C, D, E) moduel, then there is a small box you can purchase from AB that allows you to externally power the moduel but for programming the drive...it has to be connected normally in order to power up the drive electronics, unless there's some AB wizard with a tip we don't know about. I've needed to do just what you're talking about many times in the past so I finally rigged up a 480/120 transformer, fed it in reverse, and then did what I had to do. Again, seems there could be a small 24VDC connector for allowing this to happen BUT....that would be taking too much for granted. \\n </s> |
<s>[INST] Powerflex 70 main control board replacement. Hello,I have a 30KW powerflex 70 drive and the main control board has failed. I want to know if this board is available as an accessory.Thank You. [/INST] The Powerflex 70 main control pcb's aren't standard spare part items or field replaceable items. Prior to installation the board require several flash files that allow the PCB to work. The files are boot code files, application files plus the firmware files which need to flashed by the factory to the boards. All of these files are flashed at the factory during drive assembly. The best option is to send the drive in for repair, and allow the factory to properly flash the correct files to the drive/pcb. Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Kinetix 300 and Kinetix 350 Summary: What can we do if changing the damaged drive Kinetix with a new one?Hello, We have 2 types of drivesKinetix 300 and Kinetix 350 We need to store the parameters setting for the drives to my PC because if one of them damaged ,we replace it with another one and load the saved parameters from my PC to the similar new drive. How can we do it? Best regards...... [/INST] I would start by reading the user manual for the K300 drive: http://literature.rockwellautomation.com/idc/groups/literature/documents/um/2097-um001_-en-p.pdf Look at chapter 5 for using the Java-based app built into the drive. Connecting to the drive using a web browser which can run the Java app will give you the ability to upload the drive configuration to your computer. For the K350, there is no on-board configuration. The K300 and K350 share the same power structure, but the K350 is controlled from a Logix application running on a CompactLogix or ControlLogix PLC. The configuration is stored with the PLC program. Do you have a version of Logix5000 or Studio Logix Designer with which you can connect to the PLC controlling your K350? \\n </s> |
<s>[INST] 843ES Safety Encoders - Position Error Summary: 843Es Encoders give position Error between two EncodersWe are testing the new 843ES Safety Encoders. We are finding that there is a significant error in position count value between two encoders, even though they are bolded to the same shaft. And no, one is not slipping, these are being turned slowly by hand. The 2nd unit is configured anti-clockwise to the first as clockwise. We did an extra test where both are clockwise, and there seems to be minimal error, however when the 2nd one is set to anti-clockwise, then error is introduced. Can Rockwell please advise the issue? And the release of updated firmware for the 843ES Encoder? Mike. [/INST] Michael, this is not Rockwell Tech Support. If you're expecting an official answer from Rockwell, you may not get it here. This is Rockwell's user forum, users helping other users. You should contact Rockwell Tech Support directly. \\n </s> |
<s>[INST] E91 Ethernet/IP User Watchdog Timeout I have a Micrologix1400 controlling a couple of MPL (MPL-A310F-MJ72AA ) using Ethernet/IP with Kinetix300 drive (2097-V33PR3) MPL-A4560F-MJ72AA and 2097-V33PR6 for The Program is a modification of the Sample program from Rockwell (SMC_ENETIP_ML1400_K300_2AXIS_V1_0 The PLC Program and Drive has been running for years, and works great. I recently tried to connect to the Local LAN so I could use Archie's Advanced HMI. About 20 or so minutes in I get errors on the MotionView MotionView on board Fault Code E91 Ethernet/IP User Watchdog Timeout The Suggestion says: Not writing to WatchDogKick Tag frequently enough to prevent timeout. Watchdog timout period set to too low a value. Increase timout period or change controller application to kick watchdog more frequently. I tried to increase the Time value in L204:2 to 2000 from 1000, and that didn't fix it. Do you have any other ideas or suggestions? [/INST] Could it be possible maybe that the PLC program is not executing certain instructions within the timeframe that the Kinetix 300 should be expecting and therefore the process being somehow disrupted...? Do you think this problem could be still observed even with the original sample code, without any modification? \\n </s> |
<s>[INST] PF527 MAG Instruction without Encoders? Summary: Wonder if a PF527 without encoders can still use a MAG instructionAs the Title and Summary state. I'm looking to doing a velocity synchronization application between a Main Conveyor Motor and Take-up Conveyor Motor. I know the PF527 supports the MAG instruction, but does the drive need to have an encoder connected? I'm familiar with the use of servo instructions and Kinetix Drives, but this would be my first use of a PF527. I've looked for examples but couldn't find any. any help/direction is appreciated. Regards Vin [/INST] I've done simple MAJ instructions on a PF755 set up for vector control, open feedback. MAG, almost by definition, wants encoder feedback to synchronise the slave to the master. I think the results without it would be rather poor at best, if not flat out impossible to do. Are both motors on the same conveyor, one supporting the other? Or are they two different conveyors? If it's two motors on one conveyor belt, you could set the slave drive to be a torque-follower and not need feedback on it. \\n </s> |
<s>[INST] Powerflex 70 drives Summary: Is it suitable for oven chain conveyor applicationDifficult to negotiate Rockwell product selection. I want a 4kW , 400 VAC drive in the Powerflex 70 series but selection guide for PN 20AC8P7A0AYNANC0 states suitable for pumps and fan application. Is this drive suitable for oven conveyor drive? [/INST] I do not see where that drive is limited to pumps and fans. Where are you looking that you see this? A PF 70 is fine for an oven conveyor. If this drive is one you already own, or if you have a factory full of PF70s, then go for it. If you're planning to purchase a new VFD, the PF70 is not a good choice for a new application. It is not technically obsolete, but I would look at a PF753. 20F11NC8P7JA0NNNNN should match the configuration of the PF70 you show. In US dollars, I see the list price of the 753 being $250 less than the PF70. \\n </s> |
<s>[INST] PF700S with a Stegmann optional encoder I have a pair of PF700S configured in a master-slave arrangement each with a Stegmann optional encoder. I can get the drive to run in senorless mode for speed control at the reference of 600RPM.However when I try to use the Stegmann encoder speed feedback (FB opt port 0) mode for speed control I only get about 120RPM feedback with my reference at 600RPM. The slip tune and inertia wizards in DriveExecutive just osillate the motors back and forth around +-30 RPM and never complete their tests over a 5 minute span before I abort them. I have noticed the output voltage parameter 307 is 212V for senorless and 77V for FB Opt port 0. Any suggestions? [/INST] Searching the Knowledgebase, I found this: ID 26187: A Vector Drive is not Working, Or the Motor Is Rotating Slowly and the Motor is Pulling 100% Current. But the parameter they reference for the 700S2 is 367 is called Fdbk LsCnfgPosit that doesn't have an ignore option. There is no FP Opt0 LossCnfg set to Ignore (0) I can find? \\n </s> |
<s>[INST] Motion group overlap fault Summary: Which will cause the motion group overlap fault and Could you give the discription for that [/INST] Your coarse update time is set too short. https://rockwellautomation.custhelp.com/app/answers/detail/a_id/39085 https://rockwellautomation.custhelp.com/app/answers/detail/a_id/39084 Take a look at page 44 of motion-um003_-en-p \\n </s> |
<s>[INST] SMC Flex Configuration Loss I am currently experiencing problems with a couple of SMC Flex softstarters which are connected over DeviceNet to a CompactLogix system. It seems that one of two faults may occur. I have not personally attended any of the problems and are onlyrelaying information given to me. 1. The SMC Flex seems to lose their configured data for apparently no reason. I have told the client to ensure that after he has reprogrammed them that he must save the data to Eprom and he has assured me that he has done this but the configured data loss still occurres from time to time. 2. According to the client it seems that the comms between the PLC and SMC Flex freezes. It does not accept a start command over the network but when a hardwired start command is issued it starts ruling out the possibility that the enable is missing. The firmware revision is 3.006 and ADR is enabled. [/INST] Sambo, obviously the best is to be on site and see what happens exactly, which fault code is displaied etc... :smileysurprised: Anyway, there is a known issue on ADR and SMC-Flex firmware revision 3.006 and earlier, as reported in Aid 30710... also there are two new firmwares for v5 and v6 that replace the original inside some SMCs which exibits the same error ( Aid 55159). Maybe the problem out there is coming from improper ADR functionality... :smileytongue: Hope that helps....- fuzzy logic \\n </s> |
<s>[INST] Powerflex 525 Forward / Reverse Summary: Control Powerflex 525 in forward / reverse directionCan i control powerflex 525 in forward/reverse direction just start command ( Hardwired DI) and speed reference ( 4-20ma only ) that shall corresponding to -50Hz to +50Hz such that when i give speed reference 4mA and start command drive shall rotate in reverse at full speed and when i give 20mA it will rotate in forward direction or i need separate forward / reverse command Drive is not communicating to PLC over ethernet or any other protocol [/INST] The only way you can get what you want is to use the analog voltage input. It will not work with the 4-20ma current input. If you can change to analog voltage, then you would set parameter t093 to value 1 (Bi-Polar In). According to 520-UM001: https://literature.rockwellautomation.com/idc/groups/literature/documents/um/520-um001_-en-e.pdf, page 97, if you set t093 in this manner, then P043 (min freq) and t091 (anlg in 0-10V lo) get ignored. Presumably, with t093 set to bipolar, the 525 drive assumes your speed control is going to be symmetric (whatever you put in for max frequency and analog 0-10V hi) will be the same in the negative direction. \\n </s> |
<s>[INST] Cannot connect to 1756-L71 We have a setup which consist of 11 drives on DLR connected to EN2TR controlled by L71(V20) . Everything works fine but as soon as all the drives are switched OFF i am not able to connect to the controller and the controller basically hangs up .. i can see the chassis in rslinx but when i browse the chassis and try to connect to processor it does not connect and wait a very long time .. Also changing key switch from run to program also doesnt help . The programming device is also connected in the same DLR .. basically the setup is EN2TR to ETAP .. ETAP to drive 1.. drive11 -- EN2TR in DLR and i am connected to device port of ETAP .. As mentioned above i can see the chassis in rslinx but when i browse and try to connect it in logix i cant Any suggestion on what could be cause ??? [/INST] Which device is the DLR supervisor, the PLC or the ETAP? Have you tried opening the ring between the EN2TR and drive 11 so that the setup is a line, and then shutting down the drives? \\n </s> |
<s>[INST] Power Flex 700 scr pre charge board We have a AB Power Flex drive, P/N 20B D 096 A3 ANNANCO, that we lost the precharge board, P/N SK G9-PRE1-V480 (long story) and I am told by my local dist and Rockwell that it is a 10-15 day lead time. My question is do the other 700's have the same precharge board or are they specific to drive size? Thanks in advanceDave [/INST] Yes, the 400 / 480 Vac versions of all the PF700 have the same Precharge board (starting from frame 5), as you may see in the Spare Parts listing.... Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] Help needed to set up Powerflex70 Summary: Motor not starting, no faults, need advice.Hi there Is my first time in this forum, I'm not a control guy, mostly a pure mechanic but working as a Food and Beverage Mechanic sometimes I need to fix wires related problems, this time I have been mounting an old can filler( like new after rebuilt) with the 1973 original electrical panel, first step.......easy.... new wiring including a new old stock SLC 5-04 and Powerflex70, everything is working fine, but we need the motor working in three speeds, at this point I need a control guru advice....... We need to run the VFD in three different speeds: jog, low and high. We use a drawing from RA Drives Services and Support (Wiring Diagrams), the one named Selecting Multiple Speed Command Sources (Attached) without success. We have three relays wired to I/O s [/INST] Let's start with the easy stuff. Make sure you've got a good copy of the PF 70 user's manual: http://literature.rockwellautomation.com/idc/groups/literature/documents/um/20a-um001_-en-p.pdf Go to page 68, where it defines how the digital inputs will be used. You are using them correctly (364-366 set to 15, 16, 17). However, note that turning on only input 4 will give preset speed 1, turning on only input 2 will give preset speed 2, but turning on only input 3 will give preset speed 4. Rockwell uses the inputs in binary code to get up to eight (8) preset speeds. You may already know this information, but I want to be sure you understood. Go to page 33, where parameter 90 is defined. You say you've set parameter 90 to value 15, and 93 to value 16. Value 15 means preset speed 5, and value 16 means preset speed 6. Because you want to use the digital inputs and have already defined them properly, you shouldn't have to define parameter 90 at all. However, to get preset speed 1, you will need to set parameter 93 to value 11 (preset speed 1). Go to page 110. There, it says that the default source for speed reference is parameter 90, unless those speed select inputs are closed. To summarize, Parameter 90 doesn't matter. Parmeter 93 should be value 11 (for preset speed 1 when input 4 is closed) You have parameters 364-366 correct Remember that you have to set parameters 101, 102, 103 (the three preset speeds you've decided to use. Page 35 shows the defaults for those three speeds are 5, 10, and 20 hz respectively. Your problem, I believe, is because you've provided no means for starting and stopping the drive. You stated parameters 361, 362, and 363 are set to 0. This is not used according to page 68. Digital input 1 is set by default as a stop input, and digital input 2 is set to start by default (see page 68). Please refer to the installation manual for wiring choices for these two inputs: http://literature.rockwellautomation.com/idc/groups/literature/documents/in/20a-in009_-en-p.pdf Page 37 gives examples. You'd stated you were using old fashioned way to control the drive, so your PLC must provide signals to the drive via input 1 and input 2. \\n </s> |
<s>[INST] replacing MPL-B430P-RJ22AA with MPL-B430P-RJ72AA Summary: Required HelpCan we replace MPL-B430P-RJ22AA with MPL-B430P-RJ72AA physicaly without modfiying software [/INST] Yes, the 7 is for SpeedTec connectors which the software doesn't care about. The 2 was for the bayonet connector, so you'll need new cabling. \\n </s> |
<s>[INST] Following 842E-M Encoder with Kinetix 350 Summary: Question on setting up 842E-M as a Virtual Master I am using a 842E-M on a piece of equipment. I have a machine that follows this position. Best case scenario I would use the CIP Ethernet encoder, but there is about a four to six week lead time right now for those. I would just set that as the Master axis is my MAPC and go from there. So for now I am using a regular Absolute Ethernet Encoder. I recieve all my values with no issue. I am guessing I need to use a Virtual Master to imitate the encoder position. I am using the example from the TechNotes on how the setup a Virtual Master using two MAM's for a HSC card with an encoder. Should I do the same here? I am trying it, but the error on it is pretty large. I am open for all suggestions, because I have been beat down by this problem for a few days now. [/INST] Generally, one connects a master encoder through the auxiliary encoder input of a servo axis. At this point in time, it must be a SERVO axis; while PF755 drives support a number of simultaneous encoder inputs, none of them can be used as an auxiliary to be master. The K350 does not have an auxiliary encoder input, so you're stuck using the HSC card as you described. Can you give some more detail about the error? There should be no error on the virtual axis at all? Or do you mean the difference between your encoder input, and the virtual axis? Did you set the values identical to the example in the tech note? I see that (in the V16 example) the check box for master delay compensation is set. Getting the Ethernet/IP encoder is the best route for what you desire; either that or switch the K350 to a K6500; though I'm guessing that isn't going to fly because you probably used the K350 for reasons of cost. \\n </s> |
<s>[INST] Power Flex 400 Flying Start I'm trying to enable Flying Start function on the PF400, 22CD208A103, Series A. Parameter A167 is enabled, but it isn't working. It doesn't show parameter A200 too. [/INST] Juliano, parameter A200 has been added starting from release 4.xx of drive firmware... may be your drive is older... Aid 54369 When you said it isn't working, what does it mean? May you better explain...it could be useful.:smileywink: - fuzzy logic \\n </s> |
<s>[INST] scanport to 700 drive We are replacing a 1336 plus drive with a powerflex 700 standard control I can find the information that tells what you need to do to accomplish this, except for the information that tells you what bits to use for control and speed reference does anyone know where to find this information? [/INST] May you please post more details ? Which is the scanport device do you want to use ? For example, here a couple of technotes about some scanport conversions... Aid 21565Aid 43077 HERE also some infos about conversion.... Hope this helps, - fuzzy logic \\n </s> |
<s>[INST] F004 Fault on Powerflex 4M Summary: Inverters faulting on F004 during ramp-upHi all We have 4 inverters fitted in this particular panel are all failing on F004 as the individual motors are running up (only two motors run up at a time). They are reading 400V-405V at the inverter input terminals. I believe the fault level is based on the based on the drive rating (480V) and is a non-settable threshold. We lowered P001 to 380 and switched the display to D005 (DC Bus Voltage) and the display started at 575V and, when it fell over in F004, it read 555V. This seems some way off the 390V stated in the Supplementary Drive Information you forwarded me. Do you know and could you suggest anything else that could contribute to this? Thanks Stuart [/INST] 555V bus voltage would correspond to a theoretical line voltage of 392V. I think you should look harder at your line in voltage. If you can put a power monitor on it, you might find the voltage is sagging far more than you can read with just a multimeter. Also, what is P001? That is not a valid parameter for PF4M. Did you mean P101 motor name plate voltage? Are you measuring voltage as the motors run up? It sounds to me like your voltage source is very soft and not up to the load. \\n </s> |
<s>[INST] Ultra 3000 E41 I have been seeing ground faults and drive hard faults come up in my PLC.The ultraware fault history shows E41 filling the entire queue. I have an internal shunt, what options do I have to fix this error? [/INST] Try to take a look to the following technotes: Aid 22707 - Aid 26076 Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] VFD Clearance issues Summary: Powerflex 520 - Clearance IssuesAll, We are having a little debate at work on VFD clearances. and adhering to the specifications. The question is simple, I just cant find the answer. In the specifications for the Powerflex 520 Series AC Drive, you will find a section on Clearance. It shows different mounting options for Vertical and Horizontal. There are 4 scenarios for mounting vertical when you have more than one VFD, but I am only concerned with two of them 1) Vertical Mount - Keep 1 inch in between. 2) Vertical, Zero Stacking - No clearance in between. My question is, what is Zero Stacking? Is that meaning having two rows of VFD's? That's what I get out of it. Others at work disagree and think the Stacking implies the VFD mounted next to it. I think stacking means having two or more ROWS of VFD's. Co-workers think stacking as a side-by-side VFD mounting. Thoughts anyone? [/INST] It looks like zero stacking simply means when you mount the VFD next to each other with no (zero) space between them. I didn't find anything mentioning having multiple rows of VFDs. In some VFDs this can de-rate the max ambient operating temp. In others, it doesn't affect the max operating temp. Frames 0-6 do not need to be de-rated (see below language from spec sheet). • Zero Stacking™ – Frame 0…6 drives can be mounted next to each other with no reduction of surrounding air temperature rating (50 °C). This unique bookshelf design also allows access to one drive without disturbing another. In general, it looks like zero stacking derates the operating temp by 5 deg C. \\n </s> |
<s>[INST] Dual Position is now working but I have a few issue to sort out Can you help with options? 1. When there is not sheet in the straightener the servo goes into a run-away because the motor is trying to close the position error but the encoder is not moving because there is no sheet.Solution 1:install sensor at encoder and MSF the axis when no sheet is present. This would work but would adversely affect next issue. Or maybe only MSF the axis if the axis is Dual Position Servo. then Apply Solution 2.Solution 2:Install sensor at encoder and SSV the Axis to Position servo when no sheet is present. Then re-MSO then axis. 2. When loading a new sheet both the run-away issue is present and the issue that I can not Jog the sheet into the straightener with out Position error. I have about 24 Inches between the pull roler and Encoder.Solution 1:When In Manual or before a Jog command SSV the axis to Position Servo. GSV to be sure the axis is Position servo then execute the Jog Command. Above Sensor would place the Axis into Position Servo. [/INST] Well.. that's a difficult application. First, Switching axis modes from a dual mode to a single mode is restricted according to the K6K firmware release notes (under restrictions). I wouldn't depend on that method working unless you plan on cycling power to the drive to reset the drive configuration every time you switch modes. I would imagine this is unacceptable wait time. I'll admit that I haven't done this before but I'm going to suggest it. Change the servo loop configuration over to Dual Command/Feedback Servo. When the material runs out Zero the Proportional & Integral gain and change the position error to status only (if used). The Dual command should allow the system to still run velocity mode. The thing that I don't know is if the Sercos Card or Motion planner will try to close the position loop from one of the upper control levels. Because the Position gain and Integral gain are zero the only command that the motor reacts to is the Velocity command. If the velocity is zero than the motor should stay stationary. This should still let you jog the motor and move the material. Once the material is feed back into the system the position can be redefined to 0 (select actual-- not command) or some other value that zeros out the position error. You may have to MSF and MSO to reset the position error, I don't know for sure. Re-enable the proportional gain and integral gain and operate the equipment. I won't guarantee this will work but in theory it should. I don't have the hardware to test this either. I'll Take credit if it does work though. :smileywink: \\n </s> |
<s>[INST] AB 1305 VFD Upgrade Recommendations Summary: AB 1305 VFD Upgrade RecommendationsI have five AB 1305 VFDs controlling 1hp to 1.5hp motors. They still work, but the housing is falling apart and it could be a risk of shock. Does anyone have recommendations on a PowerFlex upgrade? PF4, PF40, PF523... Thank you. [/INST] While there is a conversion document to go from 1305 to PF40, I wouldn't recommend it. If you still have 1305s running, I'd grab the newer drives so that you don't have to go through the conversion process AGAIN when a more mature drive family like the PF4 or PF40 also becomes discontinued. I would recommend using the PF523. \\n </s> |
<s>[INST] Kinetix 300 Estop Condition I have a Kinetix 300 and a MPL motor. I am connected to the drive via a Micrologix 1400. My problem is that once I resume from an Estop condition, I want to be able to push a button and have the drive go to a fixed position. However, the drive wants to continue to run the 1st index. After multiple attempts to abort the index via messaging, it still wants to run the 1st index. Even if the servo is running the 2nd index when the Estop is pressed, it wants to return and run the first index. Has anyone been able to find a way around this? I would love to be able to just push a button and have the drive go to a fixed position. [/INST] nan \\n </s> |
<s>[INST] 1336 Plus II output voltage problem Hello everybody.I have 2 drives with one problem. Briefly: when drive stopped but start command issued drive is not start and in [Drive Alarm 2] set up bit [/INST] Hi, and welcome to the Forum ! There are some informations about this Alarm inside Aid 54888... it seems related to a defective Gate Driver Board... contact your Rockwell representative to have infos about spare parts or repair... - fuzzy logic \\n </s> |
<s>[INST] Power Flex 525 trips on F072 Summary: Power Flex 525 trips on F072I have around 11 nos of PF525 connected to the control logix system with L71 ( version 20) and 1756-en2tr ( supervisor enabled ) and a remote rack with 1756-en2tr ( supervisor not enabled) . The drives are connected in DLR . Under normal situations the system is fine , but once drives start one by one , a random drive trips on F072 , once i reset the drive it again works Ok for some time , but after some time any other random drive trips on F072. However if i make the network linear then the drives are running fine and there is no trip at all . but once i make network in ring the issues start appearing . I also replaced one of ethernet cable ( the one , when i removed the network becomes stable in linear ) with rockwell ethernet cable but still issues remain same. The drives do have ferrite core at the input and output Any suggestion to remove this unwanted noise ?? [/INST] The drive is reporting fault F072 on its display. Does your control network monitor network status for each Ethernet device? Is the Logix processor seeing the same dropout for whatever drive drops out? How long is each Ethernet cable connecting each node of the ring? Things to try: Change the ring supervisor over to the remote rack's EN2TR. Disable the supervisor in the primary rack. Change out the primary rack EN2TR. What would be wrong with leaving the network as linear? \\n </s> |
<s>[INST] 2094-BM01-S Fault with no Fault Code Summary: Mystery FaultYesterday evening one of the 2094-BM01-S servo drives on a piece of equipment showed a Red Light at the Drive Status light. Looking up in the manual shows that as a drive fault and to read the fault code. The drive does not show a fault code and all the servos on the bus bar are at boot step 3. When I cycle the power the light turns off until at step 3 again then lights back up and stays at step 3. PLC software shows the drive faulted, but resetting the fault does not do anything and will not indicate what fault it is. A new drive was ordered and installed but problem continued on new drive as well. Unplugging all cables does not clear the fault nor does unplugging all the cables on the servo drives next to faulted drive mirror the issue. I am at a loss, any help or direction would be appreciated. [/INST] Logix/Studio 5000 should show some sort of error code for the drive on its properties dialog box. Check out these knowledgebase articles. Most talk about a firmware / software problem with one specific combination and a phase loss attribute new to that version - did something in the system get upgraded? The other possibility is that something happened with the encoder in the motor or with the motor definition in the PLC program such that it doesn't match the actual motor. Was someone in the program recently? https://rockwellautomation.custhelp.com/app/answers/detail/a_id/48500 https://rockwellautomation.custhelp.com/app/answers/detail/a_id/48895 https://rockwellautomation.custhelp.com/app/answers/detail/a_id/33524 https://rockwellautomation.custhelp.com/app/answers/detail/a_id/56938 https://rockwellautomation.custhelp.com/app/answers/detail/a_id/23802 https://rockwellautomation.custhelp.com/app/answers/detail/a_id/53546 \\n </s> |
<s>[INST] Can multiple PFlex 70/700 drive params bet set via SSV in CLX? We have many systems using either CompactLogix or ControlLogix and PowerFlex 70/700 drives via 20 Comm E modules. We are investigating the ability to download drive parameters via ENet to the drives from the processor using SSV's or Explicit Messaging triggered from a PV+. We usually change only a few parameters from factory default and want the ability to eliminate CopyCat or manual configuration via the HIM. Has any one done this? Thanks. [/INST] Bill, you may do this through explicit messaging, that potentially gives you the ability to read/write all the parameters in the drive, but there is also another simple way, using PF7x Datalinks... You have a maximum of 8 Input Datalinks (to write parameters in the Drive) and 8 Output Datalinks (to read parameters from the Drive. I suggest to read the 20-COMM-E User Manual, chapter 5 and chapter 6, in order to understand the two possibilities....there are also some useful examples... Also, take a look to Aid 32629...it has all you need to know in order to use explicit messaging Hope this helps… - fuzzy logic \\n </s> |