<s>[INST] Does an encoder improve starting torque on a PF 7000 VSD We have a PF7000 driving a 3.3kV conveyor motor. The encoder has failed and we are running fine in sensorless mode at light loads. Will the encoder enhance the starting of heavier loads? We don't care about fine speed control but do need the conveyor to be able to ramp up with heavy loads. This hasn't been tested yet without the encoder but if required I'd get the encoder replaced before stalling under heavy loads. Regards Vince [/INST] Hi Vince, Encoder improves the motor performance. Using encoder feedback, motor increases motor torque for greater dynamic performance. Encoder also helps to eliminate the motor stall condition. hope this help. \\n </s> |
<s>[INST] PowerFlex 525 Braking Summary: Trying to stop a conveyor without any drift.I have set the Accel and Decel to “0”, the stop command to DC Braking and the conveyor will not stop without drifting. How can I stop the belt without drifting? [/INST] Are you removing the run command, or simply dropping the speed reference to 0? Look at parameter A573, digit 2 (zero speed slip). In the User's manual, chapter 4, troubleshooting, there is an entry motor is rotating at zero hz or slip frequency is not correct. You could try the remedies shown there. \\n </s> |
<s>[INST] When I type the IP address of the PLC in Chrome a web server appears. Is there a way to see tag values here? [/INST] No\n </s> |
<s>[INST] CAD drawings for various motion control products CAD drawings would be ideal, but I can get the job done if someone just has a bitmap of a technical drawing. [/INST] Oh, I know this one! :smileywink: AID 40706 If you don't find what you're looking for, give us a call at the support center. (NOTE: You'll need a support contract.) Phone# 440-646-5800 JHutchRockwell Automation Moderator \\n </s> |
<s>[INST] MAH process complete bit I am trying to get the .pc bit to come on at the end of the MAH instruction and I'm not having any luck. I am building a machine that packages line so I have a line feed axis and a rotary axis that is operated on a cam profile. For homing I do a MAS to stop the rotary axis then a MSF, then an MSO, then a MAH to a switch. The axis homes, but the .pc bit never comes on. Can anyone help me? [/INST] A similar behavior is explained inside Aid 22214... try to see if it is your case. TechConnect Authorization needed to see that technote.... - fuzzy logic \\n </s> |
<s>[INST] Power Flex 4, Manual Start Summary: Manual start to check engine Hi, I need to know how to do force to start the engine connected to the unit. Can it be done by the panel potentiometer? [/INST] Potentiometers would give an analog speed signal only. You will need to wire/configure your PF4 to start automatically from an input or from the red/green off/on buttons on the drive itself, if I understand your question. The information for configuring and wiring the drive is in the installation manual. \\n </s> |
<s>[INST] MPAI Heavy-duty Electric Cylinders (MPAI-A4300RM34Y003) Hello, I am researching the product with the code MPAI-A4300RM34Y003 in the MPAI series. I have reviewed the MPAI documents, but there is no information about the Y003 code. Products with code MPAI-A4300RM34B and MPAI-A4300RM34A are available now. According to the product code, the only difference with these products is actuator mounting. But I'm not sure. If there is another difference between the MPAI-A4300RM34Y003 and the MPAI-A4300RM34A/B, I may have problems with the accessories. The MPAI-A4300RM34Y003 has Spherical Rod Eye, but the product code is not available. Not sure if it will be compatible with MPAI-A4300RM34A/B. Another problem is: is a new cable required? If you have any information on the subject, I would be grateful if you share it. Thank you. Best regards, [/INST] Hello Gamze indeed I don't find this reference in the manuals . It seams that you have a special version for me but not 100% sure. Did you buy this MPAI or is from a machine provided by an OEM. If it's from OEM , please get in contact with them they may have some more details for you. I the mean time I will do some little investigation. If you need a fast feedback please open a ticket with our tech support service. regards \\n </s> |
<s>[INST] Generic Sercos Card Does anybody have any information on a 1756-M08SEG Card? There doesn't seem to be anything published. my local branch doesn't seem to be any help either. [/INST] The M08SEG is a bit of an engineered product. It has been tested with Indramat drives and others with success but should not be thought of as a canned product that will control anything out there. The major problem is in the different vendors implementation of the SERCOS standard. Here is an excerpt from an FAQ: SERCOS interface is covered by the IEC/EN 61491.standard. The standard defines multiple operating modes and over 500 standard parameters. While all vendors of SERCOS interface products generally follow the IEC/EN 61491 standard there are a number of issues that made multi-vendor interoperability and interchangeability difficult. To address this issue the Pack Profile specification was developed. It defines a specific set of operating modes and parameters defined in the IEC/EN 61491 standard that must be supported. A conformance testing/certification process is also enforced. The Pack Profile specification (V1.2) and a list of compliant drives is available at www.sercos.org. \\n </s> |
<s>[INST] Kinetix 6000 migration EDIT: I've provided below the translation to the posted text in the quote. Please use the English language when posting so that it can be easily read by everyone. Thanks! -FL Hola buenas tardes, La familia Kinetix 6000 esta proximo a descontinuar, y en mi caso tengo muchas lineas con esta tecnologia, hay una forma de migrar a medida que se vayan deteriorando una a una? Hello good afternoon, The Kinetix 6000 family is about to discontinue, and in my case I have many lines with this technology, there is a way to migrate as they deteriorate one by one? [/INST] EDIT: resetted used fonts to correct size, linkified manual for convenience -FL Kinetix 5700 Servo Drives are the Rockwell Automation recommended replacement for Kinetix 6000 Servo Drives. For further information, refer: https://literature.rockwellautomation.com/idc/groups/literature/documents/rm/2198-rm002_-en-p.pdf \\n </s> |
<s>[INST] DriveTools SP control bar for 1336 Plus II firmware v.6.002 I have another one question.I used my program with remote control for 1336 Plus II drives without any problems until updating the firmware from 3.001 (5.001) to 6.002. After that DriveExecutive starts telling me that it can't find a proper control bar file and offer me to visit http://www.rockwellautomation.com/support/webupdates/.But under this link I can't find corresponding file. I have updated DriveTools to the latest verion (5.01.99) but it doesn't help. Maybe I do something wrong? [/INST] Hello, Very sorry... Here is the file you are looking are looking for. It is attached here. Please unzip and copy the file into this folder on your PC: C:\Program Files\Rockwell Automation\Common\Control \\n </s> |
<s>[INST] Kinetic 5700 EDS file Hi, We're having to rebuild a machine built by a different company that uses Kinetix 5700 EIP drives, and our customer wants to reuse as much of the hardware as possible. The original machine builders are reusing the Rockwell PLC, so I need to try use the Kinetix drives with a different make of PLC. Whenever I've tried to find the .eds files for the drives, all I've managed to find is a firmware .dmk file which I can't use directly. It seems this file is used with the ControlFlash Plus software, but the download centre on Rockwell's website doesn't let me download this software. Is there a simple way to get .eds files? Thanks, [/INST] Hi Chris, You should be able to find what you need here: https://compatibility.rockwellautomation.com/pages/search.aspx?crumb=117&q=kinetix%205700 Regards, RM \\n </s> |
<s>[INST] PF525 with HTL encoder Hi everbody, I want to share my story about this:PF525 with HTL encoder.We created an easy position control application with gearbox,chain and asynchronous motor with HTL type of encoder. The encoder power supply was 24VDC and the output of the A and B channel also.We wired the encoder output channel to the PF525 encoder card.The power supply comes from the cabinet control power supply.The connection of the encoder is single ended because the type of the encoder is HTL. After we wired the all components in the application,we want to test the equipment.Didnt work properly,after every move we were in bad position,compared to where it should be.We checked everything,mechanical and electrical things.We cretaed trend about Encoder speed(378) and Units Traveled H(388).We checked what happen,why were we in bad position.We have seen on the trend,we dont go with same speed and traveled units with forward and backward,even if we dont set position control,speed feedback,(simple settings)only check what happen.First of all we checked the power supply,that the supply has correctly (24VDC and common also), but it was perfect.After we checked channel A and B with oscilloscope.The signs of the encoder were perfect,without level problem.It wasnt missing signal. Fortunately the encoder can work with 9-30VDC,therefore we wired the encoder power supply to the encoder card power supply and we had set 12VDC.Because of this level also changed to 12VDC.And what a surprise the system works fine. In summary the encoder card count badly the encoder signal with 24VDC encoder power supply.This problem exists only when the drive has controlled.If we didnt control the drive the count was good.But unfortunately is not realizable:) I think the card is very sensitive of the DC level,therefore the card dropped the signal if the level is higher than maybe 26VDC.(The RA wrote this value to the card,and also wrote down,the card can handle HTL encoder) Please check your product limit before sell it!!! Regards and sorry my english knowledge [/INST] Hi Tom, I try to use the position control mode with Pf525 and TTL encoder connected to enocoder card. But the problem is that my drive wouldn't start. The drive has been set for position mode with step logic. I want to move the converyor belt to defined position but nothing is happening after start. The drive is in the run with 0Hz. When I run the drive with velocity mode, I can read the Encoder Speed but the Units Traveled is always very high and doesn't change while drive is running. Do you have any manual or sample code, which halps me discove how to use the position mode with pf525 with CompactLogix? I will be grateful for any advice. Cheers, Przemek \\n </s> |
<s>[INST] PowerFlex 700 In Precharge Summary: PF 700 staying in Precharge under certain conditions.Hi all, I have a PF700 (20BD156FDAYNANCO) Frame 6 Series B that works fine most of the time. When the power gets cycled to it, it will stay in pre-charge and any residual DC bus voltage will eventually bleed off. I can't find much on the actually power structure of the drive, but from the documents I have gathered in the knowledge base it would seem that the pre-charge board needs replacing. Whenever the pre-charge board is not working, all of the LEDs are off on the board, but when the drive is functioning normally the green LED stays steady like it should. If we let the drive sit for a period of time (varys, but usually 10+ minutes), it will power up like normal. It is going to take a little time to get a board here. So in the mean time, is there anything else I can check? Thanks, DLR. [/INST] Just for clarification, there is an external power supply for the control voltage so the HIM is displaying the In Precharge. Someone here (the plant) thought it was a good idea for the external power supply so we would know what the drive was doing during the times it would not precharge (although, I have repeatedly asked for a precharge board to at least eliminate that component, even if it did not fix the problem). So, it has had this problem for a while now, but just hasn't received the attention it has needed due to the drive eventually working. Also, whenever I said let it sit, I mean with the power off, then turning the power on to it after a certain amount of time (doesn't matter if the external power supply is on or off during this period). Thanks, DLR \\n </s> |
<s>[INST] KINETIX 6000 2094-BM01-S FIRMWARE PROBLEM Summary: Stuck at 02 codeDear All, 2094-BM01-SA0192 was installed on a machine, now we are installing 2094-BM01-SB1111 Problem is that when we Power ON, it start showing 0,1,2 and remains on 2 while in old SA0192, it goes to 1,2,3 and 4 then comes to normal display. can anyone suggest the solution? waiting [/INST] nan \\n </s> |
<s>[INST] Drive Executive and Observer Summary: Drive observer greyed outI am using drive executive Lite version 5.06.03. Drive Observer is greyed always greyed out under the Tools menu. I tried with being online with the VFD and no success on running drive observer. I am not sure if I am missing something here. Do I need to install drive observer independent of Drive Executive or is it part of the drive tools SP? Is drive observer available for the Lite version? Any help will be appreciated as I am at start-up and cannot run Drive Observer for debug. Thanks [/INST] Hi there, Drives Observer is not available in the lite version of Executive. It is only available in the Drive Tools Suite, or as an add-on to the full Executive version. \\n </s> |
<s>[INST] 1336 Plus II HIM Network Error 7 I have a 1336 Plus II drive with a HIM and whenever I start the drive up it runs through its typical start-up routine and when the HIM attempts to connect to the drive it just goes to a network error 7. It attempts to reconnect but just goes back to the network error. Any thoughts? [/INST] Hmmm... there is a reference to this error code at the following link: http://www.ab.com/support/abdrives/peripherals/1201/errors.html It seems to be an internal bus error... did you try that HIM on another drive, or another HIM with the drive where the error is noticed ?...just to better understand if the problem is in the Main Drive Board or the HIM is faulty.... :smileysurprised: - fuzzy logic \\n </s> |
<s>[INST] Motor Starter and Timer Summary: Looking for help wiring a motor starterHey guys, I am looking for some help wiring a motor starter with a timing relay in the control circuit. I attached a sketch of what I think will achieve my purpose: using a start button to turn on a motor for 10 seconds, and then turning off automatically, with a stop button as a failsafe. My questions are more on the wiring end. If I am pulling 34 F.L. amps through the contactor, I should use heavier gauge wire. I am assuming I can use smaller wire for the controls circuit, but how much smaller? What type of current will the control circuit see? What are the standards for wire colors (as well as colors of hot wires at full voltage vs. hot wires that aren't)? I appreciate any help. Thanks, Zach [/INST] You're using line voltage for your control circuit? Which diagram should we be looking at? The top one showing a 3-phase motor, or the bottom one showing a 1-phase motor? What IS your line voltage? \\n </s> |
<s>[INST] Ultra 3000 parameters uploading and downloading? I need to upload parameters from one ultra 3000 servo drive and want to download same parameters to another ultra 3000 servo drive?Need urgent help!!!!!!!!! [/INST] Hey Vikas, so long time since you posted last time in the Forum ! Hope all is ok there... :smileywink: Well, to connect to the Ultra drives you need at least the Ultraware software and a serial cable... just you don't mention in your post about the Ultra 3000 model you have (Stand-alone, Devicenet, Sercos) ? About the last one, please refer to UltraWare / RSLogix 5000 online help for a detailed description of uploading / downloading methods. - fuzzy logic \\n </s> |
<s>[INST] Motion analyzer Summary: Why the drive which the software recommended is always the AM module?I think the first slot module sholud be IAM module. [/INST] The IAM power size is dependent on the number of drives and how they interact. If you have multiple drives, it is likely you want some of them to be operating at the same time. The default condition for multiple drives is to NOT have them running at the same time which minimizes the size of the IAM. Thus Motion Analyser first has you define all the axes, and if they work together or independently, and only then sizes / replaces the first AM with an IAM. It's not not intuitive, but it does make some sense. It would help if the sizing process were better described up front. \\n </s> |
<s>[INST] PowerFlex 40 via Ethernet Hi all. I'm developing a project with several PowerFlex 700 VC's and PowerFlex 40's on Ethernet to a ControlLogix. I'm having to set up datalinks to get a couple of extra parameters read back in. The 700s seemed pretty simple. But on the 40's I can't find where to add the extra datalinks. The Data Format box (in Module Definition) is set to 0 Data Links and is grayed out, so I can't change it. I've looked in the user manuals for the 40 and the 22-Comm-E module and I can't seem to find the info I need. [/INST] Unfortunately, Powerflex 4x has not the possibility to use Datalinks... :smileysad: Only way you have in order to read/write parameter is through Explicit Messaging. Aid 38670 22-COMM-E User Manual - chapter 6 as examples - fuzzy logic \\n </s> |
<s>[INST] Flex 150 periodic Fault Code 132 Summary: Looking to find out the descirption and cause of error 132 Here is what I have: Allen Bradley smc-flex Cat no 150-F135-NBD (on controller unit) Win no. (21) mk1rm5dh (on display module) 41391-454-01-s1fx (on display module as well) Periodically, the display is found with the following error code: Fault code (132 system error) This fault can be cleared by cycling the power to the drive, after which it will function correctly. Any thoughts? Dan [/INST] Welcome to the Forum ! Have a look here : 49370 - Causes of Fault F132 on the SMC-Flex - fuzzy logic In order to enhance Forum's contributors reputation, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] POWERFLEX 40 ETHERNET/IP Edit: EF-translated into English. I can not assign an IP with the bootp / DHCP program to my powerflex 40, in the program nor does the MAC of the powerflex appear although it is connected with ethernet, I have the code of its MAC but in the application it does not appear, then I can not assign the IP to write parameters from the PC My suspicion is that it does not recognize the powerflex, should I try an RJ45 to USB adapter? [/INST] The 22-COMM-E EtherNet/IP adapter must be installed and Parameter 02 must be set to enable BootP. Once your BootP server pushes the IP Address to the 22-COMM-E, you typically disable BootP (Parameter 2). You can manually configure the IP address via Parameters 3-14 https://literature.rockwellautomation.com/idc/groups/literature/documents/um/22comm-um004_-en-p.pdf \\n </s> |
<s>[INST] Power flex 750 series Max frequency Hello, I am trying to figure out why I cant run at 67 Hz when the speed reference is at 20 mA. At 4 mA I am at 0Hz, at 8 mA I am at 30 Hz and at 20 mA I am at 60 Hz. I changed parameter 0-37 to 67 Hz. wondering what am i missing ? Thanks [/INST] Welcome to Engage, Martinez! This can be increased by changing the setting to Parameter 520 [Max Fwd Speed] and Parameter 521 [Max Rev Speed] (depending on the direction). Analog Input parameters should also be changed. Reference QA36057 fuzzy logic Please don't forget to LIKE and highlight the decisive answer: REPLY > Make Best Answer \\n </s> |
<s>[INST] Powerflex 700S running status bit dropping out while running Hello, We have a Powerflex 700s frame 1 that has been in use for at least 5 years now and has not had the issue that we are seeing now. The past couple days while running, it will randomly loose the running status bit. The program is designed to check that the drive run bit is true and also the running bit is not false. If both those conditions are not met in 1 second, the machine shuts down. After the machine comes to a stop, you are able to start it right back up. It will then run for 2 hours before shutting down, but sometimes back to back. From everything I read, both those bits are produced from the drive and not an external source. Does anyone know if this can easily be resolved or should I look at replacing the drive? Cat [/INST] Is the running status bit a discrete output of the drive or are you getting it via network connection? If it's a discrete output, I would concentrate very hard on the physical wiring. Your problem sounds like a loose connection. It might be a failing output relay. \\n </s> |
<s>[INST] Drivers for 1784-U2DN in RSLinx Classic 2.54 not available a) Your web info suggest that Drivers for 1784-U2DN are already included in RSLinx Classic 2.51. When you open the drop-down menu in RSLinx to 'add new', the driver is not on the list. Any suggestions?b) Some pdf file is referring to a tech note and to follow the instruction to download the driver if RSLinx is before 2.51. I couldn't find the tech note on your web site. Where exactly is it?I would appreciate your help. [/INST] Try to follow suggestions inside Aid 53280... Post again if you still have troubles... - fuzzy logic \\n </s> |
<s>[INST] Homing sequence Summary: Some points during sequence in the diagram Home mode = active sequence = home to switch forward bidirectional 1.When started,Axis will forword toward home switch direction,clear the sensor and then decelerate. My question is what the sentence underlined in the picture means? [/INST] The language is butchered, and the reference point is wrong. What #2 SHOULD say is: 2. If the axis begins the homing sequence with the home limit switch already on (if the axis position is between point 1 and point 2), it will begin homing motion by moving in the reverse direction at the home return speed until the home limit switch clears, and then the axis stops. \\n </s> |
<s>[INST] Best practices to connect a group of PF 70 to and Ethernet network Greetings everyone! I appreciate your help to know what is the recommended topology to connect drives, specifically PF70 in a Ethernet network? I thought that ether ring or star topology would apply but the customer mentioned that Rockwell recommends star topology for these kind of equipment and that there is a tech note with information but I have not found it yet. thanks a lot for your support. [/INST] The 20-COMM-E only has a single ethernet port on it, so it cannot be part of a device level ring (DLR). \\n </s> |
<s>[INST] FTview 10.0: How do I expose a polygon to VBA? I have a box made of a polygon. I want the operator to activate some VBA code by clicking this box. I don't want it to be a button - just a box. When I select VBA control in the property panel, it switches to Type info Extension - and I cant have VBA code on this box. How do I get the VBA code to activate upon click on this box? [/INST] the Polygon object only exposes the Properties and the Methods provided by the Element object, it does not expose Events to VBA. As a workaround you could:\n 1. Add a Touch animation to your Polygon, and using a Toggle command you can toggle a Memory tag\n 2. Add a Numeric Display to your Display and add the previously defined Memory tag to the Expression field\n 3. Expose the Numeric Display to VBA\n 4. Use the Numeric Display Change Event to execute your VBA code\n The code will be executed every time you click the Polygon. Note: you can hide the Numeric Display from the Graphic Display: right click on it, then select Properties --> Common and uncheck Visible\n </s> |
<s>[INST] PF700S using 20-COMM-D interface Peer-to-Peer I have a pair of PF700S drives using a synclink configured as a master-slave electronic line shaft setup where there is a 20-COMM-D card on each drive for communication with the main controlller. We setup a peer-to-peer link using the 20-COMM-D card between the drives. We are sending (P158)Drive Logic Rslt of master through (P660) Datalink A to cmd/ref of slave for start/stop operation and switching the Cmd/Ref. Presently the Master (P42)Peer out time is 0.01 seconds and (P43) Peer out skip is 1. The Slave (P36) Peer Inp Timeout is 0.50 seconds. If I make the master (P42)Peer out time is 1 second and the Slave (P36) Peer Inp Timeout is 1 second. I fault the slave drive mostly right away but using shortly after starting them. The devicenet is running at 125Kb and there are only 3 devices as outlined above on the network. Have anyone used Peer-to-Peer in a 20-COMM-D card?Anything to watch out for? [/INST] djr, any informations about the fault you get on the slave and the led status for both Master and Slave drives (before and after the fault...) ? :smileywink: Also, did you try to leave only the two drives on the network ? Please, if you want, try the demo example in the following technote: Aid 24563 Check also this technote, if your drive are not new...was a problem in past firmware... Aid 23957 Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] Automation Fair 2022--Who's Going? Hi all: Just curious about which RA staff members will be at Automation Fair and/or PSUG this year? I'll be there on Thursday Nov 17. If you have an interest in discussing the Engage community, please send me an email or Teams message, and I'll try to meet up with you. Thanks! Eileen [/INST] I would really love to be able to attend this fantastic event, and meet you and all the guys who are part of the community, but unfortunately I won't be there this year... maybe next year? fuzzy logic \\n </s> |
<s>[INST] Powerflex 400 Summary: Motor high current/failureI have a Powerflex 400 Drive that is controlling a 30 HP motor and have had 2 motor failures in less than 1 month. There is no line reator installed and I don't know if it would help or not. The motor has a 1.15 service factor and I have used it numerous time without issues at other plants. The motor is loacted about 200 feet from the drive. It consistantly runs at a high current even with no load on the motor. FLA on the motor is 38 and though I initionally had about 20 amps of load; the load has increased overnight by 15. The conditions have not changed. Any idea as to why this motor may be failing? There are about 30 motors on this line and they have been running with no issues. I have now replaved the motor twice, the power cables once, and the VFD once. [/INST] I have a couple questions for you, what is the voltage of the drive and motor? What is the application you are performing with the drive and motor? A service factor rating in a motor is a rating similar to that of the OL rating on a drive, and the PF400 has an OL rating of 110% for one minute. Is there any output filtering between the drive and the motor? What type of cabling are you using? Is the motor VFD rated? Have a look at Chapter 5 of this guide; http://literature.rockwellautomation.com/idc/groups/literature/documents/in/drives-in001_-en-p.pdf It should help you to understand better what my questions are about. \\n </s> |
<s>[INST] PowerFlex 525 Sinking/Sourcing Inputs Summary: Sinking/Sourcing appears backwards in wiring schematic.In every other Rockwell product, a sinking input switches high when connected to positive voltage, and a sourcing input switches high when connected to ground or common. However, that appears completely backwards according to the schematic below. Is there any reason Rockwell decided to reverse this nomenclature? [/INST] I think the problem lies with Rockwell's incomplete explanation of the schematic. Your definition of sinking / sourcing inputs is correct, and that is what the digital input selector switch does, if you ignore the wiring outside the drive schematic footprint. The confusion, I think, arises with the typical SRC wiring and typical SNK wiring labels for the circuits outside the drive footprint (on the right). If you read those headings as this is source wiring which feeds sinking inputs and this is sinking wiring which feeds sourcing inputs then the schematic makes sense and is consistent with your definition and with all other Rockwell products. It is simply this less than fully defined schematic that causes the problem. \\n </s> |
<s>[INST] using a single servo for multiple functions I have a servo that operates a module on a machine and this module is not always used on all products. if the module (but not the servo) was removed when not in use and potentially an alternate module fitted, would it be possible to have 2 sets of parameters for the same servo? Could i load a different set depending on the product that has been selected to run enabling me to use the same servo/drive (assuming it was the correct size)? Would it be possible use two axis tags (one for each module) that would write into the selected axis tag structure upon product selection? Or would I need to make the 2 modules virtual axis that would gear to the physical axis depending upon product selection? It would be good to know any thoughts on this topic Thanks Andy [/INST] Hello Andy, So if I understand you would like to change the Axis parameters of your servo , to adapt to a different mechanical set that change depending of the production batch that you are doing... correct? If it's what you would like to do, yes it is possible , you have different options by using GSV/SSV instructions and in some cases MSG for the different parameters that you need to change , like Scaling, Tuning, inertia...etc You must do it axis disable. There is other solutions but they are mostly based on the same principal. You could also Inhibit and Un-inhibit axes... I guess you could find some info on RAKB Using the 2 virtual axis that you gear alternatively to the physical , can be a solution, if the mechanism have the same specificity , so you will not have to retune your axis (unless you have Load observer and Tracking notch to compensate if you are still in the BW of those features). Regards \\n </s> |
<s>[INST] Code 3, Type 16 error on start up - Kinetix 6K Sercos I am working on getting a new system up and running and I am having a few problems. I beleive once the first problem is fixed the other will go away. When the main circuit breaker is disconnected the PLC has a major fault on start up. The fault is a code 3, type 16. The fault is with the sercos module and the help file says to check electronic keying. The revisions do match. I even tried to disable the keying and this made no difference. Firmware in processor and sercos card match. I have tried to even re-flash each. The next problem is that I am having one of the four servos loose its position on start up. It goes to around -19,000 for a position on start up when it was at a position of 2. I do an absolute home with the all the servos and the absolute reference bit is staying set through the process. L61 with 4 Kinetix 6000 drives. Once the major fault is clear all works well untill main power is cycled. I was on the phone with tech connect this morning and no luck. Perhaps someone here has seen this problem before. [/INST] About the fault you got: Checking the box Major Fault on Controller if Connection Fails while in Run Mode in the Sercos module's properties / connection tab, will cause a major fault on the processor of Type 3 Code 16 when any fault on the sercos module occurs. For example, if the sercos ring drops out, then in the processors properties tab / Major Fault tab, you'll see Type 3 Code 16 displayed, as well as the ok led on the processor flashing red. For example it is normal for a communication error at power up because the ring takes time to phase up to phase 4 If you want to avoid this, uncheck the Major Fault check box on the Connections tab, or add a Fault Handler. - fuzzy logic \\n </s> |
<s>[INST] Power Flex 700 started running in reverse Hello, I have a 700 Power flex with vector control that was running correctly. Power was dropped to the unit during clean up. When it was brought back online the motor ran in reverse. We checked the settings and it was still in Unipolar in Direction mode. I had to change the Direction mode to Reverse Dis to get the motor running the correct direction. Checking the other parameters from our setup sheet everything was correct. Does anyone have an idea what may have caused this malfunction to happen? Could it be that drive is starting to fail? I haven't checked to see if there is a battery backup for the memory. [/INST] The most likely thing is that somebody pressed the (<- ->) direction change button on the HIM module inadvertently. I've done it. I think you are referring to Parameter 190, the Direction Mode. This has options of Unipolar, Bipolar, and Reverse Disable. The Unipolar selection means that the analog or network reference polarity will not change the direction of the drive, but that the drive logic can. Drive logic includes discrete inputs configured for direction command, or bits in a network command, or the direction button on the HIM module. When I have an application that goes in only one direction like a pump or conveyor, I always select Reverse Disable on the Direction Mode. To just prevent the HIM module from making such a change, you can mask it out with the Direction Mask parameter. At the time of the undesired operation, you might have been able to determine what input was commanding the reverse direction by reading the value of the Direction Owner parameter (parameter 291). I don't think that will show anything useful now that you have disabled reverse. \\n </s> |
<s>[INST] Servo Action Status Summary: Trying to issue a MSO or MSF while axis is in motion.I have been getting this error on a few occasions lately and this had not been a problem in the past and there has been no logic change to the servo group. My first question is where does the ServoStatusAction bit reside, I am thinking it is in the drive amp. The motion group is started and runs for whatever and then we get a fault which states what I have put in the topic summary. This is error code 22 and stems from the Motion Control Tag. For some reason the servo action status bit changes state, goes to a 0, while we are running and in a group of 7 servos this is the only one that appears to be doing this. I have changed the amp and it went away for a week or so but now it is doing it again. When this happens there is no physical fault on the drive just a fault on the motion group. Any ideas on what may be happening here would certainly be appreciated. [/INST] Your code is trying to turn the drive on while it is already on and moving. This is not a drive problem. Some part of your logic is trying to re-issue the MSO command after the drive is already on. http://literature.rockwellautomation.com/idc/groups/literature/documents/um/motion-um003_-en-p.pdf Look at the top rung of page 337 in the link above. using my_servo_axis.servoactionstatus in this manner will prevent the error you are getting. \\n </s> |
<s>[INST] Power Flex 755 Fault Codes 16 #204 , #926 Summary: Recommend to upgrade 755 firmware from 9.001 to 11.001. For a Network issue????Fault [/INST] Haven't a clue what the difference is; you could look at the firmware release notes: http://literature.rockwellautomation.com/idc/groups/literature/documents/rn/750-rn037_-en-p.pdf http://literature.rockwellautomation.com/idc/groups/literature/documents/rn/750-rn033_-en-p.pdf It very well could be they discovered a problem in 9 with memory management and fixed it in 11. I have personal experience with the early firmware releases for 755 drives running CIP motion. In version 1, the Ethernet port could only handle about 10,000 packets per second, while a simple discover query using RS-Linx could send over 30,000 packets per second. There were about 4 firmware releases in 2011 as Rockwell frantically patched serious flaws in the 755 product line. \\n </s> |
<s>[INST] Motion Analyzer V4.7 Where can I download JCalculator.exe?I have been having trouble launching from within the Crank V2.6.2 advanced template.First, I had issues (ref AID 62312)Reloaded V4.7 per AID 62312 and now Jcalculator is missing from UDAT folder. [/INST] Could it be the one in the LINK ? :smileysurprised: It is the only one I've found.... :smileytongue: Hope this helps, - fuzzy logic \\n </s> |
<s>[INST] MAFR and MASR Does not work I have upgraded an 8 axis motion system to version 32 using 1756-MO2AE analog motion control. The PLC was changed from and L63 to and L82E processor. The accuracy was greatly improved by doing this. I believe a new issue is I can not clear certain motion faults using the MASR and MAFR commands, this did seem to not give me problems before the upgrade. The most recent fault was a position error fault that MAFR and MASR commands would not clear. I also went online and used the clear axis fault that is available in the project tree, this too did not clear the fault. The only way I found to clear this fault was to unplug the Axis card and reseat. Once the card reconnected the fault was cleared. [/INST] Hi George, At the risk of sounding like a broken record, you really need to contact our Tech Support with this issue. They can best gather the information they need to walk this through to a resolution. You have not mentioned what the faults are and they will need this. They will likely need your controller project file; possibly the L63 file and the L82E file. They may also need to know if any architecture changes were made. It sounds like this is a running machine, so I would encourage to work with our skilled professionals to get it back to a reliable state. I hope you understand, \\n </s> |
<s>[INST] PF525 Alternatives....PF4 or PF40? Summary: Lead time issues with PF525 After selling a job with PF525's (due to their Ethernet IP capability) and placing the order, I am now informed of a 4 week lead time on PF525's. So, what are my alternatives? PF4 or PF40 with a COMM-E? I've never used this combination. I have 6, 2HP drives. do I need a COMM-E for each drive, or one for the whole lot? [/INST] John, there are multiple possibilities, it really depends what is needed by your application. Ethernet/IP option card is only available on PF40 / PF40P Sensorless Vector Control is only available on PF40 / PF40P Safe Torque Off is only available on PF40P (option) Closed Loop Speed Regulation is only available on PF40P Needed Power (2HP) is available for PF4M / PF4 / PF40 / PF40P About the Ethernet/IP connection, you can also have only one drive connected using the optional comm card, and then connect up to 4 other drives to it using modbus RTU, that is available for all PF4x family.... be aware that it isn't the same solution, about control possibilities and performances. - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] PF 755 Device Logix communication Summary: Error when trying to connect to device logix in drv explorer. We are currently commissioning a network of 8 PF 755 drives. We have had no issues over the development and testing until this point. We are now unable to access device logix on 7 of the drives using drive explorer. We are also unable to download to the drive using controllogix 5000. The error that shows up when downloading with controllogix is links may be locked, preventing a download. [/INST] Are you running a CIP Motion connection to these drives as well as the DeviceLogix program ? You can't run both at the same time. Is there an error code accompanying the error message ? Sometimes the precise code, like E12345-6789 can help. \\n </s> |
<s>[INST] Get Coarse Update rate in CLX I want to have the value of the coarse update rate in ms or microseconds in the CLX. I checked if I could call this value by using the GSV-instructions and did not find it. I have motiongroup updated on coarse update rate and a motiontask triggered by the event of motiongroup updated. To find a good balanceon the processor CLX execution time of the (1) motiongroup update rate itself and (2) the motion task which is logic with motion instructions, I would like to have the value called by the CLX . If possible I would also like to know if I can change the coarse update rate with a SSV, to find a better balance between both points mentioned both. Regards,FV [/INST] I have searched what you need...It isn't available in GSV or SSV instructions and also I've not found indication about a Generic CIP message that could retrive it... it seems not possible to me :smileysad: - fuzzy logic \\n </s> |
<s>[INST] Motion Groups and Axis Can a Powerflex DC Drive be defined as an axis in a motion group? [/INST] No. As far as I know, only PF 755 and PF 527 drives can be used as motion axes, and I think the PF 527 only comes through as a velocity axis. \\n </s> |
<s>[INST] Studio5000 and MPL motor with resolver Hi, I start to configure PLC for new project which required to use one servo (MPL -B320P-R). I'm using Studio5000 softwer to configure L18 controller with Kinetix 6500 modul. But there some fail was occured, because there is no option to choose this MPL motor with resolver (only H, M, S option are available). Is somebody knows what is going on, and how can I solve this problem. The stuff is ordered, so I don't want to change hardware configuration. Thank you in advance for any idea. Cheers [/INST] I found the same results through Studio 5000, but using Motion Analyser, tells me I can have a 2-pole Resolver. You'll need to place a call to tech support, I think. You could try updating the AOPs for Studio 5000, but I'm not sure there are any yet. \\n </s> |
<s>[INST] HIWIN LMS27C LINEER SERVO Hi Can i control the hiwin lms27c lineer servo motor with any AB motion product. There is a machine made with Beckhoff servo drive AX5206 . We want to revision this machine. To change the servo motor the chassis as a whole needs to be reworked for magnetic plates and servo motor. [/INST] Hello Sarici Kinetix servo drives can control many different motors type. we need more details about the motor and encoder selected to evaluate the compatibility. due to voltage, design, power, encoder technology...etc , it can be complex. So this type of sizing process are generally not supported on a community like Engage. So, Please contact our local organisation or distributor (on web page at the bottom) for a proper sizing and support during this integration. regards \\n </s> |
<s>[INST] motion fault My system is L43 and K6K*2, program is ok. But when I power up the PLC and motion at the same time , the CPU happan a fault every time. Type 11 : motion fault Code 13 : SERCOS comm fault detected. Axis : drviver1I can clear the fault by turning the key from PROM to RUN .but how can I sovle it . [/INST] Power up your PLC and then wait for the Contact Enable contact to close on the K6K, which is the drives indication that it is ready for 230/460VAC power. This will give your Sercos ring time to power up. Also make sure that before you do a MSO in your program that the drives bus is up and they are ready. There are several status bits that you can look at to ensure that the drive is ready to be enabled. \\n </s> |
<s>[INST] PowerFlex 700 and Cat 4 Safety Summary: Looking for a diagram of a Cat 4 Safety circuit with PF700Greetings all, Has anyone come across a situation requiring a category level 4 safety rating involving a PowerFlex 700? I have looked through the publication DRIVES-AP003_-EN-P, but the only cat 4 solution involves the Safe Torque Off chip, and we all know that this chip is not available in the PF700. Any and all input is well appreciated. Cheers. [/INST] nan \\n </s> |
<s>[INST] AB Powerflex 70 from Australia on African power supply Summary: Would a VFD rated for 415 - 480V run on 380V?Hello forum, I have a client that recently imported a Powerflex 70 VFD from Australia. The unit start and runs for about 30 seconds (runs well btw) and after that shuts down due to low voltage fault. I see in the manual it mentions under File E, Drive Memory Group, item 202: [Voltage Class]Configures the drive current rating and associates it with the selected voltage(for example, 400V or 480V). This parameter is normally used when downloading parameter sets. Would this setting allow the VFD to run on our 380? Is this even possible? Or is the only option a step up transformer? The installation is a plane ride and 6 hours drive away, so visiting the site is not a quick affair. Thanks in advance, Hein [/INST] It would help to know the drive part number. If this drive was purchased in Australia, it was PROBABLY a part number beginning 20ACxx. This means parameter 202 was already set for low voltage (400V). If the part number was 20ADxx then parameter 202 was set to high voltage (480V). low voltage fault - do you mean Fault 4 - undervoltage? Regardless of the parameter 202 setting, the bus voltage will give an undervoltage fault when the DC bus voltage falls below 407V in standard control, 300V in enhanced control. See page 82 of the users manual: https://literature.rockwellautomation.com/idc/groups/literature/documents/um/20a-um001_-en-p.pdf You can have your end user monitor parameter 226 (see page 55): bus volts at time of last fault. We need more information to help you: What is the drive part number What is the value of parameter 202 What is the line in voltage Does line voltage sag when this drive turns on What is the line voltage source (underpowered generator?) Is this an old drive with standard controls or does it have enhanced controls What is the motor name plate data What is the load What is the exact fault code the end user gets If the VFD is configured with parameter 202 set to low voltage, then yes, the drive should be able to run on 380VAC. Is it possible they are single-phasing the drive? \\n </s> |
<s>[INST] Maintained Contact for start?? I have a PF 400 and I thought I could confiqure it to use just a push to start momentary button and it would maintain but everytime I let go of said button it shuts down. I would rather not have a latching relay as I would need to have one more speciality item on the shelf for repairs. I would also rather not have a maintained button for the start for the same reason. Any ideas on confiquring the drive or relays would be greatly appreciated. DDP [/INST] DDP, you may want to use the configuration indicated in the screenshot... in any case you need to use another pushbutton to stop the drive... :smileysurprised: Hope this helps... - fuzzy logic \\n </s> |
<s>[INST] braking resistance (resistencia de frenado) EF-Translated title and question into English to give the original question a better chance of being answered. FL-moved to Drives community friends I was looking at several manuals to incorporate a braking resistance in a Power Flex 755 but I do not understand, they could help me [/INST] PowerFlex Dynamic Braking Resistor Calculator 750-In03 Post Glover catalog \\n </s> |
<s>[INST] Ultra3000 Using ultra3000 drives with a Sercos Interface on Clx, is there a way to get the fault code displayed on the front of the drive into a PLC register? Thanks [/INST] Yeah I would like to know about this also! If anyone has any clues!:manwink: \\n </s> |
<s>[INST] PowerFlex 700S Hour Meter Is there a way I can pull an hour meter of any kind off this drive? Thanks [/INST] I'm not sure to have correctly understood the request.... :smileysurprised: The only Hour meter I know inside a PF700s is related to the total time the drivehas been RUNNING.... Elapsed Run Time par 298. Hope this helps… - fuzzy logic \\n </s> |
<s>[INST] (S45 Fault) Feedback DataLoss Factory Limit Over Fault Hello All, I've seen S45 fault for 9 months this year. Our system configuration is VPL (VPL-B0631T-CK12AA) with Kinetix5700. Actually, we are running that axis without S45 fault for 1.3 year. But we saw higher frequency occuring trend after 1st fault. (2nd fault 60days, 3rd fault 30days, 4th fault 10 days...) We did actions to solve S45 fault. Cheked grounding, cable/connector status, torque and so on. But there's no specific clue. In the end, we've not seen S45 fault after motor/cable replacement. But I don't know hardware was a root cause of this fault. Because we didn't see any fault during 24/7 offline test using disassembled drive/motor and cable. Do you guys have similar experience? And do you knot the correct meaning and definition of feedback data loss factory limit over? Also, how is the relation ship between factoru limit and user limit? We've trouble situation because S45 fault can't be setup as status-only or alarm. It always connect to line stop whe the fault is occured. Plese help me solve this problem. [/INST] Hello Hans I understand your concerns and I will give you some information and direction for your investigation. The Servo fault S45 Motor Feedback Data Loss occurs because the number of consecutive missed or corrupted serial data packets from the feedback device has exceeded a factory set limit. Basically, communication was not established with an intelligent encoder, either due to misconfiguration, or some sort of hardware problem. the S45 fault can have multiple causes. the fact that you are not able to reproduce the error in offline test can be explained. Because the test is not executer in the same machine environment, with same cable length, with same FW, with same noise environment, cable damaged, banding radius, EMC skin effect ...Etc The RSSI : on the inverter display you can access to different menu. In Diagnostic and them encoder Diagnostic you will found multiple information (they can vary depending of the FW... with new FW you have more information's) . to read the diagnostics your drive and motor must be part of an application. The RSSI indicate the quality of the signal (look at the manual Multi-Axis Control Servo Drives Technical Documentation | Rockwell Automation).This RSSI is a very good indicator of the signal quality. You can also access the diagnostics via the drive web interface with an ethernet browser (make sure that the WEB is enable in the drive display interface)... this more convenient and you can take screenshot. with the webpage you can also access to the extended fault (FaultSubCode) Rockwell Knowledge base : check the different article related to S45 fault . (some example bellow) https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/1125944 https://rockwellautomation.custhelp.com/app/answers/answer_view/a_id/585056 you can't modify the limits or Change the status of this error to my knowledge So check the encoder diagnostics with the system in place , and check the different recommendations in the links provided above. regards \\n </s> |
<s>[INST] PowerFlex 70. Migrating from 20-COMM-D to 20-COMM-E. Retaining original VFD's. I have an MCC full of PowerFlex 70s that I need to cut over to Ethernet. I need to retain the existing drives. Does anybody have any experience, how-to's, or input as how to proceed. Stratix 5700's in place, cables pulled. Just need to swap the comms modules and make them work. [/INST] What controller are you using? I would suggest making sure the ethernet switch is configured prior to attempting the switchover. I feel like I fight them (Stratix5700) a lot during initial commissioning. Regards, RM \\n </s> |
<s>[INST] Pflex 755 Homing Can someone briefly explain to me how and what profiles the vfd uses when issuing a Find Home? [/INST] Don't know about brief, but I think this technote should thoroughly answer your question: Homing the PowerFlex 750 Series AC Drive (non CIP) QA22067 Hope it helps. Regards, RM \\n </s> |
<s>[INST] Allen Bradley 1336 + Is it possible to make a 1336 drive reverse itself if the current goes up on drive. If the screw starts binding up and current goes up drive would reverse and go the other way. [/INST] You could set the CR relay ( Par 158, 174-176 ) to 7 current limit or 5 at current and latch a off delay timer ( reverse time as the CR relay does not latch ) with the contact to I/p3 set as Rev / Fwd.To get the screw away place a time in Par 327 Start At time delay \\n </s> |
<s>[INST] Kinetix 6500 module faults Summary: Spurious module faultsHere's hoping someone can help! I've been trying solve issues with spurious 'module faults' on a system with 7 axis. The faults have occurred across nearly all the servo drives, all with the same outcome; Once the servo axis has detected a module fault, an alarm is generated in the PLC and the system stopped. However, all the drives are seen to be healthy with no faults both on the drive display and via RS Logix 5000. Could this be a firmware issue? [/INST] What is the coarse update period for the motion group? These errors sound like it is too small. If you did not set the coarse update period, the default is 2 milliseconds. I would probably double it for your 7 axes, unless you have other motion axes as well (such as a PF755). I might even set it to 5 milliseconds to ensure no timing problems. \\n </s> |
<s>[INST] PF700 Fault Alram.. If PF700 shows fault or alarm, I couldn't know when that alarm happened. Because PF700 just shows total inverter running time with alarm message. So I need yy/mm/dd/hh/mm/ss like this type for reporting. Please change it by firm-ware upgrade or other method. [/INST] I agree with Sungjong. I have often experienced somes frustrations while troubleshooting because PowerFlex 700 doesn't timestamp the default. Adding this feature would be welcome. \\n </s> |
<s>[INST] powerflex 4 Summary: control powerIs there a parameter for the 24v control power to be internal or will an external power souce be required [/INST] It depends by how you will wire your drive. Terminal 11 could be used to supply internal 24Vdc power to Digital Inputs; drive will output 100 mA maximum through that terminal. Please take a look to User Manual chapter 1, you will find informations and wiring examples for either internal or external power source. \\n </s> |
<s>[INST] Powerflex 700 VC Series B Firmware I can't run the .msi files for the Powerflex 700 VC Ser. B fimware V6 or V7. All other .msi files work (PF 70EC, 20-COMM-E and 20-COMM-Q). It returns an error that states it is not a valid windows installer package. I have tried on 3 different PCs and it doesn't work on any of them. Any help? [/INST] Just tried downloading from the following link: http://www.ab.com/support/abdrives/webupdate/firmware/PF700VCB_7_001_165_Update.msi It downloads as .txt file, just removed the .txt extension, leaving .msi.... it works fine for me. Here attached the file I've used (inside a .zip file) Let us know.... - fuzzy logic \\n </s> |
<s>[INST] Ultra 3000 e24 We have several ultra 3000 drives but only have trouble with a couple. During warmer weather we start getting E24 excess velocity error. We have changed the cables, motor and drive with another set-up and the problem doesn't follow the parts. Has anyone else had this problem? [/INST] I suggest to review the following technotes: Aid 47229 - Aid 49946 - Aid 61948 Please be aware a TechConnect Authorization is needed to access all the above technotes... - fuzzy logic \\n </s> |
<s>[INST] PowerFlex 750 Series VFD, DriveLogix, and PanelView Plus Summary: Looking to see if the PowerFlex 750 series VFD can directly communicate with any type of PanelView Plus HMI.We are investigating the use of DriveLogix in a PowerFlex 750 series VFD. We will be using both Discrete and Analog I/O boards. We want to have a PanelView Plus HMI (Component, Standard, or PV+ 6) interface with the VFD and DriveLogix probably over Ethernet/IP, but that’s still up in the air. Does anyone know if this possible and if so where can I find documentation or maybe some examples? [/INST] I don't believe you will be able to develop and run a FTV application without a CPU controller such as DriveLogix. And DriveLogix is not offered but an option for the PF700S Phase II VFD series only; PF753(750) offers the DeviceLogix option which is a configurable, embedded I/O interface. If a 5730DriveLogix EtherNet/IP option is chosen with a PF700S Phase II VFD, then you could develop and run your FTV(ME/SE) application on the subnet bridged by the DriveLogix EtherNet/IP interface. http://literature.rockwellautomation.com/idc/groups/literature/documents/um/20d-um003_-en-p.pdf For the HMI application: http://literature.rockwellautomation.com/idc/groups/literature/documents/um/viewme-um004_-en-e.pdf \\n </s> |
<s>[INST] Torque Control parameter list in PowerFlex 700 Hi,The parameter list in PowerFlex 700 AC Drives User Manual Series B, Vector Control Firmware 4.001 & Up Series B, Vector ControlFirmware 4.001 & Up Catalog 20b-um002_-en-p doesnt list the torque control parameters like 526, 527, 528 etc shown in the torque control blcok diagram http://www.ab.com/support/abdrives/powerflex700/PF700_Block_Diag_6-03.pdf I am wondering where can i have the details about these parameters. Thanks and regards Jai [/INST] Try to take a look inside the Reference Manual appendix... http://literature.rockwellautomation.com/idc/groups/literature/documents/rm/pflex-rm004_-en-e.pdf - fuzzy logic \\n </s> |
<s>[INST] Powerflex 755 loses Motion parameters Summary: PF-755 loses motion parameters during communication faultWe have a Powerflex 755 with Motion control , connected to clx to en2tr having L85 as processor Software is studio 5000 with version 32 Normally we have the drive working fine with motion control , however some times when there is communication failure , the drives motion parameters get lost and we need to reprogram it again . I tried checking for ADC but cant see in the drive properties where the ADC option is present , i guess for 755 with CIP motion , the ADC configuration is not present . Any suggestions on this [/INST] When using a PF755 in CIP motion, ALL parameters come from the processor. You cannot program the drive directly (such as with CCW or DriveExecutive). Are you saying the PLC is losing the parameters defined in the axis properties page of the ControlLogix triee? You do not need ADC for such an application; in fact it can be a real hassle sometimes. When a Logix processor connects to a PF755 in a CIP motion environment, it downloads ALL parameters necessary. If you are setting parameters in the drive, then starting the processor, all the work you did setting the parameters gets wiped out by the PLC. This is a feature of Logix, not a bug. In this way, all programming happens within the logix environment. Call it one-stop programming. You do not have to set up logix programming, then motion programming in a different environment, then drive parameters in a third environment. \\n </s> |
<s>[INST] Drives forum is now OPEN TO THE PUBLIC! Rockwell Automation is very happy to announce that access to the Drives and Motion forums are now open to the public. Now, you no longer need to have a support contract to converse with your peers on Drives and Motion related issues! A step long requested by you, our customers, we sincerely hope this will provide a valuable way for customers to help each other. Please feel free to post to this thread with any feedback you have on this change. Joshua HutchinsonRockwell Automation Forums [/INST] nan \\n </s> |
<s>[INST] I have some HMI screens that I did in CCW and I did the PLC program in RSLogix 500 Pro, how can I do it if I want to simulate everything together? [/INST] RSLogix 500 Emulate can communicate with a panel thru the virtual DF1 serial port. CCW doesn't provide a Test Application feature for PanelView 800. So, it is not possible to test together.\n </s> |
<s>[INST] Kinetix 6000 E19 Summary: 2094-BM01-S showing E19we have replaced 2094-BM01-S with new same module. old was working fine but when we install new module, shows error E19 when RUN. Do we need to make some changes in configuration? or it should be plug and play? [/INST] E19 is position error fault. It's likely you have not hooked up the encoder cable or the power cable correctly. Go through the terminations on the drive very carefully. \\n </s> |
<s>[INST] Powerflex 525 Output Voltage Hello, I am looking to use a PowerFlex 525 drive with a 480 VAC 3 phase input, and use it to drive a 220 VAC 3 phase motor. In the manual it says the output voltage is 0 .. rated voltage. Does this mean that I can use the PowerFlex change both the voltage and the frequency? I've never done it before but if I can save on buying a transformer I would like to. [/INST] You'll set that up in the motor nameplate data. Remember the output current of the drive will be more on 230V motor than for 480v at the same size. \\n </s> |
<s>[INST] PowerFlex We have a 40HP 480 volt three phase squirrel cage motor that draws 47 AMPS-what size PowerFlex drive would handle that? Thank you [/INST] There are many different models of PowerFlex drives, the selection could be related to your application needs (Heavy / Normal duty, Intermittent Overload, desidered options etc...) I suggest to review the following: Drives comparisonApplication ShowcaseSelection Guide The last document contains useful selection tables, where you may find the correct drive for the required current of your motor application. - fuzzy logic \\n </s> |
<s>[INST] gearing Summary: Servo MAG to local encoderhave a machine with several Kinetix 350's connected to a CompactLogix L33-ERM processor. Have no problem gearing them together, or to an Ether/IP encoder. Can't seem to find method to gear to an encoder connected to a local HSC module. Any suggestions? Thanks, Bob [/INST] In short - YOU CAN'T. The master encoder has to come into the logix system either as a CIP-Motion encoder, or in one of several drives which take auxiliary encoders (the K2K, K6K drives do). CIP-Motion encoders are expensive enough that it's cheaper to purchase the least-expensive K350 drive and bring the encoder into the system there. Don't bother with a servo motor, just connect your encoder to this drive. \\n </s> |
<s>[INST] Ultraware installation issue Summary: When trying to install Ultraware ver. 1.64 an error message appeared at the end.Hi, I am trying to install Ultraware ver. 1.64 over Win XP Pro, I have done this before without issues but this time I am getting the message general error occurred at the end of the installation, the only notorious difference is that the laptop into I am trying the installation doesn't have an embedded serial port. If someone knows a patch or something to workaround with this issue I would appreciate it. [/INST] Try to read the following topic about the same issue: http://forums.rockwellautomation.com/comment/13139 - fuzzy logic In order to enhance Forum's contributors reputation, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] Powerflex 70 - Wanting to start in manual mode after power failure Having a problem where after a power failure the drive reverts back to auto. Help would be greatly appreciated, cheers! [/INST] Unfortunately this is a known behavior: A workaround could be the use of a Digital Input configured to do this selection, but there are some things to be aware of... I suggest to take a look to Aid 38345 (TechConnect Authorization required) and see if it helps... - fuzzy logic \\n </s> |
<s>[INST] Using a 842-CM-MIP3BA Encoder to perform a follow Summary: Sample code req to create follow with encoder.Hello All Hopefully somebody out there has already performed this and may have some sample code. I am using a 842E-CM-MIP3BA Encoder to Follow a press. The encoder drives a motor that is installed in an off line m/c(( the motor is controlled from a 2198-H040ERS2 Drive)& the motion is controlled from a 1769-L18ERM-BB1B CONTROLLER)). I have Studio 5000 ver32.(I,m new to this so still learning) All I simply want to do is drive the motor from the encoder and if required change the motor direction and follow ratio. Any help would be appreciated guys. [/INST] Congratulations - you correctly selected a CIP motion Ethernet/IP encoder. It's very easy to NOT get it and you would not be able to take advantage of it in CIP motion. The encoder will be a CIP motion axis and you can issue a few commands to it, such as MAH and MRP. MAH only works if the homing tab of the axis is configured to be immediate. The axis can then be used as a master axis for camming or electronic gearing. In your case, it looks like MAG (motion axis gear) would work well. While it's a somewhat simple application, CIP motion is not all that simple. There's a lot to motion, more than can really be answered in a few forum posts. If you have a good local Rockwell representative or good Rockwell distributor, they should be able to spend an hour to help get you started. \\n </s> |
<s>[INST] How to Re-Enable Kinetix 300 after a fault (w/o a laptop)? I am trying to connect basic momentary buttons for operating the Kinetix 300 (to run a MPAR cylinder in indexing mode). Everything works as expected except for 2 things. 1) If you get into a fault mode or use an e-stop, I can push a button to reset that fault and that works fine (using the digital input set to reset faults). But it does not re-enable the drive. I have found NO way to enable the drive again without connecting to the drive with my laptop, and switching the enable switch field from run to inhibit then back to run again. 2) Once I manually enable the drive with the software, how do I get the cylinder rod to go back to zero. Using homing functions just resets the current position the rod is at to 0, it doesn't move the rod back to the 0 position that I have already defined (which I want at the fully retracted position). I want a button I can push and have the drive retract the rod all the way. Thanks in advance for any help you can provide. [/INST] Take a look at this knowledgebase article: https://rockwellautomation.custhelp.com/app/answers/detail/a_id/67873 Additionally, look at page 93 of the user manual: http://literature.rockwellautomation.com/idc/groups/literature/documents/um/2097-um001_-en-p.pdf How do you have your enable switch configured with parameter 29? The table defines two configurations. Also look at parameter 78 shown on page 200, reset fault configuration. \\n </s> |
<s>[INST] Power flex70 fault code F511 Summary: Fault code F511I would like to know about power flex 70 Fault code F511? For the system we use controlnet communication (20ComC) and config this port is ( 5 ). Cat no.of power flex is 20A5P0A0AYNANC0 For this code we can't reset [/INST] According to the 20-COMM-C manual, page 199 http://literature.rockwellautomation.com/idc/groups/literature/documents/um/20comm-um003_-en-p.pdf event 11 means Another peripheral with the same port number is already in use. Do you have another option card installed? \\n </s> |
<s>[INST] Would like to run 1-Powerflex755 drive from two HIM modules, two locations, is this possible Summary: Have a test stand that our engineers want to be able to control from two different locations, can we install a HIM at the drive and one remotely and set them up so they dont interfere with one another [/INST] Hi George All powerflex drives can take 2 HIMs, a local and a remote (DPI port 1 and port 2). The local HIM is normally installed on the face of the drive and the remote is plugged into the DPI port on the bottom of the 755 main control board. An extension cable to the remote him can be used part#1202-C30. For remote HIMs I would use the 20-HIM-C6S. There is also a wireless options 20-WIM-N1 and 20-WIN-N4S that may offer even more flexibility, but I haven't tried those. I would download the manuals to see what they can offer. This may allow the drive mounted HIM to be remote as well. The 2 HIMs can be set up using masks in Parameters (P324 - P328) to allow / deny certain functions by selecting / deselecting DPI 1 and 2. The speed reference source can selected by putting the HIM into manual mode to control the motor speed. Also check out Manual Preload (P331) for remebering/transferring the speed reference. A digital input on the drive can also be used for switching between speed reference sources when there is more than one but I don't think you need that in this instance. (P173-175), Regards Damian \\n </s> |
<s>[INST] PF525 EMC Filter - Internal vs External Is there a performance difference between the EMC Internal Filter vs the EMC External Filter? [/INST] Hi , Best performance is achieved by using a filtered drive and the appropriate external EMC filter. EMC filters reduce the transfer of electromagnetic noise between the drive and mains power supply. PF525 drives are fitted as standard with an internal EMC filter (240V , 480V) and for most industrial applications, this will be sufficient. In the event that a higher level of filtering is desired or required, the external EMC filter can be added to either a drive which already has the internal EMC filter, or a drive without EMC filter. Most electronic equipment will generate electrical noise, small unwanted disturbances which may be conducted back onto the mains power supply. Drives basically designed to minimise this noise transfer, and offer high levels of Electro Magnetic Compatibility. Where required, additional (External) EMC Filters may be added to further reduce the level of noise transferred back to the mains power supply, reducing the risk of other equipment being affected. however where highly sensitive equipment is used, or a reduction in the electrical noise is required, these External EMC filters can be fitted in line with the drive to reduce the conducted noise emission. *****Welcome your suggestions***** \\n </s> |
<s>[INST] Torque vs.speed curve on MPL servo motor Summary: Why I can't find the curve about torque and speed. Where I can find curve between torque vs. speed about MPL motor just for my selection based on caculated result data on mechanical part? [/INST] You can use Rockwell's free tool Motion Analyzer to do this: http://ab.rockwellautomation.com/Motion-Control/Motion-Analyzer-Software It's not a small download, but it IS a very good tool for sizing Rockwell servos. \\n </s> |
<s>[INST] Kinetix 5700 single turn encoder Summary: how to retain single turn encoder value after power cycleHow to retain Encoder value of single turn encoders to simulate as Absolute Position Encoder at power cycle event in Kinetix5700 drives? What is the tag for single turn encoder value feedback on kinetix5700 drive? [/INST] There is axis.ActualPosition; this element is going to be in user units defined by your scaling in the axis properties page and will be type REAL. In the axis properties page, Drive Parameters branch, Parameters to be read each cycle, there is a PositionFeedback1 entry. If you check that box, it gets added to the axis tag elements. This element is type DINT. This is not what you need though. You have a servo motor with incremental encoder attached to a K5700 drive. You have to set up scaling in the axis properties page. The Logix processor running this axis is going to work in user units, so axis.ActualPosition is all that you need. In the axis properties page, HOMING branch, set homing mode to active and immediate. Position doesn't matter so leave it at 0; you're going to overwrite the position. Motion will not occur when you issue an MAH with this configuration. use a MOV command to store axis.ActualPosition in tag LASTPOSITION, with logic that allows this MOV only after a startup routine has completed. This instruction should scan every PLC scan. On first scan, clear the bit that says startup routine has completed so that you do not lose LASTPOSITION. Have your startup routine issue an MAH. The axis.axishomedstatus bit gets set. When the MAH.PC bit goes true, issue an MRP with position LASTPOSITION. When the MRP.PC bit goes true, you can now set your startup routine complete bit so that the MOV instruction above begins storing the position again in anticipation of the next power cycle. The axis position is what it was at the final scan before the power cycle. \\n </s> |
<s>[INST] PowerFlex40 Regenerative Load Summary: What (if any) is the regenerative load passed to the incoming AC LineMy application is powered using a generator. The end user is concerned that the drive will pass the regenerative load back to the generator causing problems with the generator's voltage regulator. The equipment is Powerflex40 with line reactor and external dynamic brake. (There are three motors which are all set up the same (motors are 1.5 HP (2) and 1.0 HP (1)). What is the regenerative load that could be passed back to the generator and (if present) how can it be limited? [/INST] The front end of the PF40 drive is diode so there is no way to get the regen back onto the line. The bigger problem with running a drive on a generator is the non-linear load. The drive does not draw current from the source through the entire sinewave of the incoming voltage. This causes voltage and current distortion. Basically it comes down to the generator needs to be oversized for the load. What is the load that it will have regen? This drive will handle some regen, but it is not the best drive for a lot of regen. It can have problems with bus regulation. \\n </s> |
<s>[INST] 20-750-ENETR EDS FILE Hi! I would like to know if you could help me with the EDS file for the 20-750-ENETR communication card, I was checking the official Rockwell website and I couldn't find it. The inverter that I bought is 20FIAND186JA0, with the 20-750-ENETR card, the communication will be with another brand of PLC and I do not have the STUDIO 5000 software to be able to obtain it from the card [/INST] Welcome to Engage! Here is the link to PCDC website, already filtered for latest firmware version of that card: https://compatibility.rockwellautomation.com/Pages/MultiProductFindDownloads.aspx?dlpop=1&id=54307&crumb=112 Clicking Select Files you can see the available downloads: fuzzy logic Please don't forget to LIKE and highlight the decisive answer: REPLY > Make Best Answer \\n </s> |
<s>[INST] 1394 controllers ... RoHS compliant? How do you find out if the device is RoHS compliant? [/INST] Ah, another one I can answer. (Be careful, folks, that makes two in a row! :smileywink: ) AID 40015 JHutchRockwell Automation Moderator \\n </s> |
<s>[INST] E-Stop Control Circuit Integration and CSA Z432 [/INST] Ouenuga, The use of a Safety Relay with the E-Stop button will satisfy the requirement of needing a separate Reset button input to be able to re-engage the motor starter. However a safety relay alone will NOT ensure that motor power is removed in the event of the motor contactor welding. A Safety Relay only removes power from the contactor coil. It is difficult to interpret what they may mean by this, but in some assessed safety requirements, it is necessary to have two contactors in series; one as part of the motor starter that is turning the motor on and off in the course of regular operations, and a second Safety Contactor ahead of it that only opens in response to the Safety Relay, so is thereby less subject to the conditions that might cause it to weld. The Safety Contactor is not a regular motor starter in this case, it is specifically rated as a Safety Contactor, having what are called “force guided contacts” and bearing specific approvals. These type of requirements would be outlined in a Safety Assessment of your machine by a qualified individual. Most of these machine safety requirements come from IEC requirements, Canada has apparently adopted them almost directly, the US is still indirect in that matter. Although none of this is specifically REQUIRED yet by NFPA 79, it is accepted as a compliant solution if implemented. However to be compliant with CSA Z432, the Safety Assessment is I believe prescribed (I'm not Canadian but I have read the document and outlines this in the first part of it). \\n </s> |
<s>[INST] Running a Kinetix5700 drive on 120V AC. am new to the community. I teach at The Ohio State University and am using a PLC workstation with an integrated Kinetix 5700 drive. The drive has been wired to 120V AC for power instead of 240V. I have been told that to use the K5700 with 120 AC there is a specific procedure/code that allows the 5700 to use 120V, but I haven't been given the procedure or code. Does anyone know what the procedure is? [/INST] You are right for demonstration purpose we have a Demo Mode that can be enable. But we do not provide those details on Social media. If the Kinetix module that you interested in operating in Demo Mode is a part of a Rockwell Demo Box/Unit, the unit comes with all needed software to be able to operate the module in Demo Mode. If the accompanying software that is included with the Demo Box/Unit is lost or misplaced please contact your Rockwell distributor that provided the Demo Unit to you. So please contact your local Rockwell Automation office.\n </s> |
<s>[INST] The CS3000 data base does not support the connected drive (version V6.5) Only limited functionality... Summary: Problem of backup GV3000 SeriesNow i work with Reliance GV3000 series drive and i have some problem. 1. Key pad is out of order. Where i can buy GV3000 key? 2. When i connect GV3000 series with CS3000 software version 6.14 (Download from ab web), the software show The CS3000 data base does not support the connected drive (version V6.5) Only limited functionality will be available. Continue with connect?. How can i solve this problem? Thank in advance. [/INST] Or reliance are die product? AB leave support from this product? Why so silent in this forum? Unlike like siemens forum. \\n </s> |
<s>[INST] need to add pf70 rev 5.1 to aop I have added a pf70 rev 5.1 vfd to my controlnet, but the aop only goes to rev 4.1. How can I upgrade to rev 5.1 without using the web update feature? My pc cannot be connected to the internet. [/INST] You may download the latest Drives AOP from the following link: http://www.rockwellautomation.com/support/downloads.html This can be done on another PC you've connected to the internet, then installed on your PC. - fuzzy logic \\n </s> |
<s>[INST] POWERFLEX 755 HIP - CAT NO 20G1AJD545AN0NNNNN Summary: Please can you assist us with a detail manual for the above subject and how to configure it in RSLOGIX 5000.Hello All, Please can someone assist me with how to setup POWERFLEX 755 HIP-CAT NO. 20G1AJD545AN0NNNNN, in Please can you assist us with a detail manual for the Drive and how to configure it in RSLOGIX 5000 as MASTER ans SLAVE follower using ethernet TCP/IP communication. [/INST] http://literature.rockwellautomation.com/idc/groups/literature/documents/rm/750-rm002_-en-p.pdf http://literature.rockwellautomation.com/idc/groups/literature/documents/pm/750-pm001_-en-p.pdf http://literature.rockwellautomation.com/idc/groups/literature/documents/um/750com-um001_-en-p.pdf These are the places to start. That said, a 545-amp, 450-HP drive is not the place to begin learning. I strongly suggest you acquire the services of a competent integrator or specialist. Such an integrator can help you and provide training while maintaining safety and avoiding risk of damage to your drive. \\n </s> |
<s>[INST] 2198 - Kinetix 5500 drive capacitors issue? EDIT: corrected the title to better reflect the thread content and reduced picture size to allow better view -FL I bought 2198-H025-ERS2 recently, and this is the product I received from the distributor. The distributor doesn't know if that is normal or not and so do I. Does anyone know what causes the problem and should I return it? [/INST] Although it is hard to diagnose an issue through a picture, what this appears to be is conformal coating splatter on the capacitor. Normally when a capacitor is compromised or goes bad, either through high current or heat, it will tend to bulge, which this capacitor does not show signs of. Ken \\n </s> |
<s>[INST] rotery motor hello i work with kinetix 6000 and a motor how drive a plateau with 8 steps. each step = 45deg. When the motor turns 1 time around the plateau turns 3deg. My start position (he gives) 215 not zero. i thought count (+45deg offset) every time. but when he goes up 360deg he gives error. or is it something like this: (215 - 215) + X This X first time 0deg afther this every time +45deg. but how i go from 360deg to the home step? can someone help me ? [/INST] Hans, sorry, I'm having difficulties understanding your problem. It sounds like you have a rotary table driven by a motor. You want the table to index 8 steps in a machine cycle, each step is 45 degrees. The table moves 3 degrees for each motor revolution. Have I stated it correctly? If that is true, you have a 15:1 reduction ratio between the motor and the table, correct? To take full advantage of integrated motion within Logix5000, you should be putting some of those parameters into the axis definition so that your motion commands work in terms of real, useful units. Putting the 15:1 reduction ratio into the axis definition will let you issue motion commands in degrees of rotation of the table. Can you tell us what error you are getting? Just telling us that you're getting an error isn't enough; there are a lot of possible motion errors. Can you upload your logix 5000 ACD file for us to look at? \\n </s> |
<s>[INST] SERIES A Drive Cat No. 22A-DP0N104 Summary: Under VoltageHi, I have a client who currently used this kind of Drive: Cat No. 22A-DP0N104 SERIES A Motor Rating: 1.5Kw/2.0HP Input: 3 Phase, 380-480V, 46-63Hz AC Voltage Range: 342-528V Amps: 5.7A Output: 3phase, 0-240Hz Ac Voltage Range: 0-460 Continuous Amps: 4.0 60 Sec Ovld Amps: 6.0 My question is: 1) If the incoming voltage is 380V, can this type of inverter run in healthy condition? 2) What will be happening if the voltage reaches below 380V? 3) What is the minimum voltages for this inverter? 4) Will the amps (input/output) increase if the voltage decrease(below 400V)? 5) What does it mean by 'AC Voltage Range: 342-528V' ? Regards, Aziz [/INST] The specs are fairly straight forward. The inverter will run normally if you are able to maintain the voltage anywhere within 342-528V. The inverter takes that 3-phase input voltage, converts it to DC voltage (approximately 1.4 times the AC voltage). It then chops the DC voltage up to simulate an AC signal out to the motor. To answer your questions: 1) This inverter can easily run on 380V. 2) The data sheet says you will get a bus-undervoltage fault if the DC bus voltage drops to around 390Vdc, equivalent to about 275Vac line input voltage. That's a pretty significant sag if the nominal voltage you expect to give it is 380. I would try to keep the input voltage above the recommended 342Vac, but you do have a good margin. 3) I'd treat 342 as the minimum, but you can go lower without causing a bus-undervoltage fault. 4) You'd likely see a larger current draw, but if you size your overcurrent protective devices according to the specifications given in the datasheet for the drive, you should not see any problems. 5) We've covered the lower end of the voltage range. If you supply this drive with any voltage that is between these two limits, the drive will operate as expected. 480Vac is a common voltage. This AC input will give a DC bus voltage of 672V. This is well within the operating range. The drive will report a bus overvoltage if it reaches 810V (about 575 Vac input). NOTE: The drive uses the DC bus for regeneration when slowing the motor and load down. If a drive is running at the higher end of the ac input range, and slowig a heavy load down, the energy put back into the DC bus could cause it to fault with a bus over-voltage. From the theme of you questions though, I don't think you'll be working at the higher range. TJ McDermott \\n </s> |
<s>[INST] Torque Setting I have a Allen Bradley 1336F drive where I would like the drive to stop on high torque or current. At present the motor runs between 9.5 - 10 Amps so I would like it to stop at a setting of say 11.0 amps after a given time, is this possible? This is the first time I have used this make of drive so I could do with the help to create this please.Dave [/INST] Hi Dave, try to take a look to the User Manual, page 6-28 ... you may configure the Output relay either to At Current or At Torque as indicated.As far as I can remember, there isn't a way to have the Relay act with a delay. Hope this helps, - fuzzy logic \\n </s> |
<s>[INST] Usage of Single VFD (Power flex 750) for two Different Motor Applications Summary: Usage of Single VFD (Power flex 750) for two Different Motor ApplicationsIn One of My Project, I have two different Motors Applications. I want to control both the Motors with the Single VFD (Power Flex 750), since both the application are having same expected Performance Characteristics and both are operating at different Timings without any time overlap. I do have one contractor panel to switch between one motor Circuit to another motor circuit How feasible to use this technique? Please let me know is there anything need to be taken care while designing this concept ? Thanks, Mani [/INST] I believe this scenario could be implemented only if the two motors are identical and the VFD Load side switching contactors are mechanically interlocked and operated while the VFD is passive. The VFD running application needs to know the motor's nameplate data first and then the field application's requirements. \\n </s> |
<s>[INST] PowerFlex DC Summary: PowerFlex DC executive fileHi All, could you please provide me with a .Dno file (executive file configuration file according to attached drawing) many thanks in advance. [/INST] nan \\n </s> |
<s>[INST] Kinetix 6500 going into STANBY after power cycle Summary: Kinetix 6500 going into STANBY after power cycleWe have 2 kinectix 6500 that run 2 movable conveyors. Occasionaly when one of the drives faults and we cycle the power to the drives one of the drives comes back up in STANDBY mode. The only way to fix the STANBY state is to download the program. We have the lasted firmware update. Any Ideas [/INST] First determine the fault and put logic into the processor to recover from the fault. The fault can be determined either from going online with the processor, clicking on the faulted axis, and then viewing the axis status in the quick view pane lower left corner of the project organizer. Or reading the fault code on the front of the drive and consulting the trouble shooting section of the manual. If it were me I would power down the panel,remove the control module, and reseat it a couple of times and see if the issue goes away. Sometimes the connections are contaminated from handling during panel build and the control module just needs to be reseated. http://literature.rockwellautomation.com/idc/groups/literature/documents/um/2094-um002_-en-p.pdf \\n </s> |
<s>[INST] MPAR Electrical Cylinders Good Morning! I was looking over the MPAR electrical cylinders and was wondering if someone could help me with something. When looking, I was mainly focused on the 100mm and 200mm stroke cylinders. My issue with these is that one is too long while the other too short when it comes to the project I am working on. So, my question is, does anyone know of a way to have a custom 150mm stroke cylinder quoted? Any help would be appreciated. Thank you! [/INST] Hi Skyler, I want to understand your question a little better. Is the problem that the 200mm model won't physically fit into your design? Because that unit can be programmed to only extend to 150mm, if needed. Please let me know. Otherwise, if you truly need a 150mm unit, please engage with your local Rockwell or Distributor representatives to work this angle. Thanks, \\n </s> |
<s>[INST] 525 Drive Safety Open Enable - Paramter 105 Summary: Fault Disable/Fault Enable Functionality Can someone explain the difference parameter 105 Fault Enable vs. Fault Disable in a 525 drive? If I set parameter 105 to fault enable and remove jumper between terminals S+, S1 & S2 the drive faults. If I set parameter 105 to fault disable and remove jumper between S+, S1 & S2 I get same results. Also, in both cases, drive must be powered down then powered back up to clear fault. Thanks [/INST] Welcome to the Forum ! Inside the following technote, you can find a detailed description of its operation. 550198 - Relationship between Safety Inputs and Safety Hardware Fault or Safety Open Fault - fuzzy logic In order to enhance the reputation of the Forum's contributors, please rate the replies you got and remember to close the thread clicking Choose as Best Answer button over the solving answer. Thanks ! \\n </s> |
<s>[INST] PowerFlex Not Enabled- STS is flushing Yellow Hi all, I have problems with PoweFlex. STS LED is flashing yellow and as I can see from the display the driver is Not Enabled. I have checked in User manual it say if Flashing yellow Flashing, Drive Stopped : A start inhibit condition exists, the drive cannot be started. Check parameter 214 [Start Inhibits]. Flashing, Drive Running: An intermittent type 1 alarm condition is occurring. Check parameter 211 [Drive Alarm 1]. Steady, Drive Running: A continuous type 1 alarm condition exists. Check parameter 211 [Drive Alarm 1]. But there is nothing about Not Enabled..Also I can not start the drive..I have checked parameter 214 it is Fault but I can not change this parameter. Please help Aleks [/INST] Hi, first of all we have to say Param. 214 is a read-only, so you cannot change it... which of the bits are on in that parameters ?Did you configure a Digital input as Enable ? In that case you have to have 24 volt on it to enable the drive...Did you remove the hardware enable jumper from the drive board? Please check the above and post again the complete reading from Param. 214 to get more help... - fuzzy logic \\n </s> |
<s>[INST] Setup Powerflex 40 in Connected Components Workbench (CCW) Summary: Initial setup of Powerflex40 drive using USB to RS485 converter and CCW.How do I connect the Powerflex 40 drive using RS485, and set it up in Connected Components Workbench (CCW). I don't see instructions in the users manual. I see there are various add-on modules, but I just want to use a USB to RS485 converter, and splice it into the RJ45 jack. How do I get CCW to discover it using Connection Browser? I went to Configure Drivers, and I don't know if I should use 1784 PKTX(D)/PCMK for DH+ and DH485 or DH485 UIC Devices or another one? Do I need to setup anything on the drive first? Thanks, Greg Windows 10, CCW version 12.00.00 Standard [/INST] I see the users manual is saying you can use Drive Explorer application, but I think RA wants everything to move to CCW. Nevermind, I just set it up through the front panel, would be nice to know for future reference, but this issue is resolved. \\n </s> |
<s>[INST] Clarifing Sinking and Sourcing on the 700S Here are the questions that I have about the Power-flex 700S phase II drive. I will be using an external power supply source and NOT the drive internal power supply from Terminal [/INST] wow... pretty long question ! :smileyvery-happy: Yes, you're right, there is a type-o on that manual... :smileysurprised: In order to see the correct version, download the following : PF700S ph II User Manual - page 1-27 (here attached is a screenshot) Also, what you explain you want to realize is correct; you're sinking the digital outputs...again take a look to the attached image. Hope this helps... :smileywink: - fuzzy logic \\n </s> |
<s>[INST] Power Flex 700 Is it possible to remove the HIM from a Power Flex 700 without faulting Drive??? [/INST] Yes, it is... :smileyhappy: Have a look to the following technote... Aid 41437 - fuzzy logic \\n </s> |